| Clearance | Bearing bracket step minimum | less than 0.0762 | mm | |
| Other | Belt tension deflection | 0.50 to 0.75 | inch | 110 N (25 lb) force midway between pulleys |
| Other | Belt tension deflection | 13 to 19 | mm | 110 N (25 lb) force midway between pulleys |
| Other | Coolant level below filler pipe bottom | 13 | mm | |
| Other | Cooling system fill rate (maximum) | 19 | L per minute | to avoid air locks |
| Other | Engine valve rotator operation | should turn slightly when valves close | | |
| Other | Generator excitation PMG short circuit capability | 3 X In for 10 seconds | | |
| Other | High idle speed for droop governors | approximately 2% to 5% | above full load speed | governors equipped with droop |
| Other | Speed droop values commonly used | 3% and 0% | % | |
| Other | Vibration damper inspection | dented, cracked, leaking, bent or discolored damper must be replaced | | |
| Other | Voltage droop for 0.8 power factor load | approximately 5 | % | loads with a power factor of 0.8 |
| Pressure | Coolant system pressure test - use 9S-8140 Pressurizing Pump | 9S-8140 | | |
| Pressure | Engine oil pressure at low idle | 186 to 344 | kPa | low idle speed |
| Pressure | Fuel pressure (below which engine will not operate properly) | 160 | kPa | |
| Pressure | Maximum air pressure for cleaning | 205 | kPa | deadheaded nozzle with chip guarding |
| Pressure | Maximum water pressure for cleaning | 275 | kPa | |
| Pressure | Minimum recommended oil pressure | 103 | kPa | 600 rpm |
| Pressure | Minimum recommended oil pressure | 15 | psi | 600 rpm |
| Pressure | Normal operating engine oil pressure | 275 to 600 | kPa | engine running at rated engine speed, SAE 10W30 oil, operating oil temperature 104 C (219.2 F), normal engine water temperature |
| Pressure | Primary filter/water separator change pressure | 50 to 70 | kPa | 15 to 20 inches Hg |
| Pressure | Typical engine oil pressure at rated rpm with SAE10W30 (turbocharged) | 275 to 606 | kPa | rated rpm |
| Pressure | Typical engine oil pressure at rated rpm with SAE10W30 (turbocharged) | 40 to 88 | psi | rated rpm |
| Resistance | Exciter Armature (Rotor) (L2) resistance | less than 0.1 | ohm | room temperature |
| Resistance | Exciter Field (Stator) (L1) resistance | 3.0 to 6.0 | ohms | room temperature |
| Resistance | Insulation resistance minimum (contaminated generator) | 1 | megohm | |
| Resistance | Main Armature (Stator) (L4) resistance | less than 0.1 | ohm | room temperature |
| Resistance | Main Field (Rotor) (L3) resistance | 0.75 to 2.0 | ohms | room temperature |
| Resistance | Pilot Exciter Armature (L5) resistance | less than 0.1 | ohm | room temperature |
| Resistance | Varistor (CR7) resistance | minimum 15000 | ohms | |
| Speed | Actual RPM of overspeed (1500 full load rpm) | 1770 | rpm | multiply full load RPM by 1.18 |
| Speed | Actual RPM of overspeed (1800 full load rpm) | 2124 | rpm | multiply full load RPM by 1.18 |
| Speed | Frequency vs RPM - four-pole generator | divide the RPM by 30 | Hz | |
| Speed | Frequency vs RPM - six pole generator | divide the RPM by 20 | Hz | |
| Speed | Generator set functional test minimum phase voltage | 85 | VAC | half rated speed |
| Speed | Low idle (50 Hz units) | 80 | percent of full load speed | |
| Speed | Low idle (50 Hz units) | approximately 80 | % of full load speed | 50 Hz units |
| Speed | Low idle (60 Hz units) | 66 | percent of full load speed | |
| Speed | Low idle (60 Hz units) | approximately 66 | % of full load speed | 60 Hz units |
| Speed | Magnetic pickup crank termination | 400 | rpm | starter pinion disengagement |
| Speed | Overspeed switch setpoint | 118 | percent of rated engine speed | |
| Speed | Test RPM for overspeed (1500 full load rpm) | 1328 | rpm | multiply full load RPM by 0.885 |
| Speed | Test RPM for overspeed (1800 full load rpm) | 1593 | rpm | multiply full load RPM by 0.885 |
| Temperature | Air cleaner oven drying maximum | 82 | °C | |
| Temperature | Air cleaner wash water maximum | 60 | °C | soak six hours |
| Temperature | Bearing reinstall heating | 107 | C | heat for ten minutes |
| Temperature | Engine water temperature operating range | 88 to 100 | C | 88 C (190.4 F) to 100 C (212.0 F) |
| Temperature | Fuel heater maximum fuel supply temperature | 37 | °C | |
| Temperature | Generator bearing shutdown temperature | 50 | °C above ambient | |
| Temperature | Generator drying winding temperature ramp rate | 10 | °C per hour | up to 85 C (185 F) |
| Temperature | Generator drying winding temperature rise rate | 10 | C per hour up to 85 C (185 F) | do not apply heat too rapidly |
| Temperature | Generator oven drying | 65 | °C | 4 hours forced air |
| Temperature | Hub reinstall heating | 400 | C | heat for three hours |
| Temperature | Jacket water coolant temperature (maximum allowable) | 104 | °C | |
| Temperature | Jacket water coolant temperature (typical) | 87 to 98 | °C | |
| Temperature | Jacket water heater maintained coolant temperature | 32 | °C | ambient 0 C (32 F) |
| Temperature | Oven drying method temperature | 65 | C | forced air drying oven for four hours |
| Torque | Air cleaner service indicator | 18 | lb in | |
| Torque | Air cleaner service indicator | 2 | N·m | |
| Torque | Fuel line nuts | 30 ± 5 | lb ft | |
| Torque | Fuel line nuts | 40 ± 7 | N·m | |