HomeControllersDSE7310 MKII

DSE7310 MKII Controller

The DSE7310 MKII is a generator-set controller. It is used on generator sets from Briggs & Stratton, Generac, Genpowerusa and Winco, including the MDG100DF4, MDG75DF4, MMG45IF4 and MMG55DF4.

32
Generator sets
4
Brands
15–200 kW
Power range
4
Fuel types

Specifications

CommunicationsRS485
ProtectionsProtections disabled function is activated. Operation depends upon the following configuration., Never: The protections are not disabled, Always: Protections are always overridden by the DSE controller., On Input: Protections are disabled whenever a configurable input set to Protections Disabled is activated, If Disable All Protections is set to On Input, this selection allows configuration of an
Operating temperature-22 ºF to +122 ºF (-30 ºC to +50 ºC)
Dimensions245 mm X 184 mm X 51 mm (9.6” X 7.2” X 2.0”)
Relay outputs[2, 3, 5, 6, 8, 10, 11, 12, 14]

Troubleshooting

85

Fault codes

CodeMeaningCause
057-243Generator Under Volts gives a warning alarm in the event of the generator output falling below the configured Under Volts Pre-Alarm Trip value for longer than the Activation Delay.
057-243Generator Over Volts gives a warning alarm in the event of the generator output voltage rising above the configured Over Volts Pre-Alarm Trip value for longer than the Activation Delay.
057-243Generator Under Frequency gives a warning alarm in the event of the generator output frequency falling below the configured Under Frequency Pre-Alarm Trip value for longer than the Activation Delay.
057-243Under Speed Alarm
057-243Over Speed Pre-Alarm
057-243Over Speed Alarm
057-243Run Away Shutdown alarm is immediately triggered.
IDMT ALARMIf the Over Current IDMT Alarm is enabled, the controller begins following the IDMT ‘curve’ when the current on any phase passes the Trip setting. If the Trip is surpassed for an excess amount of time, the IDMT Alarm triggers (Shutdown or Electrical Trip as selected in Action). The larger the over circuit fault, the faster the trip.Generator current exceeds the trip level and remains above it for a duration that surpasses the set threshold.
IDMT ALARMIf the Over Current IDMT Alarm is enabled, the controller begins following the IDMT 'curve' when the current on any phase passes the Trip setting. If the Trip is surpassed for an excess amount of time, the IDMT Alarm triggers (Shutdown or Electrical Trip as selected in Action). The larger the over circuit fault, the faster the trip.Generator current exceeds the IDMT trip setting and remains above it for a duration that triggers the alarm.
IMMEDIATE WARNINGIf the Immediate Warning is enabled, the controller generates a warning alarm as soon as the Trip level is reached. The alarm automatically resets once the generator loading current falls below the Trip level (unless All Warnings are latched is enabled).Generator current exceeds the trip level.
Mains Earth FaultGenerator earth fault current rose above the Mains Earth Fault Trip Level for the duration of the IDMT function.
Mains Over CurrentMains output current rose above the Mains Over Current Trip level.
Mains Phase Seq WrongPhase rotation of mains was different to configured Mains Phase Rotation Alarm setting.
Over Speed AlarmShutdown alarm in the event of the engine speed rising above the configured Over Speed Alarm Trip value for longer than the Activation Delay.
Over Speed Pre-AlarmWarning alarm in the event of the engine speed rising above the configured Over Speed Pre-Alarm Trip value for longer than the Activation Delay. The Warning is automatically reset when the engine speed falls below the configured Return level.
Run AwayIn the event of the generator output frequency rising above the configured Trip value, the Run Away Shutdown alarm is immediately triggered. This is used to protect against engine damage due to uncontrolled speed increase.Generator output frequency exceeds the configured trip value.
Run AwayImmediate Shutdown alarm triggered when the engine speed rises above the configured Trip value.
Short Circuit IDMT AlarmGenerator output current rose above the Short Circuit Trip for the duration of the IDMT function.
Under Speed AlarmShutdown or Warning depending on configuration: The engine speed falling below the configured Under Speed Alarm Trip value for longer than the Activation Delay.

