Baldor — Voltage Sensing Calibration - Zero

Adjustments · MEC 2 controller AC voltage sensing

From a Baldor service manual covering: GLC100, GLC125, GLC30, GLC35, GLC45, GLC50, GLC60, GLC80, MN2408. Check it applies to your exact model before use.

Applies to: Baldor (Baldor Generators / Baldor Electric Company) GLC100, Baldor (Baldor Generators / Baldor Electric Company) GLC80

Procedure

  1. Connect external AC voltmeter to controller terminals for the phases to be calibrated.
  2. With generator stopped, confirm there is zero volts on the phases.
  3. Scroll to desired generator supply voltage phase with ZERO function selected.
  4. Use INCREMENT or DECREMENT to adjust correction factor to obtain zero volts.
  5. Press ENTER to accept the correction factor number; record it.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Zero calibration must be completed before Span calibration
  • Factory default correction factor 127

Full service-parts list: Baldor (Baldor Generators / Baldor Electric Company) GLC100 →, Baldor (Baldor Generators / Baldor Electric Company) GLC80 →

Source: Baldor service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.