The Caterpillar C32 is a 1000 kW (1250 kVA) diesel standby generator set powered by a Caterpillar C32 engine. It is available at 480 V, 3-phase and 50 Hz. It holds about 4730 L (1249.5 gal) of oil and 138 L (36.5 gal) of coolant, with a maximum ambient rating of 32 °C. Starting uses 1 group-31 battery rated 1400 CCA at 24 V. The set weighs about 7131 kg (15721 lb).

1000 kW
Standby
32.1 L
Displacement
4730.0 L
Oil capacity
7
Document types

How to read your Caterpillar serial & model number →

Typical fuel consumption for 1000–1005 kW Diesel generators →

Compare with other 1000–1005 kW Diesel generators →

Service parts for the C32

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required
4350408Air filtersee priceeBay

Fuel system

1 required
1R-0762Fuel filter (secondary)$33.99eBay

Oil system

1 required

Cooling system

1 required
1195148Coolantsee priceeBay

Electrical

1 required
7L7871Batterysee priceeBay

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power1000 kW
Standby kVA1250
Prime power880 kW
EmissionsLow BSFC
ControllerEMCP 4.2B, EMCP 4.4
Oil capacity4730.0 L
Voltage options480 V
Phase3
Power factor0.8
Circuit breaker1600 A
Battery group31
Battery cranking1400 CCA
Battery voltage24V V
Battery quantity1
Coolant capacity138 L
Max ambient32 °C
Dry weight7131 kg

Engine

Caterpillar C32
Oil capacity4730.0 L
Coolant capacity5000.0 L
Displacement32.1 L
Aspirationturbocharged
Rated speed1800 rpm

Filters for the Caterpillar C32

3

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Oil filterP551808Lube Filter, Spin-On Full FlowCATERPILLAR 1R1808, CATERPILLAR 1R808, NAPA 7792, BALDWIN B7299 KuduParts $80.00
Fuel filterP551316Fuel Filter, Spin-OnCATERPILLAR 1R0755, CATERPILLAR 3890433, NAPA 3685, BALDWIN BF7639 KuduParts $54.00 FridayParts $55.99

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Fuel / water separatorP552023Fuel Filter, Water Separator CartridgeCATERPILLAR 4P7384, CATERPILLAR 5134491, BALDWIN PF7890, EPIROC 57269037 buy

Maintenance & consumables

for the Caterpillar C32
ItemSpecCapacityPart #Interval
Air filterCLEANER GP-AIR-D4350408 eBay
Fuel filter—
Fuel filterFuel Secondary - ADV1R-0762 Amazon eBay $33.99 eBay $34.95 NAPA $43.65 FridayParts $30.63
Oil filterEngine Oil - ADV1R-1808 Amazon eBay $141.00 eBay $59.99 NAPA $45.70 NAPA $45.70 KuduParts $80.00 FridayParts $81.99
Battery24V wet, 1125 CCA, group 317L7871 eBay
Belt—
CoolantExtended Life Coolant (ELC)138.0 L1195148 eBay
Oil—
Spark plug—

