Cummins/Onan 12.5 RDJC / 15.0 RDJC — Normal Stop
Operation · Control panel
For the Cummins/Onan 12.5 RDJC / 15.0 RDJC, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan 12.5 RDJC, Cummins/Onan 15.0 RDJC, Cummins/Onan RDJC
Procedure
- Run the genset at no load for three to five minutes before stopping.
- Move the Run/Stop/Remote switch or remote starting switch to the STOP position.
- If the stop circuit fails, push the governor arm down to shut off the fuel injection pump.
Specs & values
- Time delay stop adjustable from 0.5 to 15 minutes; approximately 3 to 5 minutes is recommended
Full service-parts list: Cummins/Onan RDJC →