Specifications
| Fuel | #1 or #2 diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 12.5 kW |
| Standby kVA | 15 |
| Controller | Detector 12 (optional), Detector 7 (standard) |
| Oil capacity | 6.0 L |
| Alternator | YD (4-pole) |
| Voltage options | 120/240 V, 120/208 V, 127/220 V, 139/240 V |
| Phase | 3 |
| Power factor | 1.0 (single-phase); 0.8 (three-phase) |
| Battery group | 2 (6V in series) / Group 5D |
| Battery cranking | 560 amps (cold cranking) at 32°F (0°C); 800 amps (cold cranking) at 0°F (-18°C) CCA |
| Battery voltage | 12 Volts DC V |
| Battery quantity | 1 |
| Coolant capacity | 12 L |
| Dimensions (L×W×H) | 1438×686×1019 mm |
| Dry weight | 426 kg |
Engine
| Oil capacity | 5.7 L |
|---|---|
| Coolant capacity | 11.36 L |
| Displacement | 1.966 L |
| Aspiration | Natural |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Cummins/Onan Onan Diesel 4-cyl| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Wash element in detergent and water (use new element after 6 washings); wash pre-cleaner, dry and reinstall | — | 50 hr | ||
| Fuel filter | Spin-off throw-away unit with water drain at bottom of filter case | — | 3000 hr | ||
| Oil filter | Full Flow Type | — | 100 hr | ||
| Battery | 12 volt, negative ground; 560 amps cold cranking at 32°F (0°C), 800 amps cold cranking at 0°F (-18°C); corrected full-charge specific gravity 1.260; charge if below 1.215 | — | 200 hr | ||
| Belt | Check for a slipping fan belt and tighten if loose | — | |||
| Coolant | Check coolant level; fill cooling system with recommended coolant if low | — | |||
| Oil | SAE 15W40 that meets API Classification CC/CD, CD/SG or CE/SG; CC/CD or CD/SG oil requires oil change interval reduced to one half | — | 100 hr | ||
| Spark plug | — |
Service intervals
23| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Exhaust system | Inspect | 8 hr | ||
| Fuel supply | Check | 8 hr | See Note 1; if daily inspection shows water or excessive dirt in sediment bowl, check fuel handling and storing facilities | |
| Generator set | Inspect | 8 hr | ||
| Oil level | Check | 8 hr | Check oil level indicator after every 8 hours of operation; maintain at FULL mark | |
| Air cleaner | Check | 50 hr | Note 3: perform more often in extremely dusty conditions; remove and clean filter element after every 50 hours | |
| Cylinder head bolts and valve clearance | Adjust | 50 hr | First service — Note 2: tighten head bolts and adjust valve clearance after first 50 hours on new and overhauled engines, then adjust valve clearance each 500 hours thereafter | |
| Battery | Inspect | 100 hr | Check battery condition | |
| Crankcase oil | Change | 100 hr | First service — Or annually; perform more often in extremely dusty conditions (Note 3) | |
| Fuel transfer pump sediment bowl and filter | Clean | 100 hr | See Note 1 | |
| Governor linkage | Clean | 100 hr | Carefully pull neoprene governor ball joints apart and clean them; do not lubricate | |
| Oil filter | Replace | 100 hr | ||
| Battery electrolyte level | Check | 200 hr | Check level of electrolyte at least every 200 hours of operation | |
| Crankcase breather | Clean | 200 hr | ||
| Crankcase breather tube | Clean | 500 hr | 500 hour interval coincides with valve lash adjustments | |
| Start-disconnect circuit | Check | 500 hr | ||
| Valve clearances | Check | 500 hr | Note 4: contact an authorized service center for service | |
| Primary fuel filter | Change | 600 hr | ||
| Torsional washers | Inspect | 1500 hr | Note 5: check yearly on non-commercial sets | |
| Generator | Clean | 2000 hr | ||
| Nozzle spray pattern | Check | 2000 hr | Note 4 | |
| Valves | Other | 2000 hr | Grind valves (if required); Note 4 | |
| Secondary fuel filter | Change | 3000 hr | ||
| General overhaul | Other | 5000 hr | If required; Note 4 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
22| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Start-disconnect centrifugal switch point gap | 0.020 | in. (0.51 mm) | |
| Pressure | Engine oil pressure at operating temperature | 35 to 55 | psi (241 to 379 kPa) | at operating temperature |
| Pressure | Exhaust total back pressure of all system components | must not exceed maximum back pressure limits | ||
| Pressure | LO OIL PRES shutdown at engine oil pressure | 14 | psi (97 kPa) | |
| Pressure | PRE LO OIL PRES lamp lights at engine oil pressure | 20 | psi (138 kPa) | |
| Resistance | Battery electrolyte specific gravity, fully charged (corrected) | 1.260 | specific gravity | corrected to 80°F (27°C) |
| Resistance | Charge battery if specific gravity is below | 1.215 | specific gravity | |
| Speed | Centrifugal switch closes when engine speed reaches | 900 | rpm | |
| Speed | Engine speed (50/60 Hz) | 1500/1800 | rpm | |
| Speed | Governor speed variation, no-load to full-load | 3 | hertz | no-load to full-load operation |
| Speed | Starter disconnects when engine speed reaches | 450 to 570 | r/min | |
| Temperature | Coolant temperature | 170° to 216° | °F (77° to 102° C) | depending on the load and ambient temperature |
| Temperature | Exercising: engine oil temperature to be held at | 180 | °F (82.2° C) | for at least 30 minutes |
| Temperature | HI ENG TEMP shutdown above | 230 | °F (110° C) | |
| Temperature | LOW ENG TEMP (LET) lamp lights at coolant temperature of | 70 | °F (21° C) | |
| Temperature | PRE HI ENGINE TEMP lamp lights at approximately | 220 | °F (104° C) | |
| Torque | Cylinder head bolt torque | 44 - 46 | ft-lb (60 - 62 N·m) | |
| Torque | Glow plug torque | 10-15 | ft-lb (14 - 20 N·m) | |
| Valve clearance | Valve clearance, exhaust | 0.016 | in. (0.41 mm) | engine at room temperature about 70°F (21°C) |
| Valve clearance | Valve clearance, intake | 0.011 | in. (0.28 mm) | engine at room temperature about 70°F (21°C) |
| Voltage | DC voltmeter reading while genset running | 12 to 14 | volts | genset running |
| Voltage | Voltage adjust rheostat range | plus or minus five | percent of rated output voltage |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | SAE 15W40 | API Classification CC/CD, CD/SG or CE/SG | 6.5 U.S. quarts (6.0 l) | Table 9-2 viscosity/temperature chart: 5W30, 15W40, 10W30/10W40; 15W40 preferred summer. Limited use of 10W-30 for easier starting below 23°F (-5°C) | |
| Fuel | ASTM 2-D (No. 2 Diesel) or ASTM 1-D (No. 1 Diesel) | minimum Cetane number of 45; viscosity above 1.3 cSt; low-sulfur fuel with cloud point at least 10 degrees below lowest expected fuel temperature | below 0°C | Use number 1 diesel fuel when ambient temperatures are below 0°C (32°F) or during long periods of light engine load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
12| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| FAULT 1 | Fault 1 (red lamp) | Indicates an undedicated fault; may be field programmed as shutdown or non-shutdown, and as timed or non-timed fault (normally set for timed shutdown). | Shutdown | Nature of fault determined at installation design; correct the fault and reset the control. |
| FAULT 2 | Fault 2 (red lamp) | Indicates same features as Fault 1 (normally set for timed shutdown). | Shutdown | Nature of fault determined at installation design; correct the fault and reset the control. |
| HI ENG TEMP | High Engine Temperature (red lamp) | Indicates engine has shut down because of critically high engine temperature (above 230°F / 110°C) or low coolant level. | Shutdown | Allow engine to cool; check coolant level and replenish; check for obstructions to cooling airflow and slipping fan belt; reset control and restart. |
| LO FUEL | Low Fuel (yellow lamp) | Indicates fuel supply is marginally low. | Warning | Check fuel supply and replenish as required. |