Service intervals

40
ItemActionHoursMonthsNotes
BeltsInspect250 hr6 moFirst service — Initial 20 to 40 Service Hours - Inspect/Adjust/Replace
Engine oil (S-O-S oil sample)Test125 hrSevere service occurs at high loads, in high temperatures, and in dusty conditions
Aftercooler CoreClean250 hrEvery 250 Service Hours - Clean/Test
Battery Electrolyte LevelCheck250 hrEvery 250 Service Hours
Coolant (S-O-S coolant analysis Level 1)Test250 hrCat ELC - Every 250 Hours; also the recommended sampling interval for all conventional heavy-duty coolant/antifreeze and for commercial coolants that meet Cat EC-1
Electronic Unit InjectorInspect3000 hrFirst service — Initial 250 Service Hours - Inspect/Adjust
Electronics Grounding StudInspect250 hrEvery 250 Service Hours - Inspect/Clean/Tighten
Engine Air Cleaner Element (Single Element)Replace250 hrEvery 250 Service Hours
Engine Valve LashAdjust3000 hr12 moFirst service — Initial 250 Service Hours (Standard): Inspect/Adjust
Engine Valve LashInspect4000 hrFirst service — Initial 250 Service Hours - Inspect/Adjust
Engine Valve RotatorsInspect3000 hrFirst service — Initial 250 Service Hours
Engine crankcase oil (S-O-S oil sample)Test250 hrTable 6 S-O-S Oil Sampling Interval; severe applications may require a more frequent oil sampling interval
Fuel InjectorAdjust250 hr12 moFirst service — Initial 250 Service Hours (Standard): Inspect/Adjust
Primary air filter elementChange250 hrWhen changing the primary element at 250 operating hours (basis of the without-indicator filter-change comparison)
SCA (Supplemental Coolant Additive) concentrationTest250 hrTest the concentration of SCA or submit a coolant sample at 250 hour intervals or at PM Level 1 intervals; check at every oil change or every 250 hours, whichever occurs first
Coolant (S-O-S coolant analysis Level 2)Test500 hr12 moFirst service — For new systems, refilled systems, and converted systems that use Cat ELC or Cat DEAC; also every year; use the interval that occurs first
Cooling System Coolant Sample (Level 2)Other500 hr12 moFirst service — Initial 500 Hours (for New Systems, Refilled Systems, and Converted Systems) - Obtain
Secondary air filter elementChange750 hrWhen changing the secondary element at 750 operating hours (basis of the without-indicator filter-change comparison)
Cooling System Coolant (DEAC)Change3000 hr36 moEvery 3000 Service Hours or 3 Years
Cooling System Water Temperature RegulatorReplace3000 hr36 moEvery 3000 Service Hours
Engine MountsInspect3000 hrEvery 3000 Service Hours
Engine Speed/Timing SensorsCheck3000 hrEvery 3000 Service Hours - Check/Clean/Calibrate
TurbochargerInspect5000 hr36 moEvery 5000 Service Hours
Cat ELC Extender addition (cooling system)Other6000 hrTreat the cooling system with Cat ELC Extender at 6000 hours or one half of the coolant service life
Cooling System Coolant Extender (ELC)Other6000 hr36 moEvery 6000 Service Hours or 3 Years: Add
Fan Drive BearingReplace8000 hrEvery 8000 Service Hours
Rotating RectifierCheck8000 hr36 moEvery 8000 Service Hours (Standard)
Overhaul (Top End)Other9000 hrEvery 605 670 L (160 000 US gal) of fuel or 9000 Service Hours - C27
Coolant (Cat ELC)Change12000 hr12000 service hours or six years; use the interval that occurs first
Cooling System Coolant (ELC)Change12000 hr72 moEvery 12000 Service Hours or 6 Years
Overhaul (Major)Other18000 hrEvery 1 211 330 L (320 000 US gal) of fuel or 18 000 Service Hours - C27
AlternatorInspect6000 hr72 moEvery Year (Standby); Every 6000 Service Hours or 6 Years (Standard)
BatteriesReplace36 moEvery 3 Years (Standby); When Required (Standard)
Coolant (S-O-S coolant analysis Level 1 and Level 2)Test12 moCat DEAC - Yearly
Cooling System Coolant Sample (Level 1)Other250 hr6 moEvery 6 Months (Standby): Obtain; Every 250 Service Hours (Standard)
Cooling System Supplemental Coolant Additive (SCA)Test250 hr6 moEvery 6 Months (Standby): Test/Add; Every 250 Service Hours (Standard)
Crankshaft Vibration DamperInspect3000 hr12 moEvery Year (Standby); Every 228000 L fuel or 3000 Service Hours (Standard)
EngineClean3000 hr12 moEvery Year (Standby); When Required (Standard)
Engine Air Cleaner Element (Dual Element)Clean250 hr12 moEvery Year (Standby): Clean/Replace; Every 19000 L fuel or 250 Service Hours (Standard)
Engine Crankcase BreatherClean500 hr12 moEvery Year (Standby); Every 38000 L fuel or 500 Service Hours (Standard)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceBelt deflection9 to 15mm (0.35 to 0.59 inch)110 N (25 lb ft) force applied midway between the pulleys
