Cummins/Onan — Voltage and Voltage Stability Adjustments (AVR)

Adjustments · Voltage Regulator VR21

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan 4B3.9 engine

Before you start

  • High voltage - use dry wooden platform or rubber insulating mat, dry clothing, no jewelry, elbow length insulating gloves

Procedure

  1. Measure generator output voltage while running without load at nominal frequency.
  2. Lock the control panel voltage trimmer at its midpoint if it cannot provide enough adjustment.
  3. Turn the VOLTS pot fully counterclockwise and the STABILITY pot to its midpoint.
  4. If the red LED lights, refer to Jumper Reconnections and UFRO Adjustments.
  5. Turn the VOLTS pot clockwise until rated voltage is obtained.
  6. If voltage becomes unstable under large load, turn the STABILITY pot clockwise until stable.
  7. Check and readjust the VOLTS pot each time the STABILITY pot is readjusted.

Specs & values

  • Output voltage trimmer adjusts plus or minus five percent of nominal voltage

Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCB →, Cummins/Onan DGDA →, Cummins/Onan DGDB →, Cummins/Onan DGEA →, Cummins/Onan DGFA →, Cummins/Onan DGFB →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.