Baldor (Baldor Generators / Baldor Electric Company) GLC80 Generator Set

The Baldor (Baldor Generators / Baldor Electric Company) GLC80 is a 80 kW standby generator set.

80 kW
Standby
1
Document types

Service parts for the GLC80

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Standby power80 kW
Max ambient50 °C

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filterAIR CLEANER, ELEMENTEA0015A21 eBay

Service intervals

4
ItemActionHoursMonthsNotes
oil levelCheck5 hrCheck oil level regularly; at least every 5 to 8 operating hours
GFCI receptaclesTest1 moCheck by using the Test and Reset buttons monthly
bulk fuelTest24 moEvery two years have fuel checked and changed out to remove water, scale and bacteria
fuel supply piping and connectionsInspect1 moCheck all fuel supply piping and connections monthly for fuel leaks

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

16
TypeItemValueUnitCondition
ClearanceMagnetic pickup back-out after bottoming on flywheel tooth1/2 turnturn
PressureExhaust system backpressure (must not exceed)20inches water column
PressureFuel supply pressure to regulator6 oz (11 inches of water column)oz / in WC
PressureLow oil pressure shutdown #2 setpoint20PSI
ResistanceMaximum allowable resistance of cranking circuit0.0012Ohms12V systems
ResistanceMaximum allowable resistance of cranking circuit0.002Ohms24V systems
ResistanceOil pressure sender (p/n 003654, Datcon p/n 102227) resistance at 0 PSI6284OhmsDatcon sender with MEC software 1.81 or greater
SpeedCrank disconnect speed20% of nominal speed
SpeedNominal engine speed1800RPM
SpeedOverspeed shutdown point110% of nominal speed
TemperatureBattery heater minimum / shutoff50 to 90°F (10 to 32°C)
TemperatureEngine high temperature shutdown #2 setpoint206°F
TemperatureJacket water heater minimum coolant temperature (NFPA 110 priority level 1)90°F (32°C)
TemperatureMaximum ambient temperature122°F (50°C)
VoltageMagnetic pickup output while cranking1.3VACwhile cranking
VoltageMagnetic pickup signal at cranking (run-output fail safe enabled)2.0VACminimum during cranking

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 ethylene glycol and coolant treatmentBaldor recommends 50/50 ethylene glycol and coolant treatment for all engines; solution can be increased to 65% but freeze protection reduced after 65%
Engine oilSAE 30 (Summer); 5W/30 (Winter)6.0 QTSApplies to GLC30, GLC35, GLC45
FuelNo. 2-D as specified in ASTM D 975ASTM D 975Diesel-only guidance; No. 1-D or a blend of 1-D and 2-D may be used if climatic conditions warrant

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

8
Voltage Sensing Calibration - Span adjustment

⚠ Ensure generator output voltage is set within nominal limits

Tools: external AC voltmeter

  1. Energize generator supply voltage to the controller at nominal level.
  2. Scroll to desired generator supply voltage phase with SPAN function selected.
  3. Connect external AC voltmeter to the controller terminals for those phases.
  4. Adjust correction factor number to obtain identical voltage reading.
  5. Press ENTER to accept the correction factor number; record it.
Voltage Sensing Calibration - Zero adjustment

Tools: external AC voltmeter

  1. Connect external AC voltmeter to controller terminals for the phases to be calibrated.
  2. With generator stopped, confirm there is zero volts on the phases.
  3. Scroll to desired generator supply voltage phase with ZERO function selected.
  4. Use INCREMENT or DECREMENT to adjust correction factor to obtain zero volts.
  5. Press ENTER to accept the correction factor number; record it.
Ventilation Test diagnostic

⚠ Opening doors/windows can upset air-flow pattern and reduce cooling

Tools: two thermometers

  1. Place thermometer close to engine blower housing cool air intake.
  2. Place second thermometer outside the building in open air.
  3. Run engine under maximum load for at least one hour.
  4. Temperature difference between the two must not exceed 15 degrees F.
  5. Repeat test with doors/windows closed, then with them open.
  6. Do not run generator under conditions exceeding 15 F difference.
Battery Installation installation

