Cummins/Onan HDKB Generator Set

The Cummins/Onan HDKB is a 150 kW diesel standby generator set. It is available at 120 V, 120/240 V and 230 V, 50 Hz and rated 41.7 A. It holds about 1.9 L (0.5 gal) of oil and 2.8 L (0.7 gal) of coolant. Starting uses battery rated 650 CCA at 12 V. The set measures 876×581.2×514.4 mm (34.5×22.9×20.3 in), weighs about 181 kg (399 lb) and produces 68 dBA at 3 m.

150 kW
Standby
1.9 L
Oil capacity
5
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 150–155 kW Diesel generators →

Compare with other 150–155 kW Diesel generators →

Service parts for the HDKB

Grouped by system, with how many of each the parts manual calls for.

Cooling system

1 required
FS1006Coolant filter$29.99eBay

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power150 kW
Prime power5 kW
ControllerA1, EC-AGS+
Oil capacity1.9 L
Voltage options120 V, 120/240 V, 230 V
Rated current[41.7, 20.8] A
Circuit breaker[25, 25] A
Battery cranking650 CCA
Battery voltage12 V
Coolant capacity2.8 L
Dimensions (L×W×H)876×581×514 mm
Dry weight181 kg
Sound level68.0 dBA @ 3 m

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filter—375 hr
Fuel filter—250 hr
Oil filter—1000 hr
BatteryCranking batteries—800 hr
Belt—625 hr
Coolant2.4 liter—
Coolant filterFS1006500 hr Amazon eBay $29.99 NAPA $90.16
Oil1.9 liter—50 hr
Spark plug—1000 hr

Service intervals

35
ItemActionHoursMonthsNotes
Oil levelCheck8 hrCheck oil daily or every 8 hours of operating time; perform a general inspection daily per Operator's Manual
Engine oilChange50 hrFirst service — Break-in: change engine oil after the first 20-50 hours of operation (RV QG/RV QG RM); perform at least once a year
Genset service (first service interval, all models)Other50 hrFirst service — First service interval is 50 hours for all models.
Coolant Anti-freeze ProtectionTest150 hrFootnote 3 - at least once a year
Engine Air FilterReplace150 hrFootnotes 1,3 - more often in dusty conditions; at least once a year
Engine Oil and Oil FilterChange150 hrFirst service — Footnotes 1,2,3 - more often in dusty/hot conditions; at least once a year
Fuel FilterReplace500 hrFootnotes 3,7 - at least once a year; every 250 hours when using B20 bio-diesel
Genset serviceOther250 hrFirst service — GEN TYPE QD 7.5/8 (Quiet Diesel 7.5/8 kW; model HDKAx)
Genset service — GEN TYPE GAS RV (Camp Power)Other150 hrEC-30 service hour meter interval