| LO OIL PRES | Low Oil Pressure (red lamp) | Indicates engine has shut down because of critically low oil pressure (14 psi / 97 kPa). | Shutdown | Check oil level, lines and filters; replenish oil if low; reset control and restart; contact service center if oil pressure is 20 psi (138 kPa) or lower. |
| LOW ENG TEMP | Low Engine Temperature (yellow lamp) | Lights if engine temperature is marginally low for starting (70°F / 21°C or lower); may indicate an inoperative coolant heater. | Warning | Check coolant heater power supply, coolant level and heater operation. |
| OVERCRANK | Overcrank (red lamp) | Indicates engine has failed to start during the cranking period. | Shutdown | Check for loss of engine prime, empty fuel tank, fuel leaks, or plugged fuel lines; check filters; reset control and restart. |
| OVERSPEED | Overspeed (red lamp) | Indicates engine has shut down because of excessive speed. | Shutdown | Contact an authorized service center for service. |
| PRE HI ENG TEMP | Pre-High Engine Temperature (yellow lamp) | Indicates engine temperature is marginally high (approximately 220°F / 104°C) or coolant level is low on optionally wired sets. | Warning | Reduce load if possible; check air inlets and outlets and remove obstructions to airflow. |
| PRE LO OIL PRES | Pre-Low Oil Pressure (yellow lamp) | Indicates engine oil pressure is marginally low (20 psi / 138 kPa). | Warning | Reduce load or prepare to shut down; follow troubleshooting step 5/6 procedures. |
| RUN | Run (green lamp) | Comes on when starter circuit opens after set starting. | Info | Indicates all engine systems are normal; no corrective action required. |
| SWITCH OFF | Switch Off (flashing red lamp) | Indicates generator set is not in automatic start mode. | Warning | Move the Run/Stop/Remote switch to the Remote position for automatic starting. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Centrifugal Switch Adjustment adjustment
⚠ Shut down the set and disconnect the battery cable, negative (-) terminal first, before setting the breaker point gap
- Locate the start-disconnect centrifugal switch on the side of the engine, above the oil filter.
- If necessary, loosen the stationary contact and adjust the point gap to 0.020 inch (51 mm).
- Replace burned or faulty points.
Charge Rate Adjustment adjustment
⚠ Avoid overcharging the battery
⚠ Do not smoke or allow any flame, sparks, or arc-producing devices in the battery area
- Locate the adjustable resistor slide tap in the charging circuit, found in the generator air outlet.
- If necessary, increase the charging rate slightly by moving the slide tap up.
- Make small increments of change until the proper rate has been determined.
- Adjust this slide tap only when the engine is stopped.
Generator Voltage Check and Adjustment adjustment
⚠ High voltages can cause injury or death; use extreme caution when working on electrical components
Tools: Screwdriver, Wrench
- Move the Run/Stop/Remote switch on the engine control panel to the Run position.
- Move the Phase Selector switch to read generator output current and voltage.
- Insert a screwdriver into the Voltage Adjust potentiometer and carefully loosen the locking nut with a wrench.
- While observing the voltmeter, slowly turn the screwdriver clockwise to increase voltage or counterclockwise to decrease voltage.
- Adjust to the rated nameplate voltage.
- Tighten the locking nut, being careful not to change the adjustment.
- Move the Phase Selector switch to the Off position.
Governor Sensitivity Adjustment adjustment
- Turn the sensitivity adjusting ratchet to adjust governor sensitivity (no-load to full-load speed droop).
- Radiator cooled sets: turn the ratchet clockwise for more sensitivity (less speed drop at full load).
- Radiator cooled sets: turn the ratchet counterclockwise for less sensitivity (more speed drop).
