Cummins/Onan 15.0 RDJC Generator Set

The Cummins/Onan 15.0 RDJC is a 15 kW (18.75 kVA) #1 or #2 diesel standby generator set powered by a Cummins/Onan Onan Diesel 4-cyl engine. It is available at 120/240 V, 120/208 V, 127/220 V and 139/240 V, 3-phase and 60 Hz. It holds about 6 L (1.6 gal) of oil and 12 L (3.2 gal) of coolant. Starting uses 1 group-2 battery rated 560 CCA at 12 V. The set measures 1438×686×1019 mm (56.6×27.0×40.1 in) and weighs about 426 kg (939 lb).

15 kW
Standby
1.966 L
Displacement
6.0 L
Oil capacity
1
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 15–20 kW Diesel generators →

Compare with other 15–20 kW Diesel generators →

Specifications

Fuel#1 or #2 diesel
Frequency60.0 Hz
Standby power15 kW
Standby kVA18
ControllerDetector 12 (optional), Detector 7 (standard)
Oil capacity6.0 L
AlternatorYD (4-pole)
Voltage options120/240 V, 120/208 V, 127/220 V, 139/240 V
Phase3
Power factor1.0 (single-phase); 0.8 (three-phase)
Battery group2 (6V in series) / Group 5D
Battery cranking560 amps (cold cranking) at 32°F (0°C); 800 amps (cold cranking) at 0°F (-18°C) CCA
Battery voltage12 Volts DC V
Battery quantity1
Coolant capacity12 L
Dimensions (L×W×H)1438×686×1019 mm
Dry weight426 kg

Engine

Cummins/Onan Onan Diesel 4-cyl
Oil capacity5.7 L
Coolant capacity11.36 L
Displacement1.966 L
AspirationNatural
Rated speed1800 rpm

Maintenance & consumables

for the Cummins/Onan Onan Diesel 4-cyl
ItemSpecCapacityPart #Interval
Oil filterFull Flow Type
Spark plug

Service intervals

23
ItemActionHoursMonthsNotes
Exhaust systemInspect8 hr
Fuel supplyCheck8 hrSee Note 1; if daily inspection shows water or excessive dirt in sediment bowl, check fuel handling and storing facilities
Generator setInspect8 hr
Oil levelCheck8 hrCheck oil level indicator after every 8 hours of operation; maintain at FULL mark
Air cleanerCheck50 hrNote 3: perform more often in extremely dusty conditions; remove and clean filter element after every 50 hours
Cylinder head bolts and valve clearanceAdjust50 hrFirst service — Note 2: tighten head bolts and adjust valve clearance after first 50 hours on new and overhauled engines, then adjust valve clearance each 500 hours thereafter
BatteryInspect100 hrCheck battery condition
Crankcase oilChange100 hrFirst service — Or annually; perform more often in extremely dusty conditions (Note 3)
Fuel transfer pump sediment bowl and filterClean100 hrSee Note 1
Governor linkageClean100 hrCarefully pull neoprene governor ball joints apart and clean them; do not lubricate
Oil filterReplace100 hr
Battery electrolyte levelCheck200 hrCheck level of electrolyte at least every 200 hours of operation
Crankcase breatherClean200 hr
Crankcase breather tubeClean500 hr500 hour interval coincides with valve lash adjustments
Start-disconnect circuitCheck500 hr
Valve clearancesCheck500 hrNote 4: contact an authorized service center for service
Primary fuel filterChange600 hr
Torsional washersInspect1500 hrNote 5: check yearly on non-commercial sets
GeneratorClean2000 hr
Nozzle spray patternCheck2000 hrNote 4
ValvesOther2000 hrGrind valves (if required); Note 4
Secondary fuel filterChange3000 hr
General overhaulOther5000 hrIf required; Note 4

