Isuzu 4LE2XAGV01 Engine

The Isuzu 4LE2XAGV01 is a 2.2 L 4-cylinder turbocharged, aftercooled engine rated at 1800 rpm, producing up to 57 kW. It powers generator sets from Generac, including the MMG45IF4 and MMG50ITM. It holds 10.4 L (2.7 gal) of oil and 17 L (4.5 gal) of coolant.

Also known as: Isuzu 4LE2XAGV01

2.2 L
Displacement
4
Cylinders
1800 rpm
Rated speed
57 kW
Gross power

Service parts for the 4LE2XAGV01

The cheapest captured merchant offer per filter — see the full cross-reference below for every OEM/aftermarket option.

Air intake

1 required

Fuel system

1 required

Oil system

1 required

Prices captured from merchant listings; some links are affiliate links. Verify against your serial number before ordering.

Engine specifications

Oil capacity10.4 L
Coolant capacity17.0 L
Displacement2.2 L
Cylinders4
AspirationTurbocharged, aftercooled
Rated speed1800 rpm
Gross power57 kW

Generator sets powered by this engine

2

Common problems

15
  • Unit will not start in AUTO with 2-wire start signal.
    Cause: See if screen says unit not activated.
  • Unit was running and shuts down, attempts to restart. RPM SENSE LOSS
    Cause: Check the LEDs/Screen for alarms.
    Fix: Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact Independent Authorized Servicing Dealer to investigate possible fuel issue.
  • Unit shuts down during operation. HIGH TEMPERATURE
    Cause: Check ventilation around the intake, exhaust and rear of generator.
    Fix: Contact s Independent Authorized Servicing Dealer if no obstruction is found.
  • Unit running in AUTO but no power in house.
    Cause: Check Generator Disconnect circuit breaker.
    Fix: Contact Independent Authorized Servicing Dealer if Generator Disconnect circuit breaker is in the ON position.
  • Unit consumes large amounts of oil.
    Cause: 1) Oil tank is over filled with oil. 2) Engine breather defective. 3) Improper type or viscosity of oil. 4) Damaged gasket, seal or hose.
    Fix: 1) Adjust oil to proper level. 2) * 3) See Engine Oil Recommendations. 4) Check for oil leaks.
  • Undervoltage RED Unit shuts down during operation or starting. 1056 VSCF
    Fix: Check the LEDs/Screen for alarms. The generator output voltage is too low. Probable causes are: 1) The load is too large. Remove load and attempt to restart unit. 2) Alternator or AVR damage. Contact Independent Authorized Servicing Dealer.
  • Speed mismatch RED Unit shuts down during Operation or starting. 1066 VSCF
    Fix: Check the LEDs/Screen for alarms. Probable causes are: 1) Fuel problem (pressure loss). Check fuel supply and attempt to restart unit. 2) Large overload. Remove load and attempt to restart unit. 3) Throttle or engine problem. Contact Independent Authorized Servicing Dealer.
  • Shutdown indicator LED.
    Fix: Resolve by resolving shutdown condition.
  • Phase Error RED Unit shuts down during starting. 1055 VSCF
    Fix: Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact Independent Authorized Servicing Dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: •Verify stepper motor is moving and linkage is free. •Verify stepper motor is plugged in. •Verify gas pressure is within specified limits.
  • Overvoltage RED Unit shuts down during operation or starting. 1057 VSCF
    Fix: Check the LEDs/Screen for alarms. Probable causes are: 1) The generator has been overloaded. Remove load and attempt to restart unit. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.
  • Overload RED Unit shuts down during operation. 1049 VSCF
    Fix: Check the LEDs/Screen for alarms. Generator output is shorted or severely overloaded. Identify and clear the overload, and then restart.
  • Overfrequency RED Unit shuts down during operation. 1065
    Fix: Check the LEDs/Screen for alarms. Probable causes are: 1) Overload. Remove load and attempt to restart unit. 2) RPM sensor has failed. Contact Independent Authorized Servicing Dealer. 3) Stepper motor problem. Contact Independent Authorized Servicing Dealer.
  • Output voltage is low/high.
    Fix: Voltage calibration incorrect. Contact Independent Authorized Servicing Dealer.
  • No AC output from generator.
    Cause: 1) Main line circuit breaker is in the OFF (or OPEN) position. 2) Generator internal failure.
    Fix: 1) Reset circuit breaker to ON (or CLOSED). 2) *
  • Lug Door Open indicator LED.
    Fix: Resolve by closing lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation.

