Kohler KG2204 Engine

The Kohler KG2204 is a 2.2 L 4-cylinder natural aspiration engine rated at 1800 rpm, producing up to 30 kW. It powers generator sets from Kohler, including the 24RCL and 30RCLH. It holds 4.2 L (1.1 gal) of oil and 12.4 L (3.3 gal) of coolant.

Also known as: Kohler KG2204

Part of the Kohler KG2204 engine family — 2 variants share parts & fitment.

2.2 L
Displacement
4
Cylinders
1800 rpm
Rated speed
30 kW
Gross power

Engine specifications

Oil capacity4.2 L
Coolant capacity12.4 L
Displacement2.2 L
Cylinders4
AspirationNatural Aspiration
Rated speed1800 rpm
Gross power30 kW

Generator sets powered by this engine

2
Kohler 24RCLKohler 30RCLH

How to read your Kohler engine serial & model number →

Troubleshooting

57

Symptoms & remedies

SymptomCauseRemedy
Will Not StartNo fuelCheck fuel supply.
Will Not StartIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
Will Not StartDirty/restricted fuel systemCheck fuel system and clean components as needed.
Will Not StartIncorrect oil levelCheck engine oil level; add as needed.
Will Not StartEngine overloadedDisconnect or reduce loads.
Will Not StartFaulty spark plugInspect, adjust, or replace as needed.
Hard StartingNo fuelCheck fuel supply.
Hard StartingIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
Hard StartingRestricted fuel flowMake sure fuel supply valves are open; check for air intake system leakage.
Hard StartingDirty/restricted fuel systemCheck fuel system and clean components as needed.
Hard StartingIncorrect oil levelCheck engine oil level; add as needed.
Hard StartingEngine overloadedDisconnect or reduce loads.
Hard StartingFaulty spark plugInspect, adjust, or replace as needed.
Stops SuddenlyNo fuelCheck fuel supply.
Stops SuddenlyDirty/restricted fuel systemCheck fuel system and clean components as needed.
Stops SuddenlyIncorrect oil levelCheck engine oil level; add as needed.
Stops SuddenlyEngine overloadedDisconnect or reduce loads.
Lacks PowerIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
Lacks PowerLow fuel pressureCheck and adjust fuel pressure.
Lacks PowerIncorrect oil levelCheck engine oil level; add as needed.
Lacks PowerEngine overloadedDisconnect or reduce loads.
Lacks PowerFaulty spark plugInspect, adjust, or replace as needed.
Lacks PowerDirty/restricted fuel systemCheck fuel system and clean components as needed.
Lacks PowerAir induction system leakInspect air induction system.
Lacks PowerDamaged turbochargerInspect turbocharger compressor and turbine blades for damage and/or contact against housing.
Operates Erratically or UnevenlyIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
Operates Erratically or UnevenlyDirty/restricted fuel systemCheck fuel system and clean components as needed.
Operates Erratically or UnevenlyLow fuel supply pressureCheck and adjust.
Operates Erratically or UnevenlyEngine overloadedDisconnect or reduce loads.
Operates Erratically or UnevenlyLoose wiring at shut-off valve(s)Check wiring and repair connections.
Operates Erratically or UnevenlyFaulty spark plugInspect, adjust, or replace as needed.
Operates Erratically or UnevenlyDirty air filterInspect and replace as needed.
Knocks or PingsIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
Knocks or PingsEngine overloadedDisconnect or reduce loads.
Knocks or PingsFaulty spark plugInspect, adjust, or replace as needed.
Knocks or PingsDirty/restricted fuel systemCheck fuel system and clean components as needed.
Knocks or PingsDirty air filterInspect and replace as needed.
Knocks or PingsBoost pressure too highCheck for stuck wastegate, check for leak in wastegate boost line.
Knocks or PingsExcessive intake manifold temperatureCheck charge air cooler for debris and clean as needed.
Skips or MisfiresIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
Skips or MisfiresFaulty spark plugInspect, adjust, or replace as needed.
Skips or MisfiresDirty/restricted fuel systemCheck fuel system and clean components as needed.
Skips or MisfiresDirty air filterInspect and replace as needed.
BackfiresIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
BackfiresFaulty spark plugInspect, adjust, or replace as needed.
BackfiresDirty/restricted fuel systemCheck fuel system and clean components as needed.
BackfiresDirty air filterInspect and replace as needed.
OverheatsIncorrect fuelMake sure fuel system is configured properly for LPG or NG supply.
OverheatsDirty/restricted fuel systemCheck fuel system and clean components as needed.
OverheatsIncorrect oil levelCheck engine oil level; add as needed.
OverheatsEngine overloadedDisconnect or reduce loads.
OverheatsFaulty spark plugInspect, adjust, or replace as needed.
Consumes Excess FuelFaulty spark plugInspect, adjust, or replace as needed.
Consumes Excess FuelDirty/restricted air cleaner elementClean or replace.
Consumes Excess FuelIncorrect fuel pressureCheck and adjust fuel pressure.
ECM Does Not Store DTCFaulty electrical connections, components, or wiringContact Rehlko service.
Erratic operationAir induction system leakInspect air induction system.