ClearanceCoolant level below bottom of filler pipe / sight glass level13mm (0.5 inch)engine stopped and cool
OtherBearing bracket sleeve step minimum0.0762mm
OtherCat Fast Acting Cooling System Cleaner concentration0.5L (1 pint) per 15 L (4 US gal) of cooling system capacitycooling systems with normal deposits
OtherCooling system fill rate19L (5 US gal) per minuteno faster than, to avoid air locks
OtherGross Input Torque (TH55-E70)12 667N•m (9350 lb-ft)
OtherGross Input Torque (TH55-E90)12 677N•m (9350 lb-ft)
OtherHydrosolv liquid cleaner concentrationtwo to fivepercentat temperatures up to 93°C (200°F)
OtherRadiator cooling package design ambient temperature48.9°C (120° F)with 50/50 water/Extended Life Coolant mixture
OtherRadiator cooling package maximum elevation1524m (5000 ft)with 50/50 water/Extended Life Coolant mixture
OtherSpeed/timing sensor sliphead extension (install)minimum 4mm
OtherSpeed/timing sensor sliphead push-in forceat least 22Nfrom extended position
OtherStall Torque Ratio (TH55-E70)2.23
OtherStall Torque Ratio (TH55-E90)2.23
OtherSupplemental coolant additive (SCA) concentration - conventional coolant6percentdo not exceed
OtherSupplemental coolant additive (SCA) concentration - water and SCA systems8percentdo not exceed
PressureAir inlet filter differential pressure (clean filter)0.15kPa
PressureMaximum air pressure at the nozzle for cleaning205kPa (30 psi)less than
PressureMaximum air pressure for cleaningbelow 205kPa
PressureMaximum filtered dry air pressure for air cleaner cleaning207kPa (30 psi)maximum
PressureMaximum water pressure for cleaning275kPa (40 psi)less than
PressureMaximum water pressure for cleaningbelow 275kPa
PressurePrimary filter/water separator element change point (vacuum gauge)50 to 70kPa (15 to 20 inches Hg)
PressurePrimary filter/water separator element change pressure50 to 70kPa
PressureWS255 pump plunger load238,000lb (107,960 kg)
PressureWS273XD pump plunger load275,000lb (124 738 kg)
PressureWS305XD pump plunger load250,000lb (113 398 kg)
ResistanceExciter armature (rotor) L2less than 0.1ohms
ResistanceExciter field (stator) L1 windingapproximately 3.0 to 6.0ohmsat room temperature
ResistanceMain armature (stator) L4less than 0.1ohms
ResistanceMain field (rotor) L3 windingapproximately 1.25 to 2.0ohmsat room temperature
ResistancePilot exciter armature L5less than 0.1ohms
ResistanceThree-diode rectifier block forward reading0.4 to 1.0meter on diode range
ResistanceVaristor CR7minimum 15000ohms
SpeedEngine speed for cooling system air purge1500rpm
SpeedMaximum Input Speed (TH55-E70/TH55-E90 transmissions)1970rpm
SpeedRated Input Speed (TH55-E70/TH55-E90 transmissions)1900rpm
TemperatureAir cleaner oven drying maximum temperature82°C (160 °F)do not exceed
TemperatureAir cleaner wash tank maximum temperature60°C (140 °F)with warm water and cleaning agent
TemperatureBall bearing installation heating107°Cten minutes, induction heater
TemperatureCoolant temperature during DEAC cooling system cleaner flush82°C (180 °F)at least, run at low idle minimum of 30 minutes
TemperatureCoolant temperature during ELC cooling system flush49 to 66°C (120 to 150 °F)run at low idle until temperature reached
TemperatureCoolant temperature for cleaning system flush (DEAC change)82°Cminimum
TemperatureGenerator bearing RTD alarm85°C
TemperatureGenerator bearing RTD shutdown95°C
TemperatureHub installation heating400°Cthree hours
TemperatureJacket water heater maintained coolant temperature at 0 °C ambient32°Capproximately
TemperatureMaximum winding temperature when drying generator85°C
TemperatureOven method generator drying temperature65°Cfour hours, forced air oven
TemperatureStator winding alarm setpoint (continuous)155°C
TemperatureStator winding alarm setpoint (standby)180°C
TemperatureStator winding shutdown setpoint (continuous)165°C
TemperatureStator winding shutdown setpoint (standby)190°C
TorqueAir cleaner service indicator2N·m
TorqueAir compressor SAE "A" hydraulic pump drive maximum torque (374 L/min and 467 L/min compressors)60N•m (44 lb-ft)C7, C9 ACERT
TorqueEngine speed/timing sensor40 ± 5N·m
TorqueService indicator2N·m (18 lb in)when a new service indicator is installed
VoltageGenerator set functional test minimum measured voltage85VAC
VoltageInsulation test voltage (units 600 V or less)500V
VoltageInsulation test voltage (units more than 600 V)1000V

