Cummins/Onan 12.5 RDJC / 15.0 RDJC — Exercising the Generator Set

Operation

For the Cummins/Onan 12.5 RDJC / 15.0 RDJC, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan 12.5 RDJC, Cummins/Onan 15.0 RDJC, Cummins/Onan RDJC

Before you start

  • Improper exercising of the generator set may cause more damage than no exercising at all

Procedure

  1. Perform all required maintenance checks, start the unit, and apply a load of 50 percent or more by creating a simulated power failure.
  2. After the genset has reached its normal operating temperature, allow the genset to run an additional 30 minutes.
  3. Shut the unit down by simulating the return of normal power.
  4. Run the set approximately three to five minutes with no load to allow the engine to cool down.

Specs & values

  • Exercise at least once each week; hold engine oil temperature at 180°F (82.2°C) for at least 30 minutes

Full service-parts list: Cummins/Onan RDJC →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.