Symptoms & remedies

SymptomCauseRemedy
The module detected that an analogue input value of a DSE2131 had risen above the Flexible Sensor High Pre-Alarm Trip level.
The module detected that an analogue input value of a DSE2131 had fallen below the Flexible Sensor Low Pre-Alarm Trip level.
Generator Under Voltage Pre-Alarm
Generator Over Voltage Pre-Alarm
Generator Under Frequency Pre-Alarm
Shutdown: The engine is removed from load and is immediately stopped.Loss of sensing signal during engine running or not present during cranking when Multiple Engage Attempts is enabled.
Warning: The engine continues to run, however a warning alarm is raised. Always Latched: The engine continues to run, however a latched warning alarm is raised even if the magnetic pickup signal returns to normal.Magnetic Pickup Open Circuit
Water in Fuel
Fuel Tank Bund Level High
Generator Over Frequency gives a Shutdown alarm in the event of the generator output rising above the configured Over Frequency Alarm Trip value for longer than the Activation Delay.Generator output frequency exceeds the configured trip value for an extended period after the activation delay.Adjust the Over Frequency Alarm Trip value to suit user requirements.
Overcurrent alarm combines a simple warning trip level combined with a fully functioning IDMT curve for thermal protection.
Coolant Temperature Low Warning
Coolant Temperature High Pre Alarm
Coolant Temperature High Electrical Trip
Coolant Temperature High Shutdown
Engine Under Speed Warning
Engine Over Speed Warning
Battery Under Voltage Warning
Battery Over Voltage Warning
Charge Alternator Failure Warning
Generator Under Voltage Pre Alarm
Generator Over Voltage Pre Alarm
Generator Under Frequency Pre Alarm
Generator Over Frequency Shutdown
Generator Under Frequency Delay
Generator Over Frequency Overshoot 0 %
Generator Over Frequency Overshoot
Generator CT Primary Current
Generator Secondary Current
Generator CT Primary Earth Current
Full Load Rating
Delayed Over Current
Generator Earth Fault Trip
kW Overload Trip
Mains Under Voltage Trip
Mains Over Voltage Trip
Mains Under Frequency Trip
Mains Over Frequency Trip
The overcurrent alarm combines a simple warning trip level combined with a fully functioning IDMT curve for thermal protection.
2130 ID 0 to 3 Analogue Input E to H HighThe module detected that an analogue input value of a DSE2130 had risen above the Flexible Sensor High Pre-Alarm Trip level.
2130 ID 0 to 3 Analogue Input E to H LowThe module detected that an analogue input value of a DSE2130 had fallen below the Flexible Sensor Low Pre-Alarm Trip level.
2130 ID 0 to 3 Digital Input A to HThe module detected that a digital input configured to create a fault condition on a DSE2130 expansion module became active and the appropriate LCD message displayed.
open circuitThe module detected that the engine oil pressure had fallen below the Low Oil Pressure Shutdown Trip level after the Safety On Delay timer had expired.
low oil pressure switch activatedThe module detected that the low oil pressure switch had activated after the Safety On Delay timer had expired.
run away trip - frequencyThe module detected that the generator output frequency had risen above the Run Away Trip level.
run away trip - speedThe module detected that the engine speed had risen above the Run Away Trip level.
positive var alarmThe module detected that the generator output kvar had risen above the Positive var Alarm Trip for the configured delay timer.
communication link faultThe module detected that another module on the Dual Mutual Standby communication link
SCR Inducement faultThe module received a fault condition from the engine ECU alerting about the SCR Inducement.
water in fuel detectedThe module received a fault condition from the engine ECU alerting that water in the fuel had been detected.
Inlet Temperature AlarmEngine ECU measurement of inlet temperature rose above the Inlet Temperature Alarm Pre-Alarm Trip level.
kW Overload ProtectionGenerator output kW rose above the Overload Protection Trip for the configured delay timer.
Loss of Magnetic PickupMagnetic pick-up was not producing a pulse output after meeting Crank Disconnect criteria.
Low Coolant Temperature WarningEngine coolant temperature fell below the Low Coolant Temperature Pre-Alarm Trip level.
Low Load AlarmLoad fell below the Low Load Alarm Trip level.
Maintenance DueConfigured maintenance alarm due as its configured maintenance interval expired.
Dual Mutual Standby Communication Link FailureCommunication link failure between modules.
Negative kvar Pre-Alarm TripGenerator output kvar fell below the Negative var Pre-Alarm Trip for the configured delay timer.
Negative Phase Sequence TripCurrent imbalance across generator phases greater than the Negative Phase Sequence Trip Level percentage setting.
Oil Pressure LowEngine oil pressure fell below the Low Oil Pressure Pre-Alarm Trip level after Safety On Delay timer expired.
Positive kvar Pre-Alarm TripGenerator output kvar rose above the Positive var Pre-Alarm Trip for the configured delay timer.
Protections DisabledInput configured for Protections Disable became active.
SCR InducementFault condition from engine ECU about SCR Inducement.
Oil Pressure Low Shutdown0.00 bar 0 psi 0 kPa
Oil Pressure Low Pre Alarm0.00 bar 0 psi 0 kPa
Warning, electrical trip, and shutdown alarms