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • Generator set stops suddenly.
    Cause: Low oil pressure shutdown.
    Fix: Check for oil leaks. Check the oil level and add oil if necessary.
  • The generator set cranks but does not start, starts hard, lacks power, or operates erratically.
    Cause: Air cleaner clogged.
    Fix: Clean and/or replace the air cleaner.
  • The generator set does not crank.
    Cause: Battery weak or dead.
    Fix: Recharge or replace the battery.
  • No AC output.
    Cause: AC circuit breaker in the OFF position.
    Fix: Place the circuit breaker in the ON position.
  • Loss of communication to accessory modules.
    Cause: Bad connections.
    Fix: Check wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual.
  • Load management relays do not operate.
    Cause: Bad connections.
    Fix: Check wiring and connections. Verify that cable size and length of run comply with the instructions in the Installation manual.
  • Verify Date Time Setting — The time and date have not been set on the generator controller. Chk DateTime
    Fix: Enter the date and time using the RDC2 controller. See Figure 3-8 and Figure 3-16.
  • Unavailable Genset Serial Number — Generator set serial number is unavailable. Genset S/N Unaval
    Fix: Contact an authorized distributor/dealer for service. See section 3.11.
  • Speed Sensor Fault — Engine speed sensor has failed or engine stalled. ECM is no longer reporting valid speed. Spd Sens Flt
    Fix: Contact an authorized distributor/dealer for service.
  • Primary Loop Shorted — Ignition coil 1 voltage is abnormal. PrimLoopSht
    Fix: Check the battery voltage.; Contact an authorized distributor/dealer for service and provide the fault code.
  • Primary Loop Open — Ignition coil 1 voltage is below normal or there is an open circuit. PrimLoopOpn
    Fix: Check the battery voltage.; Contact an authorized distributor/dealer for service and provide the fault code.
  • Over Crank — Three unsuccessful starting attempts. Over Crank
    Fix: Check the fuel supply, spark plug, and battery.; Check for loose connections.; Contact an authorized distributor/dealer for service.
  • Not In Auto — The generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored. Not in Auto
    Fix: Press AUTO to place the generator set in Automatic mode, when appropriate.
  • Maintenance Required Warning — Engine maintenance is due. Maint Req’d
    Fix: Check the maintenance schedule in the operation manual for tasks such as changing the oil, spark plugs or the air filter.
  • Main Power Overload — Main power overload. An over current fault on the 70 controller power output (short circuit). MainPwrOverL
    Fix: Check for shorted run relay. Check wiring for short circuits.; Contact an authorized distributor/dealer for service.

Compiled from service & troubleshooting documentation across every generator set that uses the Kohler KG2204.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterDry—
Oil filter—
BatteryBCI group 24 size, 12-volt, minimum 630 cold cranking amps (CCA) at 0°F—
Belt5–7 mm (0.20–0.28 in.)—
Coolant50% ethylene glycol-based long-life coolant / 50% clean, softened water12.4 L (13.1 gal.)—
Oil3.3 L—
Spark plug0.7–0.8 mm (0.028–0.031 in.)GM100158 Amazon eBay $49.00