Genset service — GEN TYPE GAS/LP (Marquis, Microlite, Micro Quiet)Other150 hrEC-30 service hour meter interval
Genset service — GEN TYPE QD 5.5 (Quiet Diesel; model HDKBx)Other150 hrEC-30 service hour meter interval
Genset service — GEN TYPE QD 6/8 (Quiet Diesel; model HDKAx)Other150 hrEC-30 service hour meter interval
Spark ArrestorClean150 hr1 moFootnotes 3,6 - at least once a year; must be performed by a trained and experienced mechanic
Genset service — GEN TYPE QD 10/12 (Quiet Diesel; models HDCAx, HDKCx)Other250 hrEC-30 service hour meter interval
Coolant SystemDrain500 hrFootnote 4 - flush at least once every two years
Coolant anti-freeze protectionCheck500 hrFootnote 3 - at least once a year (Page 3-8)
Coolant Hoses and ThermostatReplace1000 hrFootnotes 5,6 - at least once every five years
Coolant Pump V-beltReplace1000 hrFootnotes 5,6 - at least once every five years
Coolant pressure capReplace1000 hr24 moFootnote 4 - replace every two years (Page 3-8)
Coolant systemOther1000 hr24 moFlush Coolant System; footnote 4 - at least once every two years (Page 3-8)
Engine V-belt (coolant pump)Replace1000 hrFootnotes 5,6 - every five years; trained mechanic (Page 8-11)
Engine Valve LashAdjust1000 hrFootnotes 5,6 - at least once every five years
Fuel injectorsOther1000 hrService Fuel Injectors; footnotes 5,6 (Page 8-1)
Generator Bearings, Drive Belt, Belt Tensioner & Drive CouplingInspect1000 hrFootnotes 5,6 - at least once every five years
Generator bearings, drive belt, belt tensioner & drive couplingCheck1000 hrFootnotes 5,6 (Page 7-1)
Drive beltReplace2000 hr60 moor if cracks, worn spots or other deterioration
Generator BearingsReplace2000 hrReplace bearings if they have been in service 5 years or 2000 hours
Generator rotor bearingsReplace2000 hr60 mo5 years or 2000 hours
BatteryClean1 moEvery Month; perform more often in hot weather (footnote 2)
Battery & connectionsClean1 moClean & check battery & connections; perform more often in hot weather
Battery and battery connectionsClean1 moEvery Month; footnote 2 - perform more often in hot weather (Page 3-5)
Oil/oil filter - Quiet Diesel 10000/12500ChangeFirst service — Break-in then repeat (footnotes 1-4, 2-4)
Oil/oil filter - Quiet Diesel 5500ChangeFirst service — Break-in then repeat (footnotes 1-4, 2-4)
Oil/oil filter - Quiet Diesel 7500/8000ChangeFirst service — Break-in then repeat (footnotes 1-4, 2-4)
Spark arresterClean1 moClean arrester; perform sooner if engine performance deteriorates