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Extracted directly from this controller's manual.

Generator sets using this controller

32

Used across brands: Briggs & Stratton, Generac, Genpowerusa, Winco

Also fitted to: Briggs & Stratton 080005, Briggs & Stratton 080006, Briggs & Stratton 080007, Briggs & Stratton 080008, Briggs & Stratton 080009, Briggs & Stratton 080010, Briggs & Stratton 080011, Briggs & Stratton 080012, Briggs & Stratton 080013, Briggs & Stratton 080014, Briggs & Stratton 080015, Briggs & Stratton 080016, Briggs & Stratton 080017, Briggs & Stratton 080018, Briggs & Stratton 080019, Briggs & Stratton 080026, Briggs & Stratton 080027, Briggs & Stratton 080028, Briggs & Stratton 080029, Genpowerusa GPR-P50-60T4F.

Troubleshooting

44

Fault codes

CodeMeaningCauseRemedy
1049 VSCFOverload RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Generator output is shorted or severely overloaded. Identify and clear the overload, and then restart.
1051 VSCFHigh Battery YELLOW LED illuminated in any state.Check the LEDs/Screen for alarms. Voltage supply to the AVR is high. If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact Independent Authorized Servicing Dealer.
1052 VSCFDC Overvoltage RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator was temporarily overloaded. 2) The output was temporarily shorted. Try to restart the unit.
1053 VSCFGate Fault RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. AVR is damaged. Contact Independent Authorized Servicing Dealer.
1055 VSCFPhase Error RED Unit shuts down during starting.Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact Independent Authorized Servicing Dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: •Verify stepper motor is moving and linkage is free. •Verify stepper motor is plugged in. •Verify gas pressure is within specified limits.
1056 VSCFUndervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The generator output voltage is too low. Probable causes are: 1) The load is too large. Remove load and attempt to restart unit. 2) Alternator or AVR damage. Contact Independent Authorized Servicing Dealer.
1057 VSCFOvervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator has been overloaded. Remove load and attempt to restart unit. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.
1058 VSCFDC Undervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The DPE winding supplies this voltage. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.
1059 VSCFField Loss RED Unit shuts down during starting.Check the LEDs/Screen for alarms. Unit detects no output voltage while starting. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.
1061 VSCFField Loss RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Unit detects loss of output voltage while running. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.
1065Overfrequency RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Probable causes are: 1) Overload. Remove load and attempt to restart unit. 2) RPM sensor has failed. Contact Independent Authorized Servicing Dealer. 3) Stepper motor problem. Contact Independent Authorized Servicing Dealer.
1066 VSCFSpeed mismatch RED Unit shuts down during Operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) Fuel problem (pressure loss). Check fuel supply and attempt to restart unit. 2) Large overload. Remove load and attempt to restart unit. 3) Throttle or engine problem. Contact Independent Authorized Servicing Dealer.
HIGH TEMPERATUREUnit shuts down during operation.Check ventilation around the intake, exhaust and rear of generator.Contact s Independent Authorized Servicing Dealer if no obstruction is found.
RPM SENSE LOSSUnit was running and shuts down, attempts to restart.Check the LEDs/Screen for alarms.Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact Independent Authorized Servicing Dealer to investigate possible fuel issue.