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

25
ItemActionHoursMonthsNotes
Air cleaner elementClean20 hr3 moReplace at 3 years or 400 hours
Bolts and nuts for tightnessCheck20 hr3 moQuarterly or 20 hours
Battery cablesClean120 hr12 mo
Battery chargeCheck120 hr12 mo
Battery fluid levelCheck120 hr12 mo
Battery for cracks and corrosionCheck120 hr12 mo
Belts and belt tensionCheck120 hr12 moSee engine O/M
Engine oil and filterChange120 hr12 mo
Fuel regulator pressureCheck120 hr12 mo
Radiator exteriorCheck120 hr12 mo
Brushes and collector ringOther300 hr12 moAuthorized distributor/dealer only
Air induction for leaksCheck500 hr36 mo
Engine coolantChange500 hr36 moLong-life coolant: 5000 hours or 5 years
Hoses, conditionCheck500 hr36 moReplace as necessary
Intake manifold for vacuum leaksCheck500 hr36 mo
Secondary ignition coil wiresCheck500 hr36 moReplace as necessary
Spark plug wires for cuts, abrasions, or hardeningCheck500 hr36 moReplace as necessary
Spark plugsChange500 hr36 mo
Exhaust manifold for leaksCheck2000 hr60 moReplace as necessary
Exhaust piping for leaksCheck2000 hr60 mo
Fuel shutoff valve operationCheck2000 hr60 mo
HEGO (oxygen) sensor connections and wiresCheck2000 hr60 moSee engine O/M
Fuel lines and connectionsCheck3 moQuarterly
Vacuum lines and fittingsInspect60 mo5 years
Wiring for cuts, abrasions, or corrosionInspect60 mo5 years

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

28
TypeItemValueUnitCondition
GapSpark plug gap0.51mm (0.02 in.)
GapSpark plug gap0.7--0.8mm (0.028--0.030 in.)
GapSpark plug gap0.7-0.8mm (0.028-0.030 in.)
GapSpark plug gap0.76mm (0.03 in.)
GapSpark plug gap0.8--0.9mm (0.03--0.04 in.)
GapSpark plug gap0.89mm (0.035 in.)
GapSpark plug gap0.9--1.0mm (0.036--0.04 in.)
GapSpark plug gap0.9-1.0mm (0.036-0.040 in.)
PressureFuel supply test pressure6-8ounces per square inch (10-14 inches water column)leak test with soap and water solution
PressureRadiator pressure cap rating97kPa (14 psi)
TorqueOil filter25Nm (18.4 ft. lbs.)after hand-tight plus 3/4 turn
TorqueSpark plug18Nm (13.3 ft. lbs.)plus additional 1/4 turn
TorqueSpark plug25Nm (18.4 ft. lbs.)plus additional 1/4 turn
TorqueSpark plug torque15Nm (11 ft. lb.)
TorqueSpark plug torque18Nm (13.3 ft. lb.)
TorqueSpark plug torque24.4--29.8Nm (18--22 ft. lb.)
TorqueSpark plug torque25Nm (18 ft. lb.)
TorqueTerminal connector, socket size 12.7mm (1/2 in)56.5Nm (500 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 14.3mm (9/16 in)67.8Nm (600 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 3.2mm (1/8 in)5.1Nm (45 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 4.0mm (5/32 in)11.4Nm (100 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 4.8mm (3/16 in)13.8Nm (120 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 5.6mm (7/32 in)17.0Nm (150 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 6.4mm (1/4 in)22.6Nm (200 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 7.9mm (5/16 in)31.1Nm (275 in. lb.)internal-drive socket-head screw
TorqueTerminal connector, socket size 9.5mm (3/8 in)42.4Nm (375 in. lb.)internal-drive socket-head screw
VoltageUndervoltage dropout (ATS source availability)90% of pickup
VoltageUndervoltage pickup (ATS source availability)90% of nominal

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol-based long-life coolant / 50% clean, softened water37°C to 149°C12.4 L (13.1 gal.)Freezing protection to -37C (-34F), overheating protection to 149C (300F); do not mix long-life and conventional coolants, no alcohol/methanol antifreeze
Engine oilSAE 5W-30 (cold environments); 10W-30 (hot environments, never below 0C/32F)API Starburst certification, service class SJ or higher (gasoline engines)4.2 L (4.4 qt.)CC/CD classification oils not acceptable