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant155L EXTENDED LIFE COOLANTPart COOL001
Coolant50/50 mixture water/Caterpillar Extended Life Coolantbelow 48°CRadiator cooling packages designed for up to 48.9° C (120° F) ambient; coolant sump refill capacities vary by oil sump/pan (18 L to 106 L service refill with new oil filter change)
CoolantCOOLANT-LONG LIFE-BULK-1 LITERPart 1195148, order qty 155
CoolantCat DEACDiesel; 3,000 Service Hours or Three Years; annual S·O·SSM Level 2 coolant sampling and analysis
CoolantCat DEAC (Diesel Engine Antifreeze/Coolant)Acceptable coolant; commercial heavy-duty antifreeze/coolant must meet ASTM D4985 or ASTM D6210Conventional heavy-duty coolant/antifreeze. Caterpillar recommends a 1:1 mixture of water and glycol. Do not use a commercial coolant/antifreeze that only meets the ASTM D3306 specification. Do not use Cat SCA at the initial fill when Cat DEAC is used.
CoolantCat ELCDiesel; 12,000 Service Hours or Six Years; add Cat ELC Extender at 6,000 service hours or one half of service life; annual S·O·SSM Level 2 coolant sampling and analysis
CoolantCat ELC (Extended Life Coolant)Caterpillar EC-1 specification (preferred); also meets ASTM D4985, ASTM D6210, and ASTM D3306Service life of 12000 service hours or six years. Premixed ELC provides freeze protection to -37 C (-34 F); ELC Concentrate can be used to lower the freezing point to -52 C (-62 F). An Extender is the only additional maintenance needed at 6000 service hours or one half of the ELC service life. Cat ELC cooling systems can withstand contamination to a maximum of ten percent of conventional heavy-duty coolant/antifreeze and/or SCA.
CoolantCat ELC (Extended Life Coolant); or Cat DEACCaterpillar EC-1 (ELC); ASTM D4985 or ASTM D5345 (heavy-duty)55.0 L1:1 mixture of water and glycol; engine only capacity 55 L
CoolantCat NGECNatural Gas; 16,000 Service Hours or Three Years; use interval that occurs first
CoolantCat SCA (Supplemental Coolant Additive) with waterSCA concentration in a cooling system that uses SCA and water should be six to eight percent by volume; do not exceed the eight percent maximum concentration. If Cat SCA is not used, the commercial SCA must provide a minimum of 2400 mg/L or 2400 ppm (140 grains/US gal) of nitrites in the final coolant mixture when used with water, and a minimum of 1400 mg/L or 1400 ppm (82 grains/US gal) with heavy-duty coolant/antifreeze.
CoolantCommercial long life coolantsCaterpillar Engine Coolant Specification -1 (Caterpillar EC-1)Obtain a Coolant Sample (Level 1) if the cooling system is filled with this coolant instead of Cat ELC.
CoolantExtended Life Coolant (ELC)138.0 L138L extended life coolant; bulk coolant part 1195148, additive part 3690804
CoolantGlycol (ethylene glycol / propylene glycol)Propylene glycol coolant must meet ASTM D6210-04Ethylene glycol: 50 percent = freeze protection -37 C (-34 F), boil protection 106 C (223 F); 60 percent = -52 C (-62 F), 111 C (232 F). Propylene glycol: 50 percent = -32 C (-26 F), 106 C (223 F). Do not use propylene glycol in concentrations that exceed 50 percent; do not use ethylene glycol in concentrations that exceed 60 percent. All Caterpillar diesel engines equipped with air-to-air aftercooling (ATAAC) require a minimum of 30 percent glycol.
CoolantLONG LIFE COOLANTPart LS0332
Engine oilCat DEO (Diesel Engine Oil) 10W-30 and 15W-40Cat ECF-1 (exceeds); API CI-4, API CI-4 PLUS, API CH-4, API CG-4, API CF (Cat DEO SAE 15W-40)Caterpillar oils are used to fill diesel engines at the factory. Non-Caterpillar commercial oils are second choice oils. Do not use API CF-4 oils in Caterpillar diesel engines. Do not use single grade API CF oils or multigrade API CF oils in 3500 Series, C175 Series and smaller DI diesel engines.
Engine oilCat NGEONatural Gas
Engine oilCommercial oils (DI engines)Cat ECF-1 required; API CG-4 multigrade acceptable; API CH-4, API CI-4 and API CI-4 PLUS acceptable only if the requirements of Cat ECF-1 are met; do not use API CF-4 oilsMinimum TBN must be 10 times the fuel sulfur level (ASTM D2896); minimum TBN of the oil is 5 regardless of a low fuel sulfur level. API CG-4 oils: do not exceed the standard oil drain interval.
Engine oilCommercial oils (PC engines)Cat ECF-1; API CH-4, API CI-4, API CI-4 PLUS (if Cat ECF-1 requirements met); API CG-4 multigrade; API CF-4 multigrade; API CFMinimum TBN of the oil that is used in PC engines must be 20 times the fuel sulfur level; minimum TBN of new oil is five. Change the oil when the TBN deteriorates to 50 percent of the original TBN.
Engine oilRe-refined base stock oilsAcceptable if they meet the performance requirements specified by Caterpillar; filtering is inadequate for producing high quality re-refined base stock oils.
Engine oilSynthetic base stock oilsAcceptable if they meet the performance requirements specified for the engine compartment. Caterpillar does not recommend the automatic extension of oil drain intervals for any type of oil.
Engine oilCat Arctic DEO SYN SAE 0W-30-40°C to 30°CEngine Crankcase; Industrial Engines
Engine oilSAE 0W-20-40°C to 10°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 0W-30-40°C to 30°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 0W-40-40°C to 40°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilCat DEO SYN SAE 5W-40-30°C to 50°CEngine Crankcase; Industrial Engines
Engine oilSAE 5W-30-30°C to 30°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilSAE 5W-40-30°C to 50°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)
Engine oilCat DEO SAE 10W-30-18°C to 40°CEngine Crankcase; Industrial Engines
Engine oilSAE 10W-30-18°C to 40°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines); SAE 10W-30 is the preferred viscosity grade for the 3116, 3126, C7, C-9 and C9 diesel engines between -18 C (0 F) and 40 C (104 F)
Engine oilSAE 10W-40-18°C to 50°CTable 1 Lubricant Viscosities for Ambient Temperatures (DI diesel engines)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Determining the cause of a plugged fuel filter (ice or wax) diagnostic
  1. Remove the fuel filters.
  2. Cut the fuel filters open.
  3. Inspect the fuel filter before the filter warms. The inspection will show that the filter is filled with particles of either ice or wax.
Insulation - Test diagnostic