Symptoms & remedies

SymptomCauseRemedy
ATS will not re-transfer to normal powerProper power line not available at line terminals in ATS panel Defective ATS control board. See ATS manual
ATS will not transfer to Emergency Supply (generator)No AC generator output Defective ATS control board. See ATS manual Circuit breaker open or defective
Emergency Stop indicator LED illuminates when Emergency Stop switch is active (pushed in).Resolve by deactivating (pulling out) Emergency Stop switch.
Emergency Stop indicator LED.Resolve by deactivating (pulling out) Emergency Stop switch.
Engine cranks but will not startImproper fuel delivery to the unit Fuel supply shut off Fuel tank empty Air in the fuel system Engine fuel solenoid has not opened Defective fuel pump Defective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid
Engine cranks but will not start.1) Out of fuel. 2) Defective fuel solenoid (FS). 3) Defective spark plug(s). 4) Valve clearance needs adjustment.1) Replenish fuel / Turn on fuel valve. 2) * 3) Clean, check gap, or replace plug(s). 4) Adjust valve clearance.
Engine starts hard and runs rough.1) Air cleaner plugged or damaged. 2) Defective spark plug(s). 3) Fuel regulator not set. 4) Fuel pressure incorrect. 5) Fuel selector in wrong position.1) Check / replace air cleaner. 2) Clean, check gap, or replace plug(s). 3) Set fuel regulator. 4) Confirm fuel pressure to regulator is 10–12 in. water column (19–22 mm mercury) for LP, and 3.5–7 in. water column (7–13 mm mercury) for natural gas. 5) Move selector to correct position.
Engine starts, then stops and alarm light comes onEngine oil pressure is low Engine has high water temperature Engine has overspeed Engine has gone into overcrank
Engine will not crank.1) Fuse blown. 2) Loose, corroded or defective battery cables. 3) Defective starter contact. 4) Defective starter motor. 5) Dead battery.1) Correct short circuit condition by replacing 7.5 Amp fuse. 2) Tighten, clean or replace as necessary.* 3) Tighten, clean or replace as necessary.* 4) Tighten, clean or replace as necessary.* 5) Charge or replace battery.
Engine won’t crankLow/dead battery Blown DC fuses Defective DSE 7310 MKII Defective key switch Loose or dirty battery terminals Defective starter Defective start solenoid
Generator does not pull full power.Current calibration incorrect. Contact Independent Authorized Servicing Dealer.
Generator is set to OFF, but the engine continues to run.1) Control board wired incorrectly. 2) Defective control board.1) Repair wiring or replace control board.* 2) Replace control board.
Generator stalls when large load is supplied.Total load is too big for the generator. Loads must be less than 10 kW or 2 hp when operating under 3600 rpm.Contact installing dealer to correct installation.
High Coolant Temperature Shutdown1. Check coolant level in the overflow jug. 2. Restart engine and read the coolant temperature to verify a high coolant temperature shutdown. Stop engine immediately if the coolant temperature is 230°F (110°C) or more. 3. Allow engine to cool. Add coolant to the overflow jug if it is low and check the level of coolant in the radiator. To access the radiator cap, remove the access panel from the top of the enclosure.
Low Coolant Level Shutdown1. Allow engine to cool. 2. Check coolant level in the radiator. To access the radiator cap, remove the access panel from the top of the enclosure directly above the radiator. Add coolant until it is 3/4 in. (2 cm) below the filler neck. Secure the radiator cap back into its original position. 3. Inspect coolant hoses, engine block and water pump for visible leaks. 4. Check engine oil to verify no coolant has mixed with it (oil will appear milky if coolant is present). For additional information, see the engine operator’s manual.
