Cummins/Onan 12.5 RDJC / 15.0 RDJC — Out-of-Service Protection

Maintenance · Generator set

For the Cummins/Onan 12.5 RDJC / 15.0 RDJC, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan 12.5 RDJC, Cummins/Onan 15.0 RDJC, Cummins/Onan RDJC

Procedure

  1. Exercise the generator set until the engine is up to operating temperature.
  2. Shut down the engine; disconnect battery and store in a cool, dry place. Connect battery to a charger every 30 days.
  3. Drain the oil base while it is still warm; refill and attach a warning tag indicating the viscosity of oil used.
  4. Service the air cleaner.
  5. Clean throttle and governor linkage and protect by wrapping with a clean cloth.
  6. Plug the intake and exhaust outlets to prevent entrance of moisture, bugs, dirt, etc.
  7. Clean and wipe the entire unit; coat parts susceptible to rust with a light coat of grease or oil.
  8. Provide a suitable cover for the entire unit after the unit has cooled down.

Specs & values

  • The inherent lubricating qualities of No. 2 diesel fuel normally protect cylinders for at least 30 days out of service

Full service-parts list: Cummins/Onan RDJC →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.