Kohler — Mount the communication module board in the DEC 3+ controller
Installation
From a Kohler service manual covering: APM402, APM603, APM802, Decision-Maker 550, GM32644-KP1, GM62466-KP1, GM91356, KPC 1000, MPAC 1000, MPAC 1200, MPAC 1500, MPAC 750. Check it applies to your exact model before use.
Applies to: Kohler APM402, Kohler APM603
Before you start
- Requires DEC 3+ controller logic (red) circuit board GM28725.
Procedure
- Remove the existing three nuts attaching the indicator panel circuit board; leave the washers in place.
- Attach the three spacers to the indicator panel circuit board studs.
- Position communication module board GM49791-1 on the spacers.
- Install three lock washers (X-22-7).
- Install the existing three nuts on the spacers to secure the communication module board; do not overtighten.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.