| AC Sens Loss | AC Sensing Lost | AC sensing lost in Auto mode; warning after 1 sec if no output after crank disconnect, shutdown after 3 sec if voltage was present then lost | Warning | Contact an authorized distributor/dealer for service |
| ATS ComError | ATS Communication Error | RXT interface connection is lost | Warning | Check communication wiring between transfer switch interface board and generator set |
| ATS PhaseRot | ATS Phase Rotation Mismatch | Transfer switch phase rotation does not match; ATS will not transfer | Warning | Correct the ATS connection per installation manual, wiring diagrams, and labels |
| Accy PwrOver | Accessory Power Overload | Over current fault (short circuit) on the accessory controller power output | Warning | Contact an authorized distributor/dealer for service |
| Aux Input | Auxiliary Input | An optional customer-connected input is closed (digital input from optional PIM) | Shutdown | Check customer-supplied equipment |
| Battery CrLo | Critically Low Battery Voltage | Battery voltage falls below 11V for more than 10 seconds; inhibited during crank | Warning | Check battery rating/condition and charger operation; charge or replace battery |
| Battery High | High Battery Voltage | Battery voltage rises above 133% (16V) of the battery voltage setting for more than 10 seconds | Warning | Check battery rating/condition and charger operation |
| Battery Low | Low Battery Voltage | Battery voltage falls below the battery voltage setting (typically 12.5V) for more than 90 seconds when engine is not running | Warning | Check battery rating/condition and charger operation; charge or replace battery |
| Chk DateTime | Verify Date Time Setting | The time and date have not been set on the generator controller | Warning | Enter the date and time using the RDC2 controller |
| CoolTemp Vhi | Ect Higher Than Expected 2 | Coolant temperature is extremely high | Shutdown | Check coolant level; check radiator/fans for obstruction; contact dealer with fault code |
| CoolTempHigh | Ect Higher Than Expected 1 | Coolant temperature is too high | Warning | Check coolant level; check radiator/fans for obstruction; contact dealer with fault code |
| Coolant Lvl Low | Low Coolant Level Shutdown | The coolant level switch input has been activated | Shutdown | Check coolant level; check radiator hoses for leaks; contact dealer |
| CoolntTemp 0 | Coolant Temp 0 Shutdown | ECM reported coolant temperature sensor problem: 0 = high temperature | Shutdown | Check coolant level and radiator/fans; contact dealer with fault code |
| CoolntTemp 3 | Coolant Temp 3 Shutdown | ECM reported coolant temperature sensor problem: 3 = high voltage | Shutdown | Contact an authorized distributor/dealer for service and provide the fault code |
| CoolntTemp 4 | Coolant Temp 4 Shutdown | ECM reported coolant temperature sensor problem: 4 = low voltage | Shutdown | Contact an authorized distributor/dealer for service and provide the fault code |
| CoolntTemp 5 | Coolant Temp 5 Shutdown | ECM reported coolant temperature sensor problem: 5 = open circuit | Shutdown | Contact an authorized distributor/dealer for service and provide the fault code |
| Crank Lost | Crank Signal Lost | Crankshaft Position Sensor (CPS) timeout error occurred | Warning | Contact an authorized distributor/dealer for service and provide the fault code |
| ECM warnings | ECM warnings (any warning with ECM in the fault name) | Group of faults that originate from the engine ECM and contain ECM in the fault name | Warning | Contact an authorized distributor/dealer for service and provide the fault code |
| Emerg Stop | Emergency Stop Shutdown | The emergency stop switch has been activated, or there has been an open circuit in the wiring | Shutdown | Contact an authorized distributor/dealer for service |
| Eng Speed High | High Engine Speed | Engine speed exceeds 115% of normal running speed for more than 0.3 seconds | Shutdown | Contact an authorized distributor/dealer for service |
| Eng Speed Low | Low Engine Speed | Engine speed drops below 85% of normal running speed for more than 3 seconds | Shutdown | Reduce the load; contact an authorized distributor/dealer for service |