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceBrush length (minimum, replace brush block)7/16inch (11 mm)
ClearanceGovernor Actuator Rotor Travelabout 1/2inch (12 mm)while cranking
GapBrush minimum length7/16 inch (11 mm)inchreplace brush block if shorter
Injection timingFuel Injection Timing18°-20°BTDC
Injection timingFuel Injection Timing (BTDC)18 - 20degrees
Injection timingFuel Injection Timing (timing marks)19° BTDC
Injection timingFuel Injection Timing Marks19degrees BTDCmarks line up
Injection timingFuel injection timing18-20degrees BTDC
Injection timingFuel injection timing marks line up19degrees BTDC
OtherAUTO GEN disabled if safety input not verified30days
OtherDC Control Fuse F130amp mini-bayonet
OtherDimensions L x W x D80.98 x 130.12 x 30.48mm (3.188 x 5.125 x 1.20 inches)
OtherEC-AGS+ gateway dimensions120 x 108 x 38mm
OtherFuel delivery flownot less than 0.4 pints (200 ml)per minute
OtherFuel lift pump flow0.4 pints (200 ml) per minutepints per minuteminimum during prime
OtherFuel system prime time1minuteHold control switch in Stop position (starts in 2 seconds)
OtherGenset off delay with no run request10minutes
OtherMinimum genset run time in automatic modes10minutes
OtherPower output change with altitude3.5% decrease per 1000 ft increasetypical power output change based on ambient conditions
OtherPower output change with temperature1% decrease per 10 degF increasetypical power output change based on ambient conditions
OtherQuiet Time pre-fill genset start2hours prior to beginning of Quiet Time
OtherSafety input re-verify prompt25daysdisplay flashes the SAFETY OFF & ON screen
OtherSpark arrestor cleanout plug7/16inch square head
OtherTemperature sensor dimensions51 x 70 x 17mm
OtherTime @ START V range5-60secondsdefault value is 15 seconds
OtherTime @ STOP V range1-60minutesdefault value is one minute
OtherTypical current draw47mA @ 12V
PressureCooling System Pressure14psi
PressureEngine oil pressure14 psi (98 kPa)psiminimum, engine running
PressureFuel Delivery Flow (return)0.4 pints (200 ml) per minute minimumpints per minuteHolding control switch at STOP (Prime) for exactly 1 minute
PressureFuel Nozzle Injection Pressure1991psi (13.73 mPa)
PressureFuel nozzle injection pressure1991 psi (13.73 mPa)psi
PressureLow oil pressure switch threshold14psi (98 kPa)
PressureMinimum Engine Oil Pressure14psi (98 kPa)
PressureSpark arrestor cleanout plug7/16 inch square head
ResistanceCoolant Temperature Sender E4approximately 800ohmsat room temperature
ResistanceCoolant temperature sender E4 resistance800ohmsroom temperature
ResistanceGateway harness continuity maximum resistance10Ohmsrepair or replace harness if greater
ResistanceGovernor Actuator Terminals1.7 - 2.8ohms
ResistanceGovernor actuator terminals resistance1.7-2.8ohms
ResistanceRotor Winding Insulation to Groundless than one megohmohmsmegger/highest ohmmeter scale (replace if less)
ResistanceRotor Winding Resistance31.97ohms@ 77° F (25° C) ± 10%
ResistanceRotor field winding resistance31.97ohms@ 77 F (25 C) +/- 10%
ResistanceRotor winding F1-F2 (A053L824)29.8 ± 3ohms at 77 F (25 C)
ResistanceRotor winding F1-F2 (A053M356 / A053R511)28 ± .5ohms at 77 F (25 C)
ResistanceRotor/stator winding insulation to ground1megohm (minimum)megger test
ResistanceStator Winding B1-B2 (120/240 VAC, 60 Hz)0.124ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding B1-B2 (230 VAC, 50 Hz)0.112ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding Q1-Q2 (120/240 VAC, 60 Hz)2.42ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding Q1-Q2 (230 VAC, 50 Hz)2.89ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding T1-T2, T1-T3, T2-T3 (3-Ph, 240 VAC, 60 Hz)0.97ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding T1-T2, T1-T3, T2-T3 (3-Ph, 400 VAC, 50 Hz)0.35ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding T1-T2, T3-4 (120 VAC, 60 Hz)0.153ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding T1-T2, T3-4 (120/240 VAC, 60 Hz)0.612ohms@ 77° F (25° C) ± 10%