Compiled from service & troubleshooting documentation across every generator set that uses the Isuzu 4LE2XAGV01.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterReplace when the yellow center bar of the filter minder gauge reaches the red section (20 in. H2O)8972319000 Amazon eBay $95.00
Fuel filter8981527372 Amazon eBay $30.00 PartsGeek $14.97
Oil filterX13201002 Amazon eBay $23.95 PartsGeek $11.97
BatteryGroup 35/55, 12V (1 per unit), 720 CCA
BeltRemove and check for wear at the 500 hour/12 month service interval; inspect pulleys and bearings500 hr
Coolant17.0 L
Oil10.4 L

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

39
ItemActionHoursMonthsNotes
Engine Oil (Isuzu)Change50 hrFirst service — First 50 hours (break-in period)
Oil Filter Element ReplacementReplace500 hrFirst service — Isuzu, first 50 hours and every 500 hours
Engine Oil and Oil Filter (John Deere)Change500 hr12 moFirst service — First 100 hours break-in, factory fill; do not exceed 100 hours with break-in oil
Check Oil Vapor Recirculation System/Non-Return ValveCheck250 hrJohn Deere engine
Electromagnetic Pump FilterReplace250 hrReplacement or cleaning
Engine OilReplace250 hrFirst service — Change the oil after the first 50 hours
Engine Oil (Isuzu, MMG25IF4)Change250 hrEvery 250 hours, MMG25IF4 only
Fan Belt TensionCheck250 hrReplace if necessary
Fuel Filter ElementReplace250 hr
Oil Filter ElementReplace250 hr
Water Sedimenter ElementClean250 hr
Air Filter ElementReplace500 hr
Change Engine Oil and Replace Oil FilterChange500 hr12 moFirst service — John Deere; decrease to every 250 hours if not using John Deere Plus 50 II oil
Engine Oil (Isuzu, MMG45IF4)Change500 hrEvery 500 hours, MMG45IF4 only; every 250 hours instead if harsh environment or fuel quality questioned
Fan BeltReplace500 hr12 moBelt to be removed and checked for wear at 500 hour/12 month service interval
Fuel Filter Elements (Isuzu)Replace500 hrEvery 500 hours (every 250 hours if harsh environment/fuel quality questioned)
Fuel Filter Elements (John Deere)Replace500 hr12 mo
Generator Drive Plate TorqueCheck500 hrRefer to page 39
Replace Engine OilChange500 hrFirst service — Isuzu, every 500 hours (or every 250 hours if harsh environment/fuel quality questioned)
Replace Fuel Filter ElementsReplace500 hr12 moJohn Deere engine
Replace Oil Vapor Recirculation FilterReplace500 hr12 moJohn Deere engine
Service BatteryOther500 hr12 moJohn Deere engine
Water Sedimenter Element (Isuzu)Clean500 hrEvery 500 hours (every 250 hours if harsh environment/fuel quality questioned)
Air Cleaner Elements (John Deere)Replace2000 hr
Air Filter Element (Isuzu)Replace2000 hr
Alternator and Fan Belts (John Deere)Replace2000 hr
Check Generator Drive Plate TorqueCheck2000 hrIsuzu engine
Lubricate Leveling JacksLubricate2000 hrIsuzu engine
Replace Air Cleaner ElementsReplace2000 hrJohn Deere engine
Replace Air Filter ElementReplace2000 hrIsuzu engine
Replace Alternator and Fan BeltsReplace2000 hrJohn Deere engine
Replace Fan BeltReplace2000 hrIsuzu engine
Test ThermostatsTest2000 hrJohn Deere engine
Diesel Particulate Filter (DPF)Other3000 hrExpected service interval at least 3,000-4,500 hours depending on engine power/operating conditions; serviced by authorized provider only
Exhaust Filter (DPF) ServiceOther3000 hrExpected service interval at least 3,000-4,500 hours based on engine power/operating conditions; serviced by authorized provider only
Reset Maintenance Alarm IntervalsOther3000 hrPower Zone controller maintenance alarm 3
Jack Maintenance (lubricate gearing/handle)Lubricate12 moPerform annually
Leveling JacksLubricate500 hr12 moAnnually
Trailer Wheel Bearings LubricationLubricate12 moMinimum every 12 months or 12,000 miles (19,312 km)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