⚠ Personal injury or death can result from electrocution

⚠ Do not touch instrument leads before discharging them

Tools: 300-8648 Insulation Testing Gp

  1. Take the generator out of service and inspect visually for moisture.
  2. Discharge the capacitance of the windings.
  3. Disconnect T0 from ground and disconnect regulator sensing leads.
  4. Connect insulation tester RED lead to ground and BLACK lead to T0.
  5. Set 500 V for units 600 V or less; set 1000 V for units more than 600 V.
  6. Apply voltage and observe readings at 30 seconds and 60 seconds.
  7. Record the 60 second reading, temperature and humidity; remove voltage.
  8. Evaluate readings against previous readings taken under similar conditions.
Rotating Rectifier - Check diagnostic

Tools: Digital multimeter

  1. Set the digital multimeter on the diode range and remove all rectifier leads.
  2. For negative block: place red lead on negative terminal, black lead on AC1, AC2, AC3; readings should be 0.4 to 1.0.
  3. For negative block: place black lead on negative terminal, red lead on AC1, AC2, AC3; meter should read OL.
  4. For positive block: place red lead on positive terminal, black lead on AC1, AC2, AC3; meter should read OL.
  5. For positive block: place black lead on positive terminal, red lead on AC1, AC2, AC3; readings should be 0.4 to 1.0.
  6. Replace the rectifier block if any reading is out of range.
Varistor - Test diagnostic

Tools: Ohmmeter, Test light

  1. Place an ohmmeter across the varistor; resistance should be a minimum of 15000 ohms.
  2. Alternatively, disconnect either lead of the varistor.
  3. Place a test light across the varistor; the lamp should not light.
  4. Reverse the test light; the lamp should still not light.
  5. Replace the varistor if the lamp lights in either direction.
Winding - Test diagnostic

⚠ High voltage can cause severe injury or death

Tools: 6V-7070 Digital Multimeter, 146-4080 Digital Multimeter (RS232)

  1. Place engine control switch in OFF; tag all starting controls.
  2. Disconnect batteries or disable the starting system.
  3. Disconnect the winding being tested from other components.
  4. Measure resistance of exciter armature L2 (less than 0.1 ohm).
  5. Measure main armature L4 (less than 0.1 ohm) and pilot exciter L5 (less than 0.1 ohm).
  6. Measure exciter field L1 (approximately 3.0 to 6.0 ohms) and main field L3 (approximately 1.25 to 2.0 ohms).
  7. Confirm no continuity to ground and no continuity between windings.
Battery Electrolyte Level - Check maintenance

⚠ All lead-acid batteries contain sulfuric acid which can burn the skin and clothing. Always wear a face shield and protective clothing when working on or near batteries.