ResistanceStator Winding T1-T2, T3-4 (230 VAC, 50 Hz)0.692ohms@ 77° F (25° C) ± 10%
ResistanceStator winding B1-B2 (120 VAC, 60 Hz)0.124ohms@ 77 F (25 C) +/- 10%
ResistanceStator winding B1-B2 (3-Ph, 240 VAC, 60 Hz)0.303ohms@ 77 F (25 C) +/- 10%
ResistanceStator winding B1-B2 (3-Ph, 400 VAC, 50 Hz)0.418ohms@ 77 F (25 C) +/- 10%
ResistanceStator winding Q1-Q2 (120 VAC, 60 Hz)2.42ohms@ 77 F (25 C) +/- 10%
ResistanceStator winding Q1-Q2 (3-Ph, 240 VAC, 60 Hz)2.73ohms@ 77 F (25 C) +/- 10%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 ethylene glycol based antifreeze and waterMix thoroughly before adding; use clean soft tap water, distilled water or pure rain; select high quality antifreeze with corrosion inhibitors
Coolant50/50 mixture of ethylene glycol anti-freeze and waterFully formulated with rust inhibitors and coolant stabilizers; use fresh water low in mineralsabove -37°C2.9 literSuitable down to -34° F (-37° C); Spec section states 2.3 quart (2.2 liter) capacity
Engine oilSAE 10W-30 / 10W-40 / 0W-30 / 5W-30Use viscosity chart to select grade for expected ambient temperature range; avoid mixing grades or brands
Engine oilSAE 15W-40API CF, CF-4, CG-4, CH-4, CI-4 or CJ-4 (diesel)OnaMax 15W-40 #326-5336; multi-grade recommended year-round in liquid-cooled engines; synthetic oil not recommended
Engine oilSAE 15W-40 (multi-grade recommended for year-round use)API Class CH-4 or better1.9 literChoose viscosity grade per ambient temperature expected until next oil change; capacity with filter
Engine oilSAE 15W-40 (multi-grade recommended year-round)API CF, CF-4, CG-4, CH-4 or CI-41.9 LRefill quantity 2 quarts (1.9 liters). In emissions-regulated areas CF/CF-4/CG-4/CH-4/CI-4 with low/ultra-low sulfur fuel is mandatory; with high-sulfur fuel change oil and filter twice as often.
Engine oilSAE 15W-40 (multi-grade)API CF, CF-4, CG-4, CH-4 or CI-41.9 L2 quart (1.9 liter) with filter. CF class recommended for high sulfur fuel in non-regulated areas. Select viscosity grade per ambient temperature (Figure 1-2).
Engine oilSAE-30API SJ, SL or SM (gasoline)OnaMax SAE-30 #326-5339; preferred summer grade for optimum oil consumption control in air-cooled engines
FuelASTM No.2-D / No.1-D / No.2-DLS / No.1-DLS / B5 Biodieselminimum Cetane number 45No.2-D or No.2-DLS above 23 degF; No.1-D or No.1-DLS below 23 degF; B5 Biodiesel above 50 degF; use No.1 diesel below 32 degF and during long light-load periods; cloud point at least 10 degF below lowest expected fuel temperature
FuelGrade 2-D S500 or 2-D S15 diesel; Grade 1-D below 14°F (-10°C)ASTM D975 or EN 590Minimum cetane 45 (50 below -4°F/-20°C or above 5000 ft/1500 m); sulfur max 500 ppm (15 ppm from 2010); lubricity ASTM D6078 min 3100 g or D6079/ISO 12156-1 max 0.45 mm scar; B5 bio-diesel suitable
FuelGrade 2-D S500 or 2-D S15; use Grade 1-D S500 or 1-D S15 below 14 F (-10 C)ASTM D975 or EN 590; bio-diesel B5-B20 per ASTM D7467 (bio component ASTM D6751 or EN14214)Minimum Fuel Cetane Rating 45; minimum 50 below -4 F (-20 C) or above 5000 ft (1500 m). Max fuel sulfur 500 ppm (0.05% weight); do not exceed 10,000 ppm (1.0% weight).
FuelHD-5 grade liquid propaneat least 90% propaneFuels other than HD-5 can contain more than 2.5% butane causing poor vaporization/starting below 32 degF
FuelNo. 2 diesel (ASTM 2-D) above freezing; No. 1 diesel (ASTM 1-D) below freezingASTM 2-D / ASTM 1-DCetane number of at least 45 for reliable starting
FuelRegular unleaded gasolineEthanol blend not more than 10% ethanol; methanol blend not more than 5% methanolUse fresh gas, not more than 30 days old; fuel stabilizer extends fuel life
Greasemolybdenum disulfide pasteOnan PN 524-0118 or equivalentFor bearing bores in end bell and adapter
OtherCummins Onan Premium Fuel System Cleaner12.0 ozTreats up to 24 gallons of gasoline; #326-5342
OtherOnaFresh GXLP fuel stabilizer16.0 ozTreats 40 gallons of gasoline; #326-5365