- City water cooled sets: turn the ratchet counterclockwise for more sensitivity.
- After making the sensitivity adjustment, readjust the speed.
Governor Speed Adjustment adjustment
Tools: Stroboscope, Frequency meter
- Turn the governor speed adjusting nut clockwise (more spring tension) to increase rpm.
- Turn the nut counterclockwise to reduce governed speed.
- Use a stroboscope or a frequency meter to make this adjustment.
Valve Clearance Adjustment adjustment
⚠ Incorrect valve clearance adjustment can lead to irrevocable damage to the generator set; only qualified personnel should perform this adjustment
Tools: Socket wrench, Feeler gauge, Torque wrench
- Check the valve clearance when the engine is at room temperature, about 70°F (21°C).
- Turn the flywheel until the cylinder to be adjusted is on its compression stroke.
- Turn the flywheel an additional 10 to 45 degrees clockwise so the piston is in its power stroke with both valves closed.
- Check cylinder head-bolt torque prior to valve clearance adjustment.
- Loosen the locknut securing the rocker arm to the cylinder head to increase clearance; tighten it to reduce clearance.
- Using a feeler gauge, check the clearance between the rocker arm and the valve until the proper gap is established.
Battery Cleaning and Specific Gravity Check maintenance
⚠ Do not smoke or allow any source of ignition while servicing batteries
⚠ Always remove the negative (-) cable first, and reconnect it last to prevent arcing
Tools: Battery hydrometer
- Disconnect the negative ground strap from the battery before working on any part of the electrical system or engine.
- Wipe the batteries clean with a damp cloth whenever dirt appears excessive.
- If corrosion is present, remove battery cables and wash terminals with an ammonia solution or a solution of 1/4 pound baking soda in 1 quart of water.
- Flush the outside of the battery and surrounding areas with clean water.
- Coat the terminals with a light application of petroleum jelly or non-conductive grease.
- Use a battery hydrometer to check the specific gravity of the electrolyte in each cell; hold the hydrometer vertical.
- Correct the reading by adding four gravity points (0.004) for every ten degrees the electrolyte temperature is above 80°F (27°C).
Contractor Model Air Cleaner Cleaning maintenance
⚠ Filters should be handled with care to prevent damage; if the filter becomes damaged, install recommended replacement part
- Remove pre-cleaner and wash out dirt; dry and reinstall.
- Loosen clamp and remove end cover.
- Remove thumbscrew and take out element.
- Wash element in detergent and water (use new element after 6 washings); dry and reinstall.
- Remove air cleaner baffle from cover, wash out dirt, and reinstall in cover.
- Install cover with "TOP" up and tighten clamp.
Crankcase Breather Cleaning maintenance
- Remove hose clamp, breather hose, breather cap clamp and insulator halves to release breather cap and valve assembly.
- Wash cap, valve assembly and baffle in suitable solvent.
- Dry and reinstall.
Oil Change maintenance
⚠ Hot crankcase oil can cause burns if spilled or splashed on skin; keep fingers and hands clear when removing the oil drain plug and wear protective clothing
Tools: Drain pan
- Stop the engine and drain the crankcase oil while the engine is still hot.
- Place a pan under the drain outlet and remove the oil drain plug or open the oil drain valve.
- After the oil is completely drained, replace the drain plug or close the drain valve.
- Replace oil filter if necessary before adding oil.
- Refill with oil of the correct API designation and SAE viscosity grade for the temperature conditions.
Oil Filter Change maintenance
⚠ Hot crankcase oil can cause burns if spilled or splashed on skin
Tools: Container
- Place a container under the oil filter and remove the filter by turning it counterclockwise.
- Clean the filter mounting area.
- Coat the oil filter gasket with clean oil.
- Install the new filter by turning it clockwise until the gasket touches the mounting base.
- Tighten the filter 1/2 turn.
Out-of-Service Protection maintenance
- Exercise the generator set until the engine is up to operating temperature.