Tools: 245-5829 Coolant Battery Tester Refractometer

  1. Remove the filler caps; maintain the electrolyte level to the FULL mark on the battery.
  2. Use distilled water, or clean water low in minerals if distilled water is not available. Do not use artificially softened water.
  3. Check the condition of the electrolyte with the 245-5829 Coolant Battery Tester Refractometer.
  4. Keep the batteries clean; clean the battery case with a baking soda/water or ammonia/water solution and rinse with clean water.
  5. Use fine grade sandpaper to clean terminals and cable clamps until surfaces are bright.
  6. Coat the clamps and terminals with 5N-5561 Silicone Lubricant, petroleum jelly or MPGM.
Battery or Battery Cable - Disconnect maintenance

⚠ The battery cover should be removed before any servicing is attempted.

⚠ Removing the battery cables or batteries with the cover in place may cause a battery explosion resulting in personal injury.

  1. Switch the engine to the OFF position; turn the ignition switch OFF and remove the key and all electrical loads.
  2. Disconnect the negative battery terminal at the battery that goes to the start switch; ensure the cable cannot contact the terminal.
  3. Tape the leads in order to help prevent accidental starting.
  4. Proceed with necessary system repairs; reverse the steps in order to reconnect all cables.
Belts - Inspect/Adjust/Replace maintenance

⚠ Replace belts that are worn or damaged. For multiple drive belts, replace belts in matched sets.

  1. Remove the belt guard. Inspect the condition and adjustment of the alternator belts and accessory drive belts.
  2. Check belt tension by applying 110 N (25 lb ft) of force midway between the pulleys; a correctly adjusted belt deflects 9 mm to 15 mm.
  3. To adjust an alternator belt, slightly loosen mounting bolt (2), mounting bolt (3) and adjusting nut (1).
  4. Move the pulley in order to adjust the belt tension.
  5. Tighten the adjusting nuts and mounting bolts; refer to the Specifications, SENR3130 for proper torques.
  6. Install the belt guard. If new belts are installed, check the belt tension again after 30 minutes at rated rpm.
Changing to Cat ELC maintenance

⚠ Do not leave an empty SCA maintenance element on a system that is filled with ELC. The element housing may corrode and leak causing an engine failure.

⚠ Improper or incomplete rinsing of the cooling system can result in damage to copper and other metal components.

⚠ The cooling system cleaner must be thoroughly flushed from the cooling system. Cooling system cleaner that is left in the system will contaminate the coolant. The cleaner may also corrode the cooling system.

Tools: Caterpillar cleaner for cooling systems, 5P-3413 Pipe Sealant, Suitable containers to collect fluids

  1. Drain the coolant into a suitable container.
  2. Dispose of the coolant according to local regulations.
  3. If equipped, remove the empty SCA maintenance element and the element base. Plug the coolant lines or bypass the coolant lines.
  4. Flush the system with clean water in order to remove any debris.
  5. Use Caterpillar cleaner for cooling systems in order to clean the system. Follow the instructions on the label.
  6. Drain the cleaner into a suitable container. Flush the cooling system with clean water.
  7. In systems with heavy deposits, disconnect the hoses. Clean deposits and debris from the hoses and fittings. Install the hoses and tighten the hose fittings.
  8. Fill the cooling system with clean water and operate the engine until the engine is warmed to 49 C to 66 C (120 F to 151 F).
  9. Drain the cooling system into a suitable container and flush the cooling system with clean water.
  10. Repeat Steps 8 and 9 until the system is completely clean.
  11. Fill the cooling system with the Cat ELC.
  12. Operate the engine until the engine is warmed. While the engine is running, inspect the engine for leaks. Tighten hose clamps and connections in order to stop any leaks.
  13. Attach the Special Publication, PEEP5027, "Label" to the cooling system filler for the engine in order to indicate the use of Cat ELC.
Cooling System Coolant (DEAC) - Change maintenance

⚠ Hot coolant can cause serious burns. Loosen the pressure cap slowly to relieve pressure.

⚠ Use only cooling system cleaners approved for Caterpillar engines.

Tools: 9S-8140 Pressurizing Pump

  1. Stop the engine and allow the engine to cool. Loosen the filler cap slowly to relieve pressure; remove the cap.
  2. Open the cooling system drain valve or remove a drain plug; allow the coolant to drain.
  3. Flush the cooling system with clean water in order to remove any debris.
  4. Close the drain valve; clean and install the drain plugs.
  5. Fill with a mixture of clean water and Cat Fast Acting Cooling System Cleaner; install the filler cap.
  6. Start and run the engine at low idle for a minimum of 30 minutes; coolant temperature should be at least 82 °C (180 °F).
  7. Stop the engine and allow to cool; drain, flush with clean water and close the drain valve.
  8. Fill the cooling system with coolant/antifreeze; refer to Refill Capacities and Recommendations.
Cooling System Coolant (ELC) - Change maintenance

⚠ Hot coolant can cause serious burns.