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

22
TypeItemValueUnitCondition
GapStart-disconnect centrifugal switch point gap0.020in. (0.51 mm)
PressureEngine oil pressure at operating temperature35 to 55psi (241 to 379 kPa)at operating temperature
PressureExhaust total back pressure of all system componentsmust not exceed maximum back pressure limits
PressureLO OIL PRES shutdown at engine oil pressure14psi (97 kPa)
PressurePRE LO OIL PRES lamp lights at engine oil pressure20psi (138 kPa)
ResistanceBattery electrolyte specific gravity, fully charged (corrected)1.260specific gravitycorrected to 80°F (27°C)
ResistanceCharge battery if specific gravity is below1.215specific gravity
SpeedCentrifugal switch closes when engine speed reaches900rpm
SpeedEngine speed (50/60 Hz)1500/1800rpm
SpeedGovernor speed variation, no-load to full-load3hertzno-load to full-load operation
SpeedStarter disconnects when engine speed reaches450 to 570r/min
TemperatureCoolant temperature170° to 216°°F (77° to 102° C)depending on the load and ambient temperature
TemperatureExercising: engine oil temperature to be held at180°F (82.2° C)for at least 30 minutes
TemperatureHI ENG TEMP shutdown above230°F (110° C)
TemperatureLOW ENG TEMP (LET) lamp lights at coolant temperature of70°F (21° C)
TemperaturePRE HI ENGINE TEMP lamp lights at approximately220°F (104° C)
TorqueCylinder head bolt torque44 - 46ft-lb (60 - 62 N·m)
TorqueGlow plug torque10-15ft-lb (14 - 20 N·m)
Valve clearanceValve clearance, exhaust0.016in. (0.41 mm)engine at room temperature about 70°F (21°C)
Valve clearanceValve clearance, intake0.011in. (0.28 mm)engine at room temperature about 70°F (21°C)
VoltageDC voltmeter reading while genset running12 to 14voltsgenset running
VoltageVoltage adjust rheostat rangeplus or minus fivepercent of rated output voltage

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilSAE 15W40API Classification CC/CD, CD/SG or CE/SG6.5 U.S. quarts (6.0 l)Table 9-2 viscosity/temperature chart: 5W30, 15W40, 10W30/10W40; 15W40 preferred summer. Limited use of 10W-30 for easier starting below 23°F (-5°C)
FuelASTM 2-D (No. 2 Diesel) or ASTM 1-D (No. 1 Diesel)minimum Cetane number of 45; viscosity above 1.3 cSt; low-sulfur fuel with cloud point at least 10 degrees below lowest expected fuel temperaturebelow 0°CUse number 1 diesel fuel when ambient temperatures are below 0°C (32°F) or during long periods of light engine load

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

12
CodeNameMeaningSeverityAction
FAULT 1Fault 1 (red lamp)Indicates an undedicated fault; may be field programmed as shutdown or non-shutdown, and as timed or non-timed fault (normally set for timed shutdown).ShutdownNature of fault determined at installation design; correct the fault and reset the control.
FAULT 2Fault 2 (red lamp)Indicates same features as Fault 1 (normally set for timed shutdown).ShutdownNature of fault determined at installation design; correct the fault and reset the control.
HI ENG TEMPHigh Engine Temperature (red lamp)Indicates engine has shut down because of critically high engine temperature (above 230°F / 110°C) or low coolant level.ShutdownAllow engine to cool; check coolant level and replenish; check for obstructions to cooling airflow and slipping fan belt; reset control and restart.
LO FUELLow Fuel (yellow lamp)Indicates fuel supply is marginally low.WarningCheck fuel supply and replenish as required.
LO OIL PRESLow Oil Pressure (red lamp)Indicates engine has shut down because of critically low oil pressure (14 psi / 97 kPa).ShutdownCheck oil level, lines and filters; replenish oil if low; reset control and restart; contact service center if oil pressure is 20 psi (138 kPa) or lower.
LOW ENG TEMPLow Engine Temperature (yellow lamp)Lights if engine temperature is marginally low for starting (70°F / 21°C or lower); may indicate an inoperative coolant heater.WarningCheck coolant heater power supply, coolant level and heater operation.
OVERCRANKOvercrank (red lamp)Indicates engine has failed to start during the cranking period.ShutdownCheck for loss of engine prime, empty fuel tank, fuel leaks, or plugged fuel lines; check filters; reset control and restart.
OVERSPEEDOverspeed (red lamp)Indicates engine has shut down because of excessive speed.ShutdownContact an authorized service center for service.
PRE HI ENG TEMPPre-High Engine Temperature (yellow lamp)Indicates engine temperature is marginally high (approximately 220°F / 104°C) or coolant level is low on optionally wired sets.WarningReduce load if possible; check air inlets and outlets and remove obstructions to airflow.
PRE LO OIL PRESPre-Low Oil Pressure (yellow lamp)Indicates engine oil pressure is marginally low (20 psi / 138 kPa).WarningReduce load or prepare to shut down; follow troubleshooting step 5/6 procedures.
RUNRun (green lamp)Comes on when starter circuit opens after set starting.InfoIndicates all engine systems are normal; no corrective action required.
SWITCH OFFSwitch Off (flashing red lamp)Indicates generator set is not in automatic start mode.WarningMove the Run/Stop/Remote switch to the Remote position for automatic starting.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Centrifugal Switch Adjustment adjustment

⚠ Shut down the set and disconnect the battery cable, negative (-) terminal first, before setting the breaker point gap

  1. Locate the start-disconnect centrifugal switch on the side of the engine, above the oil filter.
  2. If necessary, loosen the stationary contact and adjust the point gap to 0.020 inch (51 mm).
  3. Replace burned or faulty points.
Charge Rate Adjustment adjustment