- Shut down the engine; disconnect battery and store in a cool, dry place. Connect battery to a charger every 30 days.
- Drain the oil base while it is still warm; refill and attach a warning tag indicating the viscosity of oil used.
- Service the air cleaner.
- Clean throttle and governor linkage and protect by wrapping with a clean cloth.
- Plug the intake and exhaust outlets to prevent entrance of moisture, bugs, dirt, etc.
- Clean and wipe the entire unit; coat parts susceptible to rust with a light coat of grease or oil.
- Provide a suitable cover for the entire unit after the unit has cooled down.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 100 | 1 | V4-V1 | 4 lead reconnectable | 50 Hz |
| 100/200 | 1 | V4-V1 | 12 lead reconnectable | 50 Hz |
| 110 | 1 | V4-V1 | 4 lead reconnectable | 50 Hz |
| 110/190 | 3 | V4-V1 | 12 lead reconnectable | 50 Hz |
| 110/220 | 1 | V4-V1 | 12 lead reconnectable | 50 Hz |
| 115 | 1 | V4-V2 | 4 lead reconnectable | 50 Hz |
| 115/220 | 3 | V4-V2 | 12 lead reconnectable | 50 Hz |
| 115/230 | 1 | V4-V2 | 12 lead reconnectable | 50 Hz |
| 120 | 1 | V4-V1 | 4 lead reconnectable | 60 Hz |
| 120 | 1 | V4-V3 | 4 lead reconnectable | 50 Hz |
| 120/208 | 3 | V4-V1 | 12 lead reconnectable | 60 Hz; jumper wire connection on voltage regulator VR21, per representative reconnection diagram (YD generators) |
| 120/208 | 3 | V4-V3 | 12 lead reconnectable | 50 Hz |
| 120/240 | 1 | V4-V1 | 12 lead reconnectable | 60 Hz |
| 120/240 | 1 | V4-V3 | 12 lead reconnectable | 50 Hz |
| 127/220 | 3 | V4-V2 | 12 lead reconnectable | 60 Hz |
| 139/240 | 3 | V4-V3 | 12 lead reconnectable | 60 Hz |
| 220/380 | 3 | V4-V1 | 12 lead reconnectable | 50 Hz |
| 230/400 | 3 | V4-V2 | 12 lead reconnectable | 50 Hz |
| 240/416 | 3 | V4-V1 | 12 lead reconnectable | 60 Hz |
| 240/416 | 3 | V4-V3 | 12 lead reconnectable | 50 Hz |
| 254/440 | 3 | V4-V2 | 12 lead reconnectable | 60 Hz |
| 254/440 | 3 | V4-V4 | 12 lead reconnectable | 50 Hz |
| 277/480 | 3 | V4-V3 | 12 lead reconnectable | 60 Hz |
| 347/600 | 3 | V4-V1 | 12 lead reconnectable | 60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Cummins/Onan 12.5 RDJC?
The Cummins/Onan 12.5 RDJC is rated 12.5 kW standby (15.625 kVA).
What engine does the Cummins/Onan 12.5 RDJC use?
The Cummins/Onan 12.5 RDJC is powered by the Cummins/Onan Onan Diesel 4-cyl engine.
What kind of fuel does the Cummins/Onan 12.5 RDJC run on?
The Cummins/Onan 12.5 RDJC runs on #1 or #2 diesel.
What's the oil capacity on a Cummins/Onan 12.5 RDJC?
The Cummins/Onan Onan Diesel 4-cyl engine in the Cummins/Onan 12.5 RDJC has an oil capacity of 5.7 liters.
How much coolant does the Cummins/Onan 12.5 RDJC hold?
The Cummins/Onan 12.5 RDJC cooling system holds 12 liters (3.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
How much does the Cummins/Onan 12.5 RDJC weigh?
The Cummins/Onan 12.5 RDJC has a dry weight of 426 kg (939 lb).
What voltages is the Cummins/Onan 12.5 RDJC available in?