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

44
CodeNameMeaningSeverityAction
AC Sens LossAC Sensing LostAC sensing lost in Auto mode; warning after 1 sec if no output after crank disconnect, shutdown after 3 sec if voltage was present then lostWarningContact an authorized distributor/dealer for service
Accy PwrOverAccessory Power OverloadOver current fault (short circuit) on the accessory controller power outputWarningContact an authorized distributor/dealer for service
ATS ComErrorATS Communication ErrorRXT interface connection is lostWarningCheck communication wiring between transfer switch interface board and generator set
ATS PhaseRotATS Phase Rotation MismatchTransfer switch phase rotation does not match; ATS will not transferWarningCorrect the ATS connection per installation manual, wiring diagrams, and labels
Aux InputAuxiliary InputAn optional customer-connected input is closed (digital input from optional PIM)ShutdownCheck customer-supplied equipment
Battery CrLoCritically Low Battery VoltageBattery voltage falls below 11V for more than 10 seconds; inhibited during crankWarningCheck battery rating/condition and charger operation; charge or replace battery
Battery HighHigh Battery VoltageBattery voltage rises above 133% (16V) of the battery voltage setting for more than 10 secondsWarningCheck battery rating/condition and charger operation
Battery LowLow Battery VoltageBattery voltage falls below the battery voltage setting (typically 12.5V) for more than 90 seconds when engine is not runningWarningCheck battery rating/condition and charger operation; charge or replace battery
Chk DateTimeVerify Date Time SettingThe time and date have not been set on the generator controllerWarningEnter the date and time using the RDC2 controller
Coolant Lvl LowLow Coolant Level ShutdownThe coolant level switch input has been activatedShutdownCheck coolant level; check radiator hoses for leaks; contact dealer
CoolntTemp 0Coolant Temp 0 ShutdownECM reported coolant temperature sensor problem: 0 = high temperatureShutdownCheck coolant level and radiator/fans; contact dealer with fault code
CoolntTemp 3Coolant Temp 3 ShutdownECM reported coolant temperature sensor problem: 3 = high voltageShutdownContact an authorized distributor/dealer for service and provide the fault code
CoolntTemp 4Coolant Temp 4 ShutdownECM reported coolant temperature sensor problem: 4 = low voltageShutdownContact an authorized distributor/dealer for service and provide the fault code
CoolntTemp 5Coolant Temp 5 ShutdownECM reported coolant temperature sensor problem: 5 = open circuitShutdownContact an authorized distributor/dealer for service and provide the fault code
CoolTemp VhiEct Higher Than Expected 2Coolant temperature is extremely highShutdownCheck coolant level; check radiator/fans for obstruction; contact dealer with fault code
CoolTempHighEct Higher Than Expected 1Coolant temperature is too highWarningCheck coolant level; check radiator/fans for obstruction; contact dealer with fault code
Crank LostCrank Signal LostCrankshaft Position Sensor (CPS) timeout error occurredWarningContact an authorized distributor/dealer for service and provide the fault code
ECM warningsECM warnings (any warning with ECM in the fault name)Group of faults that originate from the engine ECM and contain ECM in the fault nameWarningContact an authorized distributor/dealer for service and provide the fault code
Emerg StopEmergency Stop ShutdownThe emergency stop switch has been activated, or there has been an open circuit in the wiringShutdownContact an authorized distributor/dealer for service
Eng Speed HighHigh Engine SpeedEngine speed exceeds 115% of normal running speed for more than 0.3 secondsShutdownContact an authorized distributor/dealer for service
Eng Speed LowLow Engine SpeedEngine speed drops below 85% of normal running speed for more than 3 secondsShutdownReduce the load; contact an authorized distributor/dealer for service
Exer Not SchATS Exercise Not ScheduledNo exercise has been scheduled on the RDC2 controllerWarningSet the exerciser per Section 2.5
Frequency HighHigh FrequencyGoverned frequency exceeds 110% of system frequency setpoint for more than 10 seconds (10 sec inhibit after start)ShutdownContact an authorized distributor/dealer for service
Frequency LowLow FrequencyGoverned frequency falls below 90% of system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 secondsShutdownReduce the load and restart; contact dealer
Genset S/N UnavalUnavailable Genset Serial NumberGenerator set serial number is unavailableWarningContact an authorized distributor/dealer for service
Ground FaultGround Fault WarningThe digital input for Ground Fault Warning is active (low); PIM requiredWarningCheck customer equipment connected to the PIM
IAT High 1Iat Higher Than Expected 1Engine manifold air temperature is too highWarningContact an authorized distributor/dealer for service and provide the fault code
IAT Volt LoIat Low VoltageECM reported an Engine Air Temperature/Manifold Absolute Pressure Sensor (TMAP) errorWarningContact an authorized distributor/dealer for service and provide the fault code
Lo Crank VltLow Cranking VoltageBattery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engagedWarningCharge or replace the battery
Locked RotorLocked RotorNo engine rotation is sensed during cranking; shuts down 3 seconds after fault detectedShutdownCheck battery, connections, and for obstruction of alternator or engine; contact dealer
MainPwrOverLMain Power OverloadOver current fault on the controller power output (short circuit)ShutdownCheck for shorted run relay; check wiring for short circuits; contact dealer
Maint Req'dMaintenance Required WarningEngine maintenance is dueWarningCheck the maintenance schedule in the operation manual
Not in AutoNot In AutoThe generator set is not in Automatic (standby) mode; remote start/stop commands will be ignoredWarningPress AUTO to place the generator set in Automatic mode
Oil Pres LowLow Oil PressureThe engine ECM indicates low oil pressureShutdownCheck for leaks in the lubrication system; check oil level; check oil pressure switch and wiring
Over CrankOver CrankThree unsuccessful starting attemptsShutdownCheck fuel supply, spark plug, battery, and connections; contact dealer
PrimLoopOpnPrimary Loop OpenIgnition coil 1 voltage is below normal or there is an open circuitWarningCheck the battery voltage; contact dealer with fault code
PrimLoopShtPrimary Loop ShortedIgnition coil 1 voltage is abnormalWarningCheck the battery voltage; contact dealer with fault code
Spd Sens FltSpeed Sensor FaultEngine speed sensor has failed or engine stalled; ECM no longer reporting valid speedShutdownContact an authorized distributor/dealer for service
Volts L1-L2 HighHigh Generator Voltage L1-L2Output voltage exceeds 120% of system nominal voltage for more than 2 secondsShutdownContact an authorized distributor/dealer for service
Volts L1-L2 LowLow Generator Voltage L1-L2Output voltage falls below 80% of nominal system voltage for more than 10 secondsShutdownReduce the load and restart; contact dealer
Volts L2-L3 HighHigh Generator Voltage L2-L3Output voltage exceeds 120% of system nominal voltage for more than 2 secondsShutdownContact an authorized distributor/dealer for service
Volts L2-L3 LowLow Generator Voltage L2-L3Output voltage falls below 80% of nominal system voltage for more than 10 secondsShutdownReduce the load and restart; contact dealer
Volts L3-L1 HighHigh Generator Voltage L3-L1Output voltage exceeds 120% of system nominal voltage for more than 2 secondsShutdownContact an authorized distributor/dealer for service
Volts L3-L1 LowLow Generator Voltage L3-L1Output voltage falls below 80% of nominal system voltage for more than 10 secondsShutdownReduce the load and restart; contact dealer