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

23
CodeNameMeaningSeverityAction
1High engine temperatureEngine coolant temperature exceeded 230° F (110° C)ShutdownFlush coolant system, check level, clear air openings, reduce load, test thermostat and sender E4
12Overvoltage FaultThe controller is not able to regulate to rated voltageShutdownTest output voltage; test windings; replace controller A1
13Undervoltage FaultThe controller is not able to regulate to rated voltageShutdownReduce loads; service brushes and slip rings; test windings; replace A1
14Overfrequency FaultThe controller is not able to regulate to rated frequencyShutdownCheck/reset tripped genset circuit breaker and run with fewer loads; check fuel/air leaks and prime; inspect governor actuator; replace controller A1.
15Underfrequency FaultThe controller is not able to regulate to rated frequencyShutdownTurn OFF line breaker; check fuel level and leaks, prime; check air filter; replace fuel filter; fuel pump flow test; inspect governor actuator; readjust high idle speed; service fuel injectors and injection pump; check injection timing.
19Governor actuator faultThe controller sensed that the actuator circuit is either open or shortedShutdownReconnect leads; check resistance 1.7-2.8 ohms and replace stator; check wiring
2Low oil pressureThe low oil pressure switch is closed (grounded)ShutdownCheck oil level; test oil pressure 14 psi minimum; replace switch S2 or controller A1
22Governor overloadThe duration of operation at or near full-duty cycle was beyond the design limitShutdownReduce loads; check fuel and filters; readjust high idle; service injectors
24Temperature sender faultThe controller sensed that the sender circuit is either open or shortedShutdownTighten terminal on sender E4, test sender resistance, check continuity between P1 Pin 21 and E4-1.
27AC voltage sense faultThe controller was unable to sense output voltageShutdownCheck continuity between Pin 33 and Pin 34; on 3-phase gensets test voltage sense transformer T15; service brushes and slip rings; test windings; replace controller A1.
29High battery voltageThe controller sensed battery system voltage greater than 19 voltsWarningReconnect 12 volt batteries in parallel; select lower boost charge rate
3Service checkA second-level fault occurredWarningPress Stop to blink the second-level shutdown code
32Low cranking speedCranking speed less than 100 rpm for more than 12 secondsShutdownRun the vehicle propulsion engine while starting; clean and tighten battery connections; recharge or replace battery; replace engine oil with oil of proper viscosity for ambient temperatures.
35Control card faultMicroprocessor EEPROM error during self-testShutdownReplace controller A1.
36Engine stoppedThe genset stopped without a command from the controllerShutdownCheck fuel, air leaks, filters, pump, field/quadrature circuits, governor actuator; service engine
37Invalid Set ConfigurationContinuous 'Stop' input connected to Ground or MAT sensor input not OpenShutdownCheck for open wire connections for continuous Stop and MAT sensor.
38Field overloadField voltage exceeded 150 VDCShutdownReduce the number of air conditioners running (and other low power factor appliances); check appliances for proper operation; service brushes and slip rings; test windings.
4Overcrank FaultCranking without starting exceeded 20 to 30 seconds, depending on ambientShutdownCheck fuel, air leaks, air filter, fuel filter, fuel pump flow, glow plugs and governor actuator
41Shorted rotorThe rotor circuit is shorted to groundShutdownCheck continuity between Pin 1 or 14 and B-; repair or replace wiring, brushes and slip rings or rotor as necessary; replace controller A1.
42Processor faultMicroprocessor ROM error during self-testShutdownReplace controller A1.
43Processor faultMicroprocessor RAM error during self-testShutdownReplace controller A1.
45Speed sense faultController unable to sense quadrature frequencyShutdownCheck fuel level, prime and restart; service brushes and slip rings; test field, stator and quadrature windings.
57Overprime FaultPrime mode exceeded 3 minutesWarningCheck for and remove any object that may be holding either control switch (remote or local) in the prime (stop) position.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting Frequency adjustment
  1. Remove access cover on left end of genset.
  2. Find leads marked J8 HZ, 60 HZ and 50 HZ in harness.
  3. Connect 60 HZ or 50 HZ lead to J8 HZ as appropriate.
  4. Secure access cover with 4 screws.
Adjusting High-Idle Speed adjustment

⚠ Keep hands away from the engine belt and pulleys.

⚠ The actuator could overheat if the battery is left on more than 10 minutes.

Tools: Strobe or injector clamp-on tachometer, 12 volt battery, Battery switch

  1. Adjust the speed control lever stop.
  2. Measure engine speed with a strobe or injector clamp-on tachometer.
  3. Disconnect the actuator leads and connect a 12 volt battery to the actuator terminals using a battery switch.
  4. Switch the battery on, start the genset, measure speed and stop the engine by switching off the battery.
  5. Readjust high-idle speed if not between 3300 and 3400 rpm.
  6. Repeat until high-idle speed is between 3300 and 3400 rpm and set the lock nut.
Adjusting Speed Control Lever Stop adjustment

Tools: Wrench

  1. Remove front and top panels for access to adjusting screw.
  2. Loosen stop screw locknut and back screw out a few turns.
  3. Turn stop screw in until it just makes contact and set the locknut.
Adjusting Valve Lash adjustment

⚠ Do not use the fuel injection timing marks when adjusting valve lash.