The Cummins/Onan 12.5 RDJC is offered in 120/240 V, 120/208 V, 127/220 V, 139/240 V, 3-phase.
What size battery does the Cummins/Onan 12.5 RDJC need?
The Cummins/Onan 12.5 RDJC uses 1 battery, 12 Volts DC V each, 560 amps (cold cranking) at 32°F (0°C); 800 amps (cold cranking) at 0°F (-18°C) CCA, group 2 (6V in series) / Group 5D, per the manufacturer specification sheet.
What alternator comes on the Cummins/Onan 12.5 RDJC?
The Cummins/Onan 12.5 RDJC uses a YD alternator. It has 4 poles.
Troubleshooting
36Fault codes
| Code | Meaning | Cause |
|---|---|---|
| FAULT 1 | The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run | The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay |
| FAULT 2 | The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run | The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay |
Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Engine does not start (blue-white exhaust smoke; engine is getting fuel) | Air heater element does not glow red within 30 seconds | Observe air heater through air inlet hole or by removing air cleaner; engage preheat; check air heater and glow plug wiring: connections tight? free from corrosion? |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Fuel system not primed | Prime fuel system; observe fuel flow from return line |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Fuel solenoid rod does not pull in and throttle arm does not follow when start switch is turned on | Check for binding linkage; check for loose or broken wires |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Fuel tank empty | Check fuel supply system |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Shutoff valves closed | Check fuel supply system |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Fuel lines kinked | Check fuel supply system |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Loose connections | Check fuel supply system |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Clogged fuel filters | Check fuel supply system |
| Engine does not start (little or no exhaust smoke; engine is not getting fuel) | Transfer pump may be defective | Crank engine and observe fuel flow from return line; if fuel does not spurt out, pump may be defective |
| Engine does not start in cold temperatures below 32°F (0°C) | Incorrect fuel or oil viscosity; batteries not fully charged | Use Number 1 diesel fuel; use correct viscosity oil; keep batteries fully charged; do not use ether starting aid |
| Cranking does not stop automatically when engine comes up to speed | Centrifugal switch and start-disconnect relay | Hold start switch to ON until the centrifugal switch automatically disengages starter motor |
| Engine fails to start in 45 to 120 seconds (cranking limiter trips and cranking stops) | Wait one minute before resetting the cranking limiter and trying to start the engine | |
| Stop circuit fails | Push governor arm down to shut off fuel in injection pump | |
| Emergency stop resulting from low oil pressure or high water temperature condition | Dangerously high coolant (water) temperature or low oil pressure | Investigate and correct the cause; press reset button on control panel before restarting |
| Green RUN lamp lights following engine startup | All engine systems are normal | No corrective action required |
| PRE HI ENGINE TEMP lamp lights. Engine continues to operate | Engine is operating near its capacity and temperature has risen to approximately 220 °F (104 °C) or coolant level is low on optionally wired sets | Reduce load if possible by turning off non-critical loads; check air inlets and outlets and remove any obstructions to airflow; if engine can be stopped, follow procedure in step 3 |
| HI ENG TEMP lamp lights. Engine shuts down | Engine has overheated (engine temperature has risen above 230 °F/110 °C) or coolant level is low | Allow engine to cool down completely before proceeding with the following checks: check coolant level and replenish if low, look for possible coolant leakage points and repair if necessary; check for obstructions to cooling airflow and correct as necessary; check for a slipping fan belt and tighten if loose; reset control and restart after locating and correcting problem; contact an authorized service center if none of the above |
| PRE LO OIL PRES lamp lights. Engine continues to operate | Engine oil pressure has dropped to 20 psi (138 kPa) | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure; if engine can be stopped, follow procedures in step 5 |
| LO OIL PRES lamp lights. Engine shuts down | Engine oil pressure has dropped to 14 psi (97 kPa) | Check oil level, lines and filters; if oil system is OK but oil level is low, replenish; reset control and restart; contact an authorized service center if oil pressure is 20 psi (138 kPa) or lower |