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
12-Lead Generator Reconnection Procedure adjustment

⚠ Verify that voltage ratings of transfer switch, line breakers, and accessories match the selected line voltage

Tools: digital multimeter, voltmeter

  1. Press the OFF button on the RDC2 controller
  2. Disconnect engine starting battery, negative lead first
  3. Disconnect utility power to the generator set
  4. Select desired voltage connection and connect leads according to the diagram
  5. Reconnect engine starting battery, negative lead last
  6. Enter the RDC2 Genset System menu and check/change system voltage, frequency, phase settings
  7. Connect a digital multimeter (DVM) to the generator set output
  8. Press RUN to start the generator set
  9. Use a voltmeter to check output voltage and calibrate if necessary
  10. Press OFF to stop the generator set
  11. Reconnect utility power to the generator set
  12. Press AUTO to place the generator set in automatic mode
Fuel Conversion: Reset Regulator for NG adjustment
  1. Push up on the adjusting cap and rotate counterclockwise, release upward pressure, and lock into place
  2. Disconnect wire N20 and wire 45
Fuel Conversion: Set Regulator for LPG adjustment

⚠ Do not adjust the IEPR or the air/fuel mixer

  1. Push the adjusting cap to its upper stop and rotate clockwise, release upward pressure, and lock into place
  2. For LPG fuel only, use the quick-connect adapters to connect wire N20 from the fuel pressure regulator to wire 45 from the ECM wiring harness
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Voltage Calibration Using RDC2 Controller Keypad and Menus adjustment