| Exer Not Sch | ATS Exercise Not Scheduled | No exercise has been scheduled on the RDC2 controller | Warning | Set the exerciser per Section 2.5 |
| Frequency High | High Frequency | Governed frequency exceeds 110% of system frequency setpoint for more than 10 seconds (10 sec inhibit after start) | Shutdown | Contact an authorized distributor/dealer for service |
| Frequency Low | Low Frequency | Governed frequency falls below 90% of system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds | Shutdown | Reduce the load and restart; contact dealer |
| Genset S/N Unaval | Unavailable Genset Serial Number | Generator set serial number is unavailable | Warning | Contact an authorized distributor/dealer for service |
| Ground Fault | Ground Fault Warning | The digital input for Ground Fault Warning is active (low); PIM required | Warning | Check customer equipment connected to the PIM |
| IAT High 1 | Iat Higher Than Expected 1 | Engine manifold air temperature is too high | Warning | Contact an authorized distributor/dealer for service and provide the fault code |
| IAT Volt Lo | Iat Low Voltage | ECM reported an Engine Air Temperature/Manifold Absolute Pressure Sensor (TMAP) error | Warning | Contact an authorized distributor/dealer for service and provide the fault code |
| Lo Crank Vlt | Low Cranking Voltage | Battery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged | Warning | Charge or replace the battery |
| Locked Rotor | Locked Rotor | No engine rotation is sensed during cranking; shuts down 3 seconds after fault detected | Shutdown | Check battery, connections, and for obstruction of alternator or engine; contact dealer |
| MainPwrOverL | Main Power Overload | Over current fault on the controller power output (short circuit) | Shutdown | Check for shorted run relay; check wiring for short circuits; contact dealer |
| Maint Req'd | Maintenance Required Warning | Engine maintenance is due | Warning | Check the maintenance schedule in the operation manual |
| Not in Auto | Not In Auto | The generator set is not in Automatic (standby) mode; remote start/stop commands will be ignored | Warning | Press AUTO to place the generator set in Automatic mode |
| Oil Pres Low | Low Oil Pressure | The engine ECM indicates low oil pressure | Shutdown | Check for leaks in the lubrication system; check oil level; check oil pressure switch and wiring |
| Over Crank | Over Crank | Three unsuccessful starting attempts | Shutdown | Check fuel supply, spark plug, battery, and connections; contact dealer |
| PrimLoopOpn | Primary Loop Open | Ignition coil 1 voltage is below normal or there is an open circuit | Warning | Check the battery voltage; contact dealer with fault code |
| PrimLoopSht | Primary Loop Shorted | Ignition coil 1 voltage is abnormal | Warning | Check the battery voltage; contact dealer with fault code |
| Spd Sens Flt | Speed Sensor Fault | Engine speed sensor has failed or engine stalled; ECM no longer reporting valid speed | Shutdown | Contact an authorized distributor/dealer for service |
| Volts L1-L2 High | High Generator Voltage L1-L2 | Output voltage exceeds 120% of system nominal voltage for more than 2 seconds | Shutdown | Contact an authorized distributor/dealer for service |
| Volts L1-L2 Low | Low Generator Voltage L1-L2 | Output voltage falls below 80% of nominal system voltage for more than 10 seconds | Shutdown | Reduce the load and restart; contact dealer |
| Volts L2-L3 High | High Generator Voltage L2-L3 | Output voltage exceeds 120% of system nominal voltage for more than 2 seconds | Shutdown | Contact an authorized distributor/dealer for service |
| Volts L2-L3 Low | Low Generator Voltage L2-L3 | Output voltage falls below 80% of nominal system voltage for more than 10 seconds | Shutdown | Reduce the load and restart; contact dealer |
| Volts L3-L1 High | High Generator Voltage L3-L1 | Output voltage exceeds 120% of system nominal voltage for more than 2 seconds | Shutdown | Contact an authorized distributor/dealer for service |
| Volts L3-L1 Low | Low Generator Voltage L3-L1 | Output voltage falls below 80% of nominal system voltage for more than 10 seconds | Shutdown | Reduce the load and restart; contact dealer |