  1. Remove the top panel for access.
  2. Rotate the engine clockwise until the intake valve push rod just stops moving down.
  3. Turn the engine half a turn more.
  4. Set lash for both valves at 0.0059 - 0.0073 inch (0.145 - 0.185 mm).
  5. Repeat this procedure for the other cylinder.
Adjusting Voltage adjustment

⚠ Hazardous voltage; stand on a dry wooden platform or rubber insulating mat and use insulated tools.

Tools: Accurate AC voltmeter and frequency meter

  1. Disconnect all generator loads and connect accurate AC volt and frequency meters.
  2. Start the genset and let voltage and frequency stabilize 5 to 10 seconds.
  3. Rapidly press the control switch to START 6 times within 10 seconds.
  4. Press START and release quickly to raise voltage about 0.6 volt each time.
  5. Press START and release in 1 second to drop voltage about 0.6 volt each time.
  6. Normal operation resumes 20 seconds after the last adjustment.
Setting GEN TYPE adjustment

⚠ GEN TYPE sets the service interval for service messages and critical automatic starting parameters.

  1. Navigate to the SETUP & INFO display and press ENTER.
  2. Navigate to the SETUP GENSET display and press ENTER; the GEN TYPE is displayed.
  3. Press SET; the display will flash.
  4. Use the UP/DOWN key to select the GEN TYPE and press ENTER when the appropriate type is displayed.
Setting Quiet Time (QT) Start & End adjustment

⚠ QUIET ON mode prohibits the genset from automatically starting between the start and end of Quiet Time.

  1. Use the UP/DOWN key to navigate to the QT START or QT END display; the current setting is shown.
  2. Press SET to change the setting.
  3. Use the UP/DOWN key to change the value.
  4. Press ENTER to store the new time.
Setting Safety Type adjustment

⚠ If it has not been setup (SafeType NONE), automatic operation will not be allowed.

  1. Use the UP/DOWN key to select the correct type of safety input: Ignition, Brake, or Park.
  2. Press ENTER to store in permanent memory.
Setting the Hour-Meter (SET Gen Hour) adjustment

⚠ ENTER to unlock prevents unauthorized changes to the hour-meter.

  1. Check the hour-meter on the genset and record the reading.
  2. Enter the SETUP & INFO menu and navigate to the SETUP GENSET display; press ENTER.
  3. Use the DOWN key to select the SET Gen hour's display; press SET.
  4. Press ENTER at the ENTER to unlock display to continue.
  5. Hold down the UP/DOWN key and scroll until the left-most digit matches the desired value.
  6. Release the UP/DOWN key and wait four seconds for the underline to move to the next digit; scroll to its desired value.
  7. Set each successive digit to the right until the correct genset hours are displayed, then press ENTER to store.
Fuel Delivery Test diagnostic

⚠ Diesel fuel is combustible; keep flames and sparks away.

Tools: Quart (1 L) container

  1. Disconnect fuel return hose; point end into a 1 liter container.
  2. Hold Start/Stop switch at STOP (Prime) for exactly one minute.
  3. Flow should not be less than 0.4 pints (200 ml) per minute.
  4. If low: replace fuel filter, check restrictions and air leaks, replace pump.
Installation and Setup Test diagnostic
  1. Verify generator set operation using the Start/Stop switch located on the generator set.
  2. Verify manual start/stop of the generator set from the app dashboard using the START and PRIME/STOP buttons.
  3. Check operation of the temperature sensors with Auto mode and Air Conditioning Sense enabled.
  4. Verify the generator set starts automatically when the settings are met.
  5. Verify the accelerometer by driving the vehicle at 10 mph and checking that AGS is automatically disabled.
  6. Verify delayed shutdown: enable AGS, allow the generator set to start, disable AGS, confirm shutdown in 10 minutes.
Run Gen Test diagnostic

⚠ The sequence can only be interrupted by manually stopping the genset using the STOP switch.

