| 3 | 12 Lead Delta | T6 and T9 tied together and grounded = neutral | T2 and T10 connection is the high phase |
| 3 | 12 Lead Wye - High Voltage | T10, T11, T12 tied together = neutral | Typical high voltage connection (Series Wye, 60 Hz) |
| 3 | 12 Lead Wye - Low Voltage | T10, T11, T12 tied together = neutral | Typical low voltage connection (Parallel Wye, 60 Hz) |
| 3 | 6 Lead Delta | | Typical Delta Configuration (60 Hz, 6 Lead) |
| 3 | 6 Lead Wye | T4, T5, T6 tied together = neutral | Terminals T4, T5 and T6 become a neutral connection when tied together |
| 3 | Delta - 6 lead | 6 | Winding pitch must be two-thirds or the generator must be derated. |
| 3 | Wye - 10 lead (high voltage) | 10 | Illustration 13. Only used on 3306B generator sets and 3406C generator sets. Terminal T0 is the neutral lead. |
| 3 | Wye - 10 lead (low voltage) | 10 | Only used on 3306B and 3406C generator sets. Terminal T0 is the neutral lead. |
| 3 | Wye - 12 lead (high voltage) | 12 | Terminals T10, T11, and T12 become neutral connections when tied together. |
| 3 | Wye - 12 lead (low voltage) | 12 | Terminals T10, T11, and T12 become neutral connections when tied together. |
| 3 | Wye - 4 lead | 4 | Only used on 3306B generator sets and 3406C generator sets. Terminal T0 is the neutral lead. |
| 3 | Wye - 6 lead | 6 | Terminals T4, T5, and T6 become neutral connections when the terminals are tied together. |
| 190-220 (50 Hz), 190-240 (60 Hz) | 3 | Wiring Code A | 12 wire | Winding 6; 5000/6100/7000 12 wire factory connection |
| 240 | 3 | Delta | | Produces 208 V high phase to neutral and 240 V low phase to neutral |
| 240 | 3 | Delta - 12 lead | 12 | Terminals T6 and T9 become the neutral connections when tied together and grounded. T2 and T10 connection is the high phase. 240 V, 60 Hz, three-phase: 208 Volts between the high phase and neutral; 240 Volts between either of the low phases and neutral. |
| 380-415 (50 Hz), 380-480 (60 Hz) | 3 | Wiring Code D | 12 wire | Winding 6; 5000 12 wire factory connection |
| 480 | 3 | Parallel Wye | 12 lead | Typical high voltage connection |
| 480 | 3 | Series Wye | 12 lead | Typical high voltage connection |
| 480 | 3 | Wye | 6 lead | Typical Wye Configuration |
| 58% of three-phase connected voltage | 1 | Wye | any phase lead and neutral | Single-phase from three-phase generator |
| 600 | 3 | Wiring Code D | 12 wire | Winding 9; R448 voltage sensing and transformer |
| Four Lead Wye | Three-phase | T1/T2/T3 to loads, T0 to neutral | T1, T2, T3, T0 | Regulator leads 22, 24, 20 from T1, T2, T3 respectively |
| Six Lead Delta | Three-phase | T1/T6, T2/T4, T3/T5 series loop connections | T1, T2, T3, T4, T5, T6 | Delta configuration |
| Six Lead Wye | Three-phase | T1/T2/T3 to loads, T4/T5/T6 to neutral | T1, T2, T3, T4, T5, T6 | Regulator sensing from T1, T2, T3 |
| Ten Lead Wye High Voltage | Three-phase | T1/T2/T3 to loads with T4/T7, T5/T8, T6/T9 series connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T0 | High voltage configuration |
| Ten Lead Wye Low Voltage | Three-phase | T1/T7, T2/T8, T3/T9 parallel connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T0 | Low voltage configuration |
| Twelve Lead Delta | Three-phase | T1/T12, T2/T10, T3/T11 series loops with jumpers | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Delta configuration with 12 leads |
| Twelve Lead Wye High Voltage | Three-phase | T1/T2/T3 to loads with series connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | High voltage configuration with 12 leads |
| Twelve Lead Wye Low Voltage | Three-phase | T1/T7, T2/T8, T3/T9 parallel connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Low voltage configuration with 12 leads |