⚠ Never jump start a battery

⚠ Do not cause flame or spark in battery area

⚠ Remove watches, rings, necklaces and all metal objects

Tools: washers, lock washer, nut

  1. Open access doors and locate battery tray.
  2. Place the correct battery (BCI Group 31) on the tray.
  3. Install Battery Hold Down Bar and Rods through tray holes; secure with washers and nut.
  4. Repeat hold down rod installation for the other rod.
  5. Connect positive lead to positive (+) battery terminal.
  6. Connect negative lead to negative (-) battery terminal.
  7. Connect charging source to the battery terminals.
  8. Disconnect battery ground terminal before working near battery.
LP Gas Connections (vapor withdrawal only) installation

⚠ LPG and natural gas fuels are flammable and can cause fire, explosion, injury or death

Tools: soap solution for leak check

  1. Connect proper size gas pipe at the input to the LP Gas regulator.
  2. Use correct pipe size per Table 3-6 for flow rate and pipe length.
  3. Ensure all connections are sealed and no leaks are present.
  4. Verify fuel supply pressure is 11 inches water column (6 oz pressure).
Natural Gas Connections installation

⚠ Only a professional experienced technician should install a fuel supply system

Tools: soap solution for leak check

  1. Connect proper size gas pipe at Inlet Connection to the Fuel Lock Solenoid.
  2. Use correct pipe size per Table 3-5 for flow rate and pipe length.
  3. Ensure all connections are sealed and no leaks are present.
  4. Verify fuel supply pressure is 11 inches water column (6 oz pressure).
  5. Comply with all building codes.
Post Installation Checks installation

⚠ Stop engine immediately if a fuel, coolant or oil leak is detected

Tools: voltmeter

  1. Verify transfer switch is in Utility Power mode; no power present at generator.
  2. Verify engine starting battery is disconnected.
  3. Verify generator is securely mounted and anchored to its cement pad.
  4. Verify generator and transfer switch are properly grounded.
  5. Verify engine oil and coolant levels are full.
  6. Verify fuel source is ON with correct pressure and flow rate.
  7. Connect battery, start generator and check for fuel/coolant/oil leaks.
Magnetic Pickup Replacement repair

⚠ Do not insert a screwdriver into the magnetic pickup hole - threads can be damaged

⚠ Do not use the generator cooling fan to rotate the engine/generator

Tools: socket on engine crank pulley, jam nut wrench

  1. Disconnect battery from generator set; remove old magnetic pickup sensor.
  2. Center a flywheel gear ring tooth in the pickup hole; rotate engine via crank pulley.
  3. Measure distance d from tooth top to outside of flywheel housing.
  4. Set jam nut slightly beyond d (d+) so pickup fully threads into housing.
  5. Thread magnetic pickup into flywheel housing until it bottoms on tooth.
  6. Back pickup out 1/2 turn and tighten jam nut to flywheel housing.
  7. Verify proper operation (1.3 VAC while cranking).
  8. Apply a drop of wicking fastener adhesive to the locking nut.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
208/1203// WYE12/311GLC30 Nat Gas, FLA 104, 115% FLA 120, breaker 125, C.T. 125:5, wire (1) #4
240/1201Series4/06GLC30 Nat Gas, L-L 240 VAC, L-N 120 VAC, FLA 125, 115% FLA 144, breaker 150, C.T. 150:5, wire (1) #4
240/1203Series/Delta12/311GLC30 Nat Gas, FLA 90, 115% FLA 104, breaker 110, C.T. 125:5, wire (1) #6
240/1393// WYE12/311GLC30 Nat Gas, FLA 90, 115% FLA 104, breaker 110, C.T. 125:5, wire (1) #6
380/2203Series Wye12/311GLC30 Nat Gas, FLA 57, 115% FLA 66, breaker 70, C.T. 75:5, wire (1) #8
480/2773Series WYE12/311GLC125 Nat Gas, FLA 195, 115% FLA 225, breaker 225, C.T. 250:5, wire (1) #1
480/2773Series Wye12/311GLC30 Nat Gas, FLA 45, 115% FLA 52, breaker 60, C.T. 60:5, wire (1) #8

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Baldor (Baldor Generators / Baldor Electric Company) GLC80?

