Home›Repair guides›Baldor›Ventilation Test

Baldor — Ventilation Test

Testing & diagnosis · Genset room ventilation

From a Baldor service manual covering: GLC100, GLC125, GLC30, GLC35, GLC45, GLC50, GLC60, GLC80, MN2408. Check it applies to your exact model before use.

Applies to: Baldor (Baldor Generators / Baldor Electric Company) GLC100, Baldor (Baldor Generators / Baldor Electric Company) GLC80

Before you start

  • Opening doors/windows can upset air-flow pattern and reduce cooling

Procedure

  1. Place thermometer close to engine blower housing cool air intake.
  2. Place second thermometer outside the building in open air.
  3. Run engine under maximum load for at least one hour.
  4. Temperature difference between the two must not exceed 15 degrees F.
  5. Repeat test with doors/windows closed, then with them open.
  6. Do not run generator under conditions exceeding 15 F difference.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • maximum 15 degrees F difference

Full service-parts list: Baldor (Baldor Generators / Baldor Electric Company) GLC100 →, Baldor (Baldor Generators / Baldor Electric Company) GLC80 →

Source: Baldor service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Baldor repair guides →