Tools: digital multimeter

  1. With the generator set off, connect a digital multimeter to measure output voltage across L1 and L2
  2. Start the generator set by pressing RUN
  3. Navigate to the Generator Metering menu
  4. Press Select to display Volts L1-L2 and compare to the voltmeter reading
  5. If incorrect, press Select, use up/down arrows to adjust voltage to match the voltmeter, press Select to save
  6. Wait 30-60 seconds for the reading to stabilize
  7. For three-phase models, repeat for L2-L3 and L3-L1
  8. Step to Return and exit the Generator Metering menu
  9. Press OFF to stop the generator set
Obtain DC2 Controller Password and Serial Number diagnostic
  1. Press OFF and verify that the generator set is not running.
  2. Press and hold the Exercise button until Press Again to Reset OnCue Plus PW is displayed.
  3. Release the Exercise button and press it again within 5 seconds.
  4. Write down the serial number (S/N) and password.
Obtain RDC/DC Controller Password diagnostic
  1. Press OFF to place the controller into OFF mode.
  2. Press the down arrow button (RDC) or exercise button (DC) 5 times.
  3. Note the four-digit code displayed on the controller; this is the controller password.
  4. Write down the password and press OFF to clear the display.
Obtain RDC2 or VSC Controller Password and Serial Number diagnostic
  1. Press the controller down arrow button to navigate to the Networking Information menu.
  2. Follow the reset password procedure shown in Figure 1-3.
  3. Write down the serial number (S/N) and password displayed for 10 seconds.
Power Cycle the Controller diagnostic
  1. Disconnect all input power for two minutes to allow capacitors to discharge.
  2. Remove the battery negative cable or disconnect P1 from the back of the controller.
  3. Disconnect the battery charger 120 VAC input power supply or disconnect P5 from the back of the controller.
  4. Unplug the USB mini-B connector from the front of the controller if plugged in.
  5. Wait two minutes, then reconnect power, hooking up battery power (P1) first.
Resetting the Controller after a Fault Shutdown diagnostic

⚠ Always identify and correct the cause of a fault shutdown before resetting

  1. Press the Select button to go to the Overview menu
  2. Press Select again to display the active fault
  3. Press Select; Confirm Clear Fault: NO is displayed
  4. Press the Up arrow button; Confirm Clear Fault: YES is displayed
  5. Press Select to enter YES and clear the fault
  6. Press Select to return to the Overview menu
  7. Press AUTO to put the generator set into automatic mode

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Three-phase (12-lead)Reconnectable to voltages/phases per generator set specification sheet12-leadSee Figure 3-2, 24RCL and 30RCLH
100/2001Single
100/2003Delta
110/2201Single
110/2203Delta
115/2301Single
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/20834D5.012, ReconnectableThree-phase
120/2083Wye
120/24014E5.04Single-phase
120/2401Single
120/2403Delta
120/240 VSingle-phase (four-lead)Factory connection, not reconnectable4-lead60 Hz; see Figure 3-1
127/22034D5.012, ReconnectableThree-phase
127/2203Wye
2201Single
220/3803Wye
2301Single
230/4003Wye
2401Single
240/4163Wye
277/4803Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Kohler KG2204 family

6
Part #DescriptionCategory
GM103786Battery heater wrapBattery heater wrap
GM104701Battery heater wrapBattery heater wrap
GM104708Battery heater wrapBattery heater wrap
GM103784Battery heater wrapService part / kit
GM104699Battery heater wrapService part / kit
GM104703-KP1Battery heater kit, 120 Volts, heater wrap rating 50 Watts, battery wrap length 864 mm (34 in.), power cord length 483 mm (19 in.), plug cord length 75 mm (3 in.)Service part / kit

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Kohler KG2204?

The Kohler KG2204 engine has an oil capacity of 4.2 liters.

What is the displacement of the Kohler KG2204?

The Kohler KG2204 has a displacement of 2.2 liters with 4 cylinders.

Which generators use the Kohler KG2204 engine?

The Kohler KG2204 powers 2 generator set(s), including Kohler 24RCL, Kohler 30RCLH.

What is a common problem with the Kohler KG2204 engine?

A commonly reported issue on generators using the Kohler KG2204 is: Generator set stops suddenly.. Cause: Low oil pressure shutdown.. Fix: Check for oil leaks. Check the oil level and add oil if necessary..