| OVERCRANK lamp lights and engine stops cranking, or engine runs, shuts down, and LO OIL PRES lamp lights | Possible fuel system problem | Check for loss of engine prime, empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; check for dirty fuel filter and replace if necessary (see Maintenance section); check for dirty or plugged air filter and replace if necessary (see Maintenance section); reset the control and restart after correcting the problem; contact an authorized service center for service if none of the above |
| Engine runs and then shuts down, OVERSPEED lamp lights | Engine has exceeded normal operating speed | Contact an authorized service center for service |
| SWITCH OFF lamp flashes | Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used | Move the Run/Stop/Remote switch to the Remote position for automatic starting |
| LO FUEL lamp lights. Engine continues to run | Diesel fuel supply is running low | Check fuel supply and replenish as required |
| LO FUEL LAMP lights. Engine shuts down and LO OIL PRES lamp lights | Engine has run out of fuel | Check fuel level and replenish as required |
| LO ENG TEMP lamp lights. Set is in standby mode but is not operating. (Lamp lights when engine coolant temperature is 70 °F (21 °C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm even during initial generator set operation.) | Engine coolant heater is not operating, is not circulating coolant, or ambient temperature has exceeded capability of heater | Check for the following conditions: coolant heater not connected to power supply — check for blown fuse or disconnected heater cord and correct as required; check for low coolant level and replenish if required, look for possible coolant leakage points and repair as required; contact an authorized service center if none of the above |
| Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits | The monitor board or a sensor may be at fault | Contact an authorized service center for service |
| Engine starts from generator control panel but will not start automatically or from a remote panel. (Note: The Run/Stop/Remote switch must be in the Remote position for automatic or remote starting) | Remote circuit breaker is tripped | Reset breaker and restart; contact an authorized service center if breaker trips after resetting |
| Engine will not crank | Possible fault with control or starting system: fault lamp on | Correct fault and reset control |
| Engine will not crank | Possible fault with control or starting system: poor battery cable connections | Clean the battery cable terminals and tighten all connections |
| Engine will not crank | Possible fault with control or starting system: discharged or defective battery | Recharge or replace the battery |
| Engine will not crank | Possible fault with control or starting system: emergency stop button (if equipped) pushed in | To reset, pull switch out and move Run/Stop/Remote switch to Stop position. Then push test switch to Reset/Lamp position |
| Engine will not crank | Possible fault with control or starting system | Contact an authorized service center if none of the above |
| No AC output voltage | Breaker is tripped | Reset breaker; contact an authorized service center if voltage buildup causes breaker to trip |
| Green RUN lamp does not light following engine startup | Possible Start/Disconnect relay failure | Contact an authorized service center for assistance |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Repair guides
20- Automatic Starting and Stopping
- Battery Cleaning and Specific Gravity Check
- Break-In
- Centrifugal Switch Adjustment
- Charge Rate Adjustment
- Contractor Model Air Cleaner Cleaning
- Crankcase Breather Cleaning
- Emergency Stop
- Exercising the Generator Set
- Generator Voltage Check and Adjustment
- Governor Sensitivity Adjustment
- Governor Speed Adjustment
- Normal Stop
- Oil Change
- Oil Filter Change
- Out-of-Service Protection
- Priming the Fuel System
- Returning a Unit to Service
- Starting at Control Panel
- Valve Clearance Adjustment
Step-by-step procedures compiled from the Cummins/Onan service manual for this model.
Parts
4| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 300-0688 | Switching regulator | Avr | eBay | |
| 300-1540 | AVR-A VOLTAGE REGULATOR | 1 | Avr | Amazon eBay $2250.00 |
| 130-0626 | Pencil, Zinc (Included in Heat Exchanger) | 1 | Service part / kit | Amazon eBay |
| 625-2758 | Reconnection Diagrams (drawing No. 625-2758, Rev. A, modified 12/1/93) | Service part / kit | eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 100% | 4.92 | 1.3 |
| Standby | 100% | 6.0 | 1.6 |