  1. Verify the location is safe for running the genset and that its installation is completed.
  2. Navigate to the display that says ENTER to Run Gen and press ENTER.
  3. The EC-30 goes through a complete start and stop sequence and displays results as the test happens.
  4. When the test is complete the display says Gen Ok ENTER; press ENTER to exit back to ENTER to Run Gen.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
AC Present + positive#14Positive input for shore AC present sensing; do not connect 120VAC or 240VAC line voltage.
AC Present - ground#13Supplied by UL Listed 120VAC to 12-16VAC transformer, or the 12VDC ground side of a UL Listed 120VAC to 12VDC plug-in power supply.
Battery Ground (Negative)Wire #1Supplies ground/negative side of the circuit for the EC-20; must be supplied from the genset.
Battery ground (negative)#1Supplies the ground or negative side of the circuit for the EC-30; must be supplied from the genset.
Genset Status LightWire #6Diagnostic output from the genset that flashes the red light in the START/STOP switch; decoded by the EC-20 to display a text fault message.
Genset status light#6Diagnostic output that flashes the red light in the START/STOP switch to indicate a genset fault; decoded to a text fault message.
Not UsedWire #4
Start/PreheatWire #3Supplies start/preheat signal to the genset; controlled by the STOP/START switch and in automatic mode by the EC-20.
Start/preheat#3Supplies the start/preheat signal to the genset; controlled by the STOP/START switch and, in automatic mode, by the EC-30.
Stop OutputWire #2Active low or grounded output supplying the stop signal to the genset; controlled by the STOP/START switch.
Stop output#2Active low or grounded output to the genset; controlled by the STOP/START switch and, in automatic mode, by the EC-30.
Switched B+ From GensetWire #5Switched to battery positive when the genset is running; provides genset hour-meter and running signal.
Switched B+ from genset#5Switched to battery positive voltage when the genset is running; provides genset hour meter and running indication.
12Request HVAC active low#4Active low or ground input; requires a transition from +12V to ground to activate the auto-gen start function.
12Run request HVAC #1#10Must supply +12V to the controller when the HVAC system requires the genset to run.
12Run request HVAC #2#11Used with a second HVAC unit; must supply +12V to the controller when the HVAC system requires the genset to run.
12Run request HVAC #3#12Used with a third HVAC unit; must supply +12V to the controller when the HVAC system requires the genset to run.
12Safety input +12V#16Positive input to the safety circuit; treat like a relay coil input or light bulb; if supplied with a negative input connect #16 to +12V.
12Safety input - negative#15Voltage across the input must change from 0VDC to 12VDC or 12VDC to 0VDC when the vehicle is parked; if supplied with a positive input connect #15 to negative.
12-24Engine battery sense#9Optional; positive sense voltage for the engine starting battery; connect directly to the battery; 5A inline fuse.
12-24House battery sense#8Positive sense voltage used for the house battery voltage display and state-of-charge indicator; connect directly to the battery; 5A inline fuse.
12-24VDCEngine Battery SenseWire #9Optional positive sense voltage for the engine starting battery; only displayed if connected; connect directly to battery; 5A inline fuse.
12-24VDCHouse Battery SenseWire #8Positive sense voltage displayed as house battery voltage and used for state-of-charge indicator; connect directly to battery; 5A inline fuse.
8-35Power + (VDC)#7Positive power supply to the EC-30; must be protected by a 5A inline fuse located as close to the battery or source as possible.
8-35VDCPower +Wire #7Positive power supply to the EC-20; protect with a 5A inline fuse located as close to the battery/source as possible.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Cummins/Onan HDKB?

The Cummins/Onan HDKB is rated 150 kW standby.

What fuel does the Cummins/Onan HDKB use?

The Cummins/Onan HDKB runs on diesel.

