Cummins/Onan — Run Gen Test

Testing & diagnosis · EC-30 genset start/stop outputs

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan HDKA, Cummins/Onan HDKB, Cummins/Onan HDKC

Before you start

  • The sequence can only be interrupted by manually stopping the genset using the STOP switch.

Procedure

  1. Verify the location is safe for running the genset and that its installation is completed.
  2. Navigate to the display that says ENTER to Run Gen and press ENTER.
  3. The EC-30 goes through a complete start and stop sequence and displays results as the test happens.
  4. When the test is complete the display says Gen Ok ENTER; press ENTER to exit back to ENTER to Run Gen.