⚠ Avoid overcharging the battery

⚠ Do not smoke or allow any flame, sparks, or arc-producing devices in the battery area

  1. Locate the adjustable resistor slide tap in the charging circuit, found in the generator air outlet.
  2. If necessary, increase the charging rate slightly by moving the slide tap up.
  3. Make small increments of change until the proper rate has been determined.
  4. Adjust this slide tap only when the engine is stopped.
Generator Voltage Check and Adjustment adjustment

⚠ High voltages can cause injury or death; use extreme caution when working on electrical components

Tools: Screwdriver, Wrench

  1. Move the Run/Stop/Remote switch on the engine control panel to the Run position.
  2. Move the Phase Selector switch to read generator output current and voltage.
  3. Insert a screwdriver into the Voltage Adjust potentiometer and carefully loosen the locking nut with a wrench.
  4. While observing the voltmeter, slowly turn the screwdriver clockwise to increase voltage or counterclockwise to decrease voltage.
  5. Adjust to the rated nameplate voltage.
  6. Tighten the locking nut, being careful not to change the adjustment.
  7. Move the Phase Selector switch to the Off position.
Governor Sensitivity Adjustment adjustment
  1. Turn the sensitivity adjusting ratchet to adjust governor sensitivity (no-load to full-load speed droop).
  2. Radiator cooled sets: turn the ratchet clockwise for more sensitivity (less speed drop at full load).
  3. Radiator cooled sets: turn the ratchet counterclockwise for less sensitivity (more speed drop).
  4. City water cooled sets: turn the ratchet counterclockwise for more sensitivity.
  5. After making the sensitivity adjustment, readjust the speed.
Governor Speed Adjustment adjustment

Tools: Stroboscope, Frequency meter

  1. Turn the governor speed adjusting nut clockwise (more spring tension) to increase rpm.
  2. Turn the nut counterclockwise to reduce governed speed.
  3. Use a stroboscope or a frequency meter to make this adjustment.
Valve Clearance Adjustment adjustment

⚠ Incorrect valve clearance adjustment can lead to irrevocable damage to the generator set; only qualified personnel should perform this adjustment

Tools: Socket wrench, Feeler gauge, Torque wrench

  1. Check the valve clearance when the engine is at room temperature, about 70°F (21°C).
  2. Turn the flywheel until the cylinder to be adjusted is on its compression stroke.
  3. Turn the flywheel an additional 10 to 45 degrees clockwise so the piston is in its power stroke with both valves closed.
  4. Check cylinder head-bolt torque prior to valve clearance adjustment.
  5. Loosen the locknut securing the rocker arm to the cylinder head to increase clearance; tighten it to reduce clearance.
  6. Using a feeler gauge, check the clearance between the rocker arm and the valve until the proper gap is established.
Battery Cleaning and Specific Gravity Check maintenance

⚠ Do not smoke or allow any source of ignition while servicing batteries

⚠ Always remove the negative (-) cable first, and reconnect it last to prevent arcing

Tools: Battery hydrometer

  1. Disconnect the negative ground strap from the battery before working on any part of the electrical system or engine.
  2. Wipe the batteries clean with a damp cloth whenever dirt appears excessive.
  3. If corrosion is present, remove battery cables and wash terminals with an ammonia solution or a solution of 1/4 pound baking soda in 1 quart of water.
  4. Flush the outside of the battery and surrounding areas with clean water.
  5. Coat the terminals with a light application of petroleum jelly or non-conductive grease.
  6. Use a battery hydrometer to check the specific gravity of the electrolyte in each cell; hold the hydrometer vertical.
  7. Correct the reading by adding four gravity points (0.004) for every ten degrees the electrolyte temperature is above 80°F (27°C).
Contractor Model Air Cleaner Cleaning maintenance

⚠ Filters should be handled with care to prevent damage; if the filter becomes damaged, install recommended replacement part

  1. Remove pre-cleaner and wash out dirt; dry and reinstall.
  2. Loosen clamp and remove end cover.
  3. Remove thumbscrew and take out element.
  4. Wash element in detergent and water (use new element after 6 washings); dry and reinstall.
  5. Remove air cleaner baffle from cover, wash out dirt, and reinstall in cover.
  6. Install cover with "TOP" up and tighten clamp.
Crankcase Breather Cleaning maintenance
  1. Remove hose clamp, breather hose, breather cap clamp and insulator halves to release breather cap and valve assembly.
  2. Wash cap, valve assembly and baffle in suitable solvent.
  3. Dry and reinstall.
Oil Change maintenance

⚠ Hot crankcase oil can cause burns if spilled or splashed on skin; keep fingers and hands clear when removing the oil drain plug and wear protective clothing

