Baldor — LP Gas Connections (vapor withdrawal only)
Installation · Gaseous fuel supply - LPG
From a Baldor service manual covering: GLC100, GLC125, GLC30, GLC35, GLC45, GLC50, GLC60, GLC80, MN2408. Check it applies to your exact model before use.
Applies to: Baldor (Baldor Generators / Baldor Electric Company) GLC100, Baldor (Baldor Generators / Baldor Electric Company) GLC80
Before you start
- LPG and natural gas fuels are flammable and can cause fire, explosion, injury or death
Procedure
- Connect proper size gas pipe at the input to the LP Gas regulator.
- Use correct pipe size per Table 3-6 for flow rate and pipe length.
- Ensure all connections are sealed and no leaks are present.
- Verify fuel supply pressure is 11 inches water column (6 oz pressure).
Tools required
- soap solution for leak check Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 11 inches water column (6 oz pressure)
Full service-parts list: Baldor (Baldor Generators / Baldor Electric Company) GLC100 →, Baldor (Baldor Generators / Baldor Electric Company) GLC80 →
Source: Baldor service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.