Low Fuel Level Shutdown1. Check fuel level on the Liquid Crystal Display (LCD) window. Verify the unit is sitting level to ensure an accurate reading. 2. Check for leaks in fuel tank. The fuel tank should not run dry under normal circumstances. The engine controller will shut the engine down when there is five percent of fuel remaining in the tank. 3. If fuel level is good and no leaks are found, check the fuel level sender and the connecting wiring for damage. To check for continuity between the sender and the engine controller, remove the appropriate bolts from the control panel to access the inside of the control box. See the appropriate DC wiring diagram Wiring Diagrams for the proper path between the engine controller and the fuel level sender.
Low Load indicator LED illuminates when genset has operated at less than 30% capacity for more than 15 minutes.Resolve by increasing electrical load. If unable to operate genset at more than 30% load, use a smaller generator.
Low Load indicator LED. • Indicates genset has operated at less than 30% capacity for more than 15 minutes.Resolve by increasing electrical load. If unable to operate genset at more than 30% load, use a smaller generator.
Low Oil Pressure Shutdown1. Check engine oil level with the dipstick. The engine controller will shut the engine down when oil pressure is less than 20 psi (138 kPa). Add oil if required. 2. Visually inspect engine for oil leaks. 3. If oil level is good, restart the unit and verify the loss of oil pressure. Shut the engine down immediately if the oil pressure value does not read 5 psi (34 kPa) within five seconds. 4. Check oil pressure sender. To identify corrective action, see the troubleshooting section of the engine operator’s manual.
Lug Door Open indicator LED illuminates when lug-box door is open.Resolve by closing lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation.
Lug Door Open indicator LED.Resolve by closing lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation.
No AC output from generator.1) Main line circuit breaker is in the OFF (or OPEN) position. 2) Generator internal failure.1) Reset circuit breaker to ON (or CLOSED). 2) *
No output from AC generatorLoss of speed signal Loss of run signal Engine will not come up to speed after it starts Insufficient fuel volume getting to the unit 1. Too small of fuel line 2. Fuel racks not open properly Governor is defective AC short in generator components
Output voltage is low/high.Voltage calibration incorrect. Contact Independent Authorized Servicing Dealer.
Shutdown indicator LED illuminates when a shutdown alarm is present.Resolve by resolving shutdown condition.
Shutdown indicator LED.Resolve by resolving shutdown condition.
Unit consumes large amounts of oil.1) Oil tank is over filled with oil. 2) Engine breather defective. 3) Improper type or viscosity of oil. 4) Damaged gasket, seal or hose.1) Adjust oil to proper level. 2) * 3) See Engine Oil Recommendations. 4) Check for oil leaks.
Unit running in AUTO but no power in house.Check Generator Disconnect circuit breaker.Contact Independent Authorized Servicing Dealer if Generator Disconnect circuit breaker is in the ON position.
Unit will not crank when power failsDigital genset not in AUTO Transfer control switch not in AUTOMATIC position Incorrect wiring between ATS and genset Defective control relay in ATS Fuse(s) blown in the DSE 7310 MKII Defective DSE 7310 MKII Loose or dirty battery terminals Defective starter Defective start solenoid Low/dead battery
Unit will not start in AUTO with 2-wire start signal.See if screen says unit not activated.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.