⚠ Clean water only is needed when ELC is drained and replaced.

Tools: 9S-8140 Pressurizing Pump

  1. Stop the engine and allow the engine to cool. Loosen the filler cap slowly to relieve pressure; remove the cap.
  2. Open the drain valve or remove drain plugs; allow the coolant to drain.
  3. Flush the cooling system with clean water in order to remove any debris.
  4. Close the drain valve; clean and install the drain plugs.
  5. Fill the cooling system with clean water; install the filler cap.
  6. Start and run the engine at low idle until temperature reaches 49 to 66 °C (120 to 150 °F).
  7. Stop the engine and allow to cool; drain, flush with clean water and close the drain valve.
  8. Fill the cooling system with Extended Life Coolant (ELC); refer to Refill Capacities and Recommendations.
Cooling System Coolant Extender (ELC) - Add maintenance

⚠ Use only Cat Extended Life Coolant (ELC) Extender with Cat ELC.

⚠ Do NOT use conventional supplemental coolant additive (SCA) with Cat ELC.

  1. Loosen the cooling system filler cap slowly in order to relieve pressure; remove the cap.
  2. Drain enough coolant from the cooling system if necessary to add the Cat ELC Extender.
  3. Add Cat ELC Extender according to the requirements for your engine's cooling system capacity.
  4. Clean the cooling system filler cap and inspect the gaskets.
  5. Replace the filler cap if the gaskets are damaged; install the filler cap.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
312 Lead DeltaT6 and T9 tied together and grounded = neutralT2 and T10 connection is the high phase
312 Lead Wye - High VoltageT10, T11, T12 tied together = neutralTypical high voltage connection (Series Wye, 60 Hz)
312 Lead Wye - Low VoltageT10, T11, T12 tied together = neutralTypical low voltage connection (Parallel Wye, 60 Hz)
36 Lead DeltaTypical Delta Configuration (60 Hz, 6 Lead)
36 Lead WyeT4, T5, T6 tied together = neutralTerminals T4, T5 and T6 become a neutral connection when tied together
2403DeltaProduces 208 V high phase to neutral and 240 V low phase to neutral
4803WyeThree-phase voltage connection

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Caterpillar C32?

The Caterpillar C32 is rated 1000 kW standby (1250.0 kVA).

Which engine powers the Caterpillar C32?

The Caterpillar C32 is powered by the Caterpillar C32 engine.

What fuel does the Caterpillar C32 use?

The Caterpillar C32 runs on diesel.

What's the oil capacity on a Caterpillar C32?

The Caterpillar C32 engine in the Caterpillar C32 has an oil capacity of 4730.0 liters.

What is the cooling system capacity of the Caterpillar C32?

The Caterpillar C32 cooling system holds 138 liters (36.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Caterpillar C32?

The Caterpillar C32 is rated 880 kW prime (1100 kVA), against 1000 kW standby.

What is the dry weight of the Caterpillar C32?

The Caterpillar C32 has a dry weight of 7131 kg (15721 lb).

What voltage does the Caterpillar C32 produce?

The Caterpillar C32 is offered in 480 V, 3-phase.

What battery does the Caterpillar C32 use?

The Caterpillar C32 uses 1 battery, 24V V each, 1400 CCA, group 31, per the manufacturer specification sheet.

Which oil filter part number does the Caterpillar C32 take?

The Caterpillar C32 uses oil filter part number 1R-1808.

Which fuel filter part number does the Caterpillar C32 take?

The Caterpillar C32 uses fuel filter part number 1R-0762.

Which air filter part number does the Caterpillar C32 take?

The Caterpillar C32 uses air filter part number 4350408.

