Baldor — Ventilation Test
Testing & diagnosis · Genset room ventilation
From a Baldor service manual covering: GLC100, GLC125, GLC30, GLC35, GLC45, GLC50, GLC60, GLC80, MN2408. Check it applies to your exact model before use.
Applies to: Baldor (Baldor Generators / Baldor Electric Company) GLC100, Baldor (Baldor Generators / Baldor Electric Company) GLC80
Before you start
- Opening doors/windows can upset air-flow pattern and reduce cooling
Procedure
- Place thermometer close to engine blower housing cool air intake.
- Place second thermometer outside the building in open air.
- Run engine under maximum load for at least one hour.
- Temperature difference between the two must not exceed 15 degrees F.
- Repeat test with doors/windows closed, then with them open.
- Do not run generator under conditions exceeding 15 F difference.
Tools required
- two thermometers Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- maximum 15 degrees F difference
Full service-parts list: Baldor (Baldor Generators / Baldor Electric Company) GLC100 →, Baldor (Baldor Generators / Baldor Electric Company) GLC80 →