What is the cooling system capacity of the Cummins/Onan HDKB?

The Cummins/Onan HDKB cooling system holds 2.8 liters (0.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

How much oil does the Cummins/Onan HDKB take?

The Cummins/Onan HDKB has an engine oil capacity of 1.9 liters (2.0 US quarts), per the manufacturer specification sheet.

What is the prime power rating of the Cummins/Onan HDKB?

The Cummins/Onan HDKB is rated 5 kW prime, against 150 kW standby.

How loud is the Cummins/Onan HDKB?

The Cummins/Onan HDKB is rated at 68.0 dBA at 3 m, per the manufacturer specification sheet.

What is the dry weight of the Cummins/Onan HDKB?

The Cummins/Onan HDKB has a dry weight of 181 kg (399 lb).

What voltage does the Cummins/Onan HDKB produce?

The Cummins/Onan HDKB is offered in 120 V, 120/240 V, 230 V.

What battery does the Cummins/Onan HDKB use?

The Cummins/Onan HDKB uses 12 V each, 650 CCA, per the manufacturer specification sheet.

Troubleshooting

6

Fault codes

CodeMeaning
Code 1Engine Over Temperature
Code 2Low Oil Pressure
Code 3Service Check

Symptoms & remedies

SymptomRemedy
Exhaust leak or any danger of exhaust gases entering or being drawn into the vehicleShut down the genset and have it repaired before operating again. Check for openings or holes between the genset compartment and vehicle cab or living space if engine sounds louder than usual, close off or seal such openings to prevent exhaust gases from entering the vehicle.
The genset stopsDoes the genset operate correctly from the genset controls? If it does not, the problem is in the genset, not the EC-20 controller. See the genset Operator, Installation, and Service Manuals.
The indicator light in the Start/Stop switch turns offConfirm that the correct connection diagram (Figures 5 - 7) was used, then check EC 30 wiring connections. Confirm that the correct voltages are present on each terminal. Check all terminal connections on both ends of the wiring harness. Are harness connectors properly joined?

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan HDKB troubleshooting guide (18 entries) →

Parts

1
Part #DescriptionQtySystem
FS1006Filter, Fuel Water Separator2Fuel filter Amazon eBay $29.99 NAPA $90.16

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
0.930.25
50%1.570.41
100%2.510.66
Full-load2.510.66
Full-load100%2.040.54
Half-load1.570.41
Half-load50%1.230.32
No-load0.740.2

Available documents

Spec sheet — PDA-1581 (Cummins/Onan)Reference — 981-0650 Onan HDKBB HDKBC Installation Manual (1-2014) (Cummins/Onan)Owner's manual — Onan-EC-AGS Manual (Cummins/Onan)Parts manual — 0058719 (Cummins/Onan)Parts manual — Cummins Onan Commercial Mobile Accessories 1 (Cummins/Onan)Parts manual — F-1123 Cummins-Onan RV Generator Handbook (08-2007) (Cummins/Onan)Service manual — 900-0541B-energy-command-operation (Cummins/Onan)Service manual — 900-0543 Onan Energy Command 20 Operators Installation (1-2006) (Cummins/Onan)Service manual — 900-0621 Onan HDKBA HDKBB Repair Times (Cummins/Onan)Service manual — 981-0183 Onan HDKBB HDKBC Operator's Manual (2-2015)Service manual — 981-0535 Onan HDKB (spec A-F) Diesel RV Genset Service manual (01-2010) (Cummins/Onan)Service manual — 981-0535 Onan HDKBA HDKBB Mobile Genset Service manual (10-2002) (Cummins/Onan)Service manual — 981-0633B Onan HDKBA Installation Manual (6-2003) (Cummins/Onan)Service manual — 981-0634B Onan HDKBB Diesel Genset Installation manual (06-2003) (Cummins/Onan)Service manual — HDKBA, HDKBB, HDKBC Service Manual (Cummins/Onan)

This page was generated from the 15 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Coolant filter FS1006$29.99
1 priced item$29.99