The Baldor (Baldor Generators / Baldor Electric Company) GLC80 is rated 80 kW standby.

What air filter fits the Baldor (Baldor Generators / Baldor Electric Company) GLC80?

The Baldor (Baldor Generators / Baldor Electric Company) GLC80 uses air filter part number EA0015A21.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
This generator must not be used on or near any forest covered, brush covered, or grass covered land unless the engine’s exhaust system is equipped with a spark arrestor.The spark arrestor must be maintained in effective working order by the operator.
Never move a generator set that is running.Loads should be connected and position secure before starting the engine. Hazards are caused by moving a generator set that is running.
Be sure that you understand how to stop the engine quickly in case of an emergency situation.Become familiar with the controls and safety systems provided with this generator set.
Improper operation may cause violent motion of connected equipment.Be certain that unexpected movement will not cause injury to personnel or damage to equipment.
Never permit anyone to operate the generator without proper instructions.Be sure to keep a copy of this manual with the generator so that all users can be properly informed of its safe operation.
Do not put hands, feet, tools clothing or other objects near rotating parts such as drive shaft, pulley, belt etc.Rotating parts cause extremely dangerous situations because they can catch loose clothing or extremities and cause serious or fatal injury.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

27
Part #DescriptionQtySystem
CT0050A06CURRENT TRANSFORMERSensor eBay
EA0007A07MAG PICK-UP ASSY (GM engines)Sensor eBay
EA0015A21AIR CLEANER, ELEMENTAir filter eBay
GS0089A07GASKET, EXHAUST RINGGasket eBay
CK0070A44BREAKER, W/SHUNTService part / kit eBay
DI0176A00DIODE, 1N5408Service part / kit eBay
DI0179A00LAMP FIXTURE, DASHService part / kit eBay
DI0180A00LAMP, #67, 12 VOLTService part / kit eBay
EA0010A02CHARGER, BATTERY, 12V, 6 AMPService part / kit eBay
EA0044A05VALVE, FUMOTO FG-2NService part / kit eBay
EA0044A07VALVE, FUMOTO F-107-NService part / kit eBay
EA0049A02HEATER, BLOCK 120VService part / kit eBay
FU0066A03FUSE, AGC 2Service part / kit eBay
FU0066A07FUSE, BUSS, AGC 15Service part / kit eBay
FU0070A00FUSE, 10AService part / kit eBay
FU0071A00FUSE, 1AService part / kit eBay
HW2412A00KNOB, RHEOSTATService part / kit eBay
RE5031A01RELAYService part / kit eBay
SE0052A04SOLENOID, FUEL, 12VDCService part / kit eBay
SE0057A01SOLENOID, ENGINE 12VService part / kit eBay
SP9079SWITCH, TOGGLEService part / kit eBay
SP9094SWITCH, DPDTService part / kit eBay
SP9095SWITCH, E, 3PHService part / kit eBay
SP9134RHEOSTAT, 1K, 2W ENCLOSEDService part / kit eBay
SW00925A00SWITCH, E-STOPService part / kit eBay
TA0000A07TANK, COOLANT RECOVERYService part / kit eBay
TA0002A07CAP, COOLANT RECOVERY TANKService part / kit eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Service manual — Baldor GLC30,35,45,50,60,80,100,125 (Baldor (Baldor Generators / Baldor Electric Company))