Parts

41
Part #DescriptionQtySystem
1195148COOLANT-LONG LIFE-BULK-1 LITER1Fluid eBay
1R-0762Fuel Secondary - ADV2Fuel filter Amazon eBay $33.99 eBay $34.95 NAPA $43.65 FridayParts $30.63
1R-0770Fuel/Water Separator1Fuel filter eBay $38.77 NAPA $57.83 KuduParts $22.00 FridayParts $24.00 SinoCMP $65.00
1R-1808Engine Oil - ADV1Oil filter Amazon eBay $141.00 eBay $59.99 NAPA $45.70 NAPA $45.70 KuduParts $80.00 FridayParts $81.99
1U-5490Hydrosolv 4165 liquid cleaner, 19 L (5 US gallon)Fluid Amazon eBay
3690804ADDITIVE-COOLANT2Fluid eBay $19.67
4350408CLEANER GP-AIR-D1Air filter eBay
4471546TRANSFORMER GP-CURRENT1Sensor eBay
5N-5561Silicone LubricantFluid Amazon eBay
5N9597VOLTAGE INDICATOR 480V, 60HZ1Sensor eBay
ACL0017STANDARD AIR CLEANER 171Air filter eBay
COOL001155L EXTENDED LIFE COOLANT1Fluid eBay
CT20006CT 2000:5 RATIO1Sensor eBay
JWH0241JW HEATER - SINGLE W/PUMP 60HZ1Pump eBay
LF4811P FRAME / R FRAME DC REGULATOR1Avr eBay
LF5341JWH W/ PUMP - 60HZ1Pump eBay
LF9848IVR-EM10A1Avr eBay
LS0328ELECTRIC STARTING MOTOR-HEAVY1Starter eBay
LS0332LONG LIFE COOLANT1Fluid eBay
M-3675181PistonPiston Amazon eBay
M-3758261PistonPiston Amazon eBay
M-4599781Gasket Set - Oil Cooler & LinesGasket Amazon eBay
M-CK3675181PCylinder KitCylinder kit Amazon eBay
M-CK3758261PCylinder KitCylinder kit Amazon eBay
1535710BATTERY-WET2Service part / kit Amazon eBay $299.97 eBay
174-6854Hydrosolv 100 liquid cleaner, 19 L (5 US gallon)Service part / kit Amazon eBay NAPA $10.64
2323232Connecting rodService part / kit eBay $201.50
2613291MOTOR GP-ELECSTG1Service part / kit eBay
3395996CHARGER-BATTERY1Service part / kit eBay
4864557HEATER GP-GEN1Service part / kit eBay
5770040HEATER GP-JW BSC1Service part / kit eBay
7L787124 VOLT BATTERY SET / BATTERY GP1Service part / kit eBay
7L787224 VOLT BATTERY SET1Service part / kit eBay
BAT2429ENCLO BATT 24V WET 1400CCA 291Service part / kit eBay
BTC1038ENCLOSURE BATT CHARGER 10A1Service part / kit eBay
ELSM248ELEC. START MOTOR HEAVY DUTY1Service part / kit eBay
LF3239SERIES WIRED SPACE HEATERS1Service part / kit eBay
LS1230ENCLOSURE HVY DUTY BATTERY SET1Service part / kit eBay
R-20R2284C15/C18/C27/C32 ACERT Trim file (12-digit serial)1Service part / kit Amazon eBay
R-20R2285C15/C18/C27/C32 ACERT Trim file (12-digit serial)1Service part / kit Amazon eBay
SHK0022SPACE HEATER 1400S FRAME1Service part / kit eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime100%4.541.2

Available documents

Engine spec — Cat-C32-industriemotor (Caterpillar)Spec sheet — XQ1000 LEHE6385-04 (Caterpillar)Operator's manual — Caterpillar-CAT-C27-C32-operation-and-maintenance-manual (Caterpillar)Reference — Aug+2010+Engine+Selection+Guide (Caterpillar)Reference — CMPS+News+Flash+-+Moonen+yachts+rely+on+Caterpillar+powerReference — Caterpillar-Oil-and-Gas-Ratings-Guide-2021-03 (Caterpillar)Reference — LECW2462-25 1 oil gas (Caterpillar)Reference — LEDM3457-27 (Caterpillar)Reference — Specs-and-Description-2 (Caterpillar)Reference — ledh6161 attachments guide (Caterpillar)Owner's manual — C27+and+C32+Industrial+and+Locomotive+Engines-Maintenance+Intervals (Caterpillar)Parts manual — Caterpillar Engines (Caterpillar)Parts manual — LFDH6161-00 HR (Caterpillar)Parts manual — New-CAT-C32-SN-PRH08985-as-shipped (Caterpillar)Parts manual — New-CAT-C32-SN- PRH09523-as-shipped (Caterpillar)Service manual — Caterpillar Diesel Engine Fluid Recommendations (Caterpillar)

This page was generated from the 16 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Fuel filter (secondary) 1R-0762$33.99
Oil filter 1R-1808$45.70
2 priced items$79.69
Other sets with this engine