48
TypeItemValueUnitCondition
GapAir filter restriction (replace air filter)20in. H2Oyellow center bar reaches red section
OtherAir Filter Minder Gauge Replacement Threshold20in. H2O
OtherRadiator Cap Coolant Fill Clearance3/4in.below filler neck (approx 2 cm)
PressureEngine oil pressure (normal operating)241-552kPaengine running
PressureEngine oil pressure (normal operating)35-80psiengine running
PressureLoss-of-oil-pressure shutdown verification threshold5psi (34 kPa)shut engine down immediately if pressure does not read this value within 5 seconds of restart
PressureLow Oil Pressure Shutdown Threshold20psi
PressureLow oil pressure shutdown138kPa
PressureLow oil pressure shutdown20psi
PressureMaximum tire pressure50psi
PressureMaximum trailer tire pressure65psi
PressureNormal Operating Oil Pressure35-80psi
PressureOil Pressure Gauge Range0-100psi
PressureOil Pressure Shutdown Confirmation Threshold5psiif not attained within 5 seconds of restart, shut engine down immediately
PressureOil pressure reading after start34kPawithin five seconds
PressureOil pressure reading after start5psiwithin five seconds
SpeedEngine operating speed1800rpm
SpeedFrequency, no load60Hzno load
TemperatureAmbient air temperature limit120°F
TemperatureCoolant Temperature Gauge Range150-250°F
TemperatureHigh Coolant Temperature Shutdown Threshold230°F
TemperatureHigh coolant temperature shutdown230°F (110°C)stop engine immediately at or above this temperature
TemperatureMaximum water temperature110°C
TemperatureMaximum water temperature230°F
TemperatureNormal Operating Coolant Temperature180-200°Faverage ambient air temperature of 70°F (21°C)
TorqueGenerator Drive Plate Bolts30ft-lbs
TorqueGenerator Drive Plate Bolts40ft-lbs
TorqueGenerator drive plate bolts36ft-lbs
TorqueGenerator drive plate bolts49Nm
TorqueGenerator drive plate bolts - MMG25IF430ft-lbs (40 Nm)
TorqueGenerator drive plate bolts - MMG35DF440ft-lbs (54 Nm)
TorqueGenerator drive plate bolts - MMG45IF430ft-lbs (40 Nm)
TorqueGenerator drive plate bolts - MMG55DF440ft-lbs (54 Nm)
TorqueTrailer wheel lug nuts, first pass20-25ft-lbs
TorqueTrailer wheel lug nuts, first pass27-33Nm
TorqueTrailer wheel lug nuts, second pass50-60ft-lbs
TorqueTrailer wheel lug nuts, second pass67-81Nm
TorqueTrailer wheel lug nuts, third pass122-162Nm
TorqueTrailer wheel lug nuts, third pass90-120ft-lbs
VoltageBattery Voltage Gauge Range0-50V
VoltageBattery voltage13-14Vengine running, 12V systems
VoltageBattery voltage24-26Vengine running, 24V systems
VoltageFine voltage adjustment example window, 208/120V position108-132Vline to neutral
VoltageFine voltage adjustment example window, 208/120V position188-228Vline to line
VoltageGenerator output voltage tolerance versus selector switch setting10%
VoltageNormal Battery Reading12-14V12 volt systems, engine running
VoltageNormal Battery Reading24-26V24 volt systems, engine running
VoltageVoltage regulation+/- 1%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilJohn Deere Plus 50 II (John Deere engine)Refer to OEM engine manual for viscosity grade by season/climate
FuelUltra-low-sulfur diesel379.0 L (100 gal total, 90 gal usable)
GreaseHigh quality grease made specifically for lubrication of wheel bearingsTrailer wheel bearings; lubricate at least every 12 months or 12,000 miles (19,312 km); automotive grease for leveling jack internal gearing; lightweight oil for jack handle/screw stem

