Caterpillar — Generator - Dry (Controlled Current Method)

Maintenance

From a Caterpillar owner's manual covering: 3306B, 3406, 3406E, 3412C, 3412C Generator Set, 3500 Series. Check it applies to your exact model before use.

Applies to: Caterpillar 3306B, Caterpillar 3406, Caterpillar 3406E, Caterpillar 3412C, Caterpillar 3412C engine

Before you start

  • Personal injury or death can result from improper troubleshooting and repair procedures.

Procedure

  1. Make an external power source.
  2. Disconnect F1+ and F2- from voltage regulator; disconnect generator load.
  3. Connect rheostat at maximum resistance and external power source to F1+ and F2-.
  4. Start generator set and run at IDLE speed.
  5. Monitor phase current; gradually increase RPM until rated phase current or full speed.
  6. Slowly turn rheostat until rated phase current is reached.
  7. On an hourly basis stop and check insulation resistance.
  8. Repeat until insulation resistance is acceptable.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Raise winding temperature gradually at 10 C (50 F) per hour up to 85 C (185 F)

Full service-parts list: Caterpillar 3406 →, Caterpillar 3406E →, Caterpillar 3412C →, Caterpillar 3412C engine →

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.