Tools: Drain pan

  1. Stop the engine and drain the crankcase oil while the engine is still hot.
  2. Place a pan under the drain outlet and remove the oil drain plug or open the oil drain valve.
  3. After the oil is completely drained, replace the drain plug or close the drain valve.
  4. Replace oil filter if necessary before adding oil.
  5. Refill with oil of the correct API designation and SAE viscosity grade for the temperature conditions.
Oil Filter Change maintenance

⚠ Hot crankcase oil can cause burns if spilled or splashed on skin

Tools: Container

  1. Place a container under the oil filter and remove the filter by turning it counterclockwise.
  2. Clean the filter mounting area.
  3. Coat the oil filter gasket with clean oil.
  4. Install the new filter by turning it clockwise until the gasket touches the mounting base.
  5. Tighten the filter 1/2 turn.
Out-of-Service Protection maintenance
  1. Exercise the generator set until the engine is up to operating temperature.
  2. Shut down the engine; disconnect battery and store in a cool, dry place. Connect battery to a charger every 30 days.
  3. Drain the oil base while it is still warm; refill and attach a warning tag indicating the viscosity of oil used.
  4. Service the air cleaner.
  5. Clean throttle and governor linkage and protect by wrapping with a clean cloth.
  6. Plug the intake and exhaust outlets to prevent entrance of moisture, bugs, dirt, etc.
  7. Clean and wipe the entire unit; coat parts susceptible to rust with a light coat of grease or oil.
  8. Provide a suitable cover for the entire unit after the unit has cooled down.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
1001V4-V14 lead reconnectable50 Hz
100/2001V4-V112 lead reconnectable50 Hz
1101V4-V14 lead reconnectable50 Hz
110/1903V4-V112 lead reconnectable50 Hz
110/2201V4-V112 lead reconnectable50 Hz
1151V4-V24 lead reconnectable50 Hz
115/2203V4-V212 lead reconnectable50 Hz
115/2301V4-V212 lead reconnectable50 Hz
1201V4-V14 lead reconnectable60 Hz
1201V4-V34 lead reconnectable50 Hz
120/2083V4-V112 lead reconnectable60 Hz; jumper wire connection on voltage regulator VR21, per representative reconnection diagram (YD generators)
120/2083V4-V312 lead reconnectable50 Hz
120/2401V4-V112 lead reconnectable60 Hz
120/2401V4-V312 lead reconnectable50 Hz
127/2203V4-V212 lead reconnectable60 Hz
139/2403V4-V312 lead reconnectable60 Hz
220/3803V4-V112 lead reconnectable50 Hz
230/4003V4-V212 lead reconnectable50 Hz
240/4163V4-V112 lead reconnectable60 Hz
240/4163V4-V312 lead reconnectable50 Hz
254/4403V4-V212 lead reconnectable60 Hz
254/4403V4-V412 lead reconnectable50 Hz
277/4803V4-V312 lead reconnectable60 Hz
347/6003V4-V112 lead reconnectable60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Cummins/Onan 15.0 RDJC?

The Cummins/Onan 15.0 RDJC is rated 15 kW standby (18.75 kVA).

Which engine powers the Cummins/Onan 15.0 RDJC?

The Cummins/Onan 15.0 RDJC is powered by the Cummins/Onan Onan Diesel 4-cyl engine.

What fuel does the Cummins/Onan 15.0 RDJC use?

The Cummins/Onan 15.0 RDJC runs on #1 or #2 diesel.

What is the oil capacity of the Cummins/Onan 15.0 RDJC?

The Cummins/Onan Onan Diesel 4-cyl engine in the Cummins/Onan 15.0 RDJC has an oil capacity of 5.7 liters.

Which alternator is fitted to the Cummins/Onan 15.0 RDJC?

The Cummins/Onan 15.0 RDJC uses a YD alternator. It has 4 poles.

Troubleshooting

3

Symptoms & remedies

SymptomCauseRemedy
Engine does not startThe starter will disengage after a specified period of time and the control will indicate an overcrank fault.Place the Run/Stop/Remote switch in the STOP position and momentarily depress the Reset switch. Wait two minutes for the starter motor to cool, then repeat the starting procedure. If the engine does not run after a second attempt at starting, refer to the Troubleshooting section.
Engine fails to start after 20 seconds of cranking.Wait one minute, to conserve battery and repeat steps 1 and 2. Absence of blue exhaust smoke during cranking indicates no fuel is being delivered.
Engine fails to start.If engine fired, repeat above procedures, including preheat. If it still does not start after 20 seconds of cranking, wait one minute before resetting the cranking limiter and trying to start the engine.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

1
Part #DescriptionQtySystem
130-0626Zinc pencil anode for heat exchanger1Sensor Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime100%4.921.3
Standby100%6.01.6

Available documents

Operator's manual — 974-0127 Onan RDJC Operator's Manual (8-1994) (Cummins/Onan)