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

31
CodeNameMeaningSeverityAction
AnInIOM SdAnInIOM SdShutdown alarm configurable on the input of IG-IOM/IGS-PTM.Shutdown
AnInIOM WrnAnInIOM WrnWarning alarm configurable on the input of IG-IOM/IGS-PTM.Warning
Battery Flat (low battery)Battery FlatIf the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection.Shutdown
Binary InputBinary InputConfigurable Warning/Shutdown alarms on the inputs of IL-NT.
ChrgAlternFailChrgAlternFailFailure of the alternator to charge the battery.Warning
EmergencyStopEmergencyStopIf the red emergency stop switch is pushed or opened, shutdown is immediately activated.Shutdown
Engine Temp SdEngine Temp SdWater temperature is greater than Sd Water Temp setpoint.Shutdown
Engine Temp WrnEngine Temp WrnWater temperature is greater than Wrn Water Temp setpoint.Warning
Fgen<,>Fgen<,>The generator frequency is out of limits given by Gen >f and Gen <f setpoints.Shutdown
Fuel Level SdFuel Level SdFuel level is smaller than Sd Fuel Level setpoint (5%).Shutdown
Fuel Level WrnFuel Level WrnFuel level is smaller than Wrn Fuel Level setpoint (15%).Warning
GCB failGCB failFailure of the generator circuit breaker.Shutdown
Igen unblIgen unblThe generator current is unbalanced.Shutdown
Low BackupBattLow BackupBattRTC backup battery is flat (low).Warning
Oil Press SdOil Press SdOil pressure is smaller than Sd Oil Press setpoint.Shutdown
Oil Press WrnOil Press WrnOil pressure is smaller than Wrn Oil Press setpoint.Warning
OverloadOverloadThe load is greater than the value given by Overload setpoint.Shutdown
OverspeedOverspeedThe protection comes active if the speed is greater than Overspeed setpoint.Shutdown
ParamFailParamFailWrong checksum of parameters. Typically happens after downloading new firmware or changing a parameter. The controller stays in INIT mode.Check all parameters, write at least one new parameter.
PickupFaultPickupFaultFailure of the magnetic pick up sensor for speed measurement.Shutdown
Sd IOM failSd IOM failShutdown alarm in case of lost connection to IOM/IGS-PTM module.Shutdown
SprinkIActiveSprinkIActiveThe protection is active if the output Sprinkler is closed.Warning
Start failedStart failedUnit did not start.ShutdownPress FAULT RESET to clear the controller, then press ENGINE START.
Stop failStop failUnit did not stop.Shutdown
UbatUbatBattery voltage is out of limits given by Batt Undervolt setpoints.Warning
UnderspeedUnderspeedDuring starting, when RPM reaches Starting RPM setpoint the starter switches off; speed can drop under Start RPM again and Underspeed becomes active. Protection evaluation starts 5 seconds after startup.Shutdown
Vgen unbalVgen unbalThe generator voltage is unbalanced more than the value of Volt unbal setpoint.Shutdown
Vgen<,>Vgen<,>The generator voltage is out of limits given by Gen <V and Gen >V setpoints.Shutdown
Wrn ECU AlarmWrn ECU AlarmECU alarm list is not empty.Warning
Wrn RA15 failWrn RA15 failWarning alarm in case of lost connection to IGL=RA15 module.Warning
WrnMaintenanceWrnMaintenanceThe period for servicing is set by the WrnMaintenance setpoint; protection comes active when the running hours of the engine reach this value.WarningReset the Time to Service reminder to the 250 hour interval.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting the Display Backlighting adjustment
  1. Press and hold ENTER, then press the up or down arrow to increase or decrease brightness.
  2. Release ENTER when the desired brightness is attained.
Fine Voltage Adjustment adjustment

