Cummins/Onan — Resetting an Emergency Stop Shutdown
Operation · Control panel
From a Cummins/Onan operator's manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCG, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan DGFC, Cummins/Onan 4B3.9 engine, Cummins/Onan 6CTA8.3 engine, Cummins/Onan 6CTAA8.3 engine
Before you start
- Emergency Stop shutdown can be reset only at the PCC front panel.
Procedure
- Pull the emergency stop button out (allow it to pop out).
- Turn the O/Manual/Auto switch to O (Off).
- Press the front panel Fault Acknowledge/Reset button.
- Select Manual or Auto, as required.
Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCB →, Cummins/Onan DGFA →, Cummins/Onan DGFB →, Cummins/Onan DGFC →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.