⚠ NEVER change the voltage selector switch while the engine is running or the controller is on.

Tools: Flat head screwdriver

  1. Check the output voltage on the Generator screen (L1N or L12 voltage).
  2. Nominal output voltage should be within 10% of the voltage rating on the voltage selector switch.
  3. Use a flat head screwdriver to turn the voltage adjustment screw until the voltage matches the selector setting.
  4. Adjustment must be made within the 45 second V Detect countdown.
Lowering the Trailer Tongue installation

⚠ If the jack was used to support the unit, move the jack back to the tongue location before towing.

Tools: Hoist or forklift, Front jack, Hitch pins

  1. Elevate the unit using a hoist or forklift, or use the front jack on the trailer tongue.
  2. Remove the hitch pin (1) securing the tongue to the trailer frame, then remove hitch pin (2) from the trailer frame.
  3. Lower the trailer tongue and reinstall the hitch pins at the locations shown (3).
Checking Generator Drive Plate Torque maintenance

Tools: Torque wrench

  1. Disconnect the engine starting battery.
  2. Remove the generator fan guard.
  3. Torque each of the drive plate bolts to 36 ft-lbs (49 Nm).
  4. Reinstall the generator fan guard. Reconnect the battery.
Jack Maintenance maintenance

⚠ Perform these procedures at least annually.

Tools: Grease gun or needle nose applicator, Automotive grease, Lightweight oil

  1. Side-wind models: apply a small amount of automotive grease to the internal gearing via the jack cover or lubrication point.
  2. Side-wind models: apply lightweight oil to the handle unit at both sides of the tube.
  3. Side-wind models: lubricate the caster wheel axle bolt and nut assembly with the same lightweight oil.
  4. Top-wind models: apply a lightweight oil to the screw stem.
Resetting the Maintenance Alarms maintenance
  1. With unit shut down, move Control Power switch to ON
  2. Press any directional arrow to enter maintenance screens
  3. Press Enter and Stop/Reset simultaneously to open Configuration menu
  4. Move cursor down to Maintenance group
  5. Press right arrow to access sections and highlight Maintenance section
  6. Press right arrow to access parameters and highlight the alarm to reset
  7. Press Enter to select editable parameter, highlight Reset
  8. Press Enter to reset the selected alarm
  9. Repeat for additional alarms
  10. Press and hold Enter for five seconds to save changes
Resetting the Time to Service Reminder maintenance
  1. With the unit shut down, power up the controller with the Control Power switch.
  2. Press PAGE SELECT; lines of text display starting with Password.
  3. Press the down arrow to move the cursor to Engine Protect.
  4. Press ENTER; WrnMaintenance appears with the current service time (0) below it.
  5. Press ENTER; the current run time in hours appears under WrnMaintenance.
  6. Press the up arrow to reset the current run time hour setting to 250.
  7. Press ENTER to save the run time hour setting.
  8. Move the Control Power switch to the OFF (O) position.
Towing the Unit - Wheel Lug Torque maintenance

Tools: Torque wrench

  1. Start all lug nuts by hand.
  2. First pass: tighten to 20-25 ft-lbs (27-33 Nm).
  3. Second pass: tighten to 50-60 ft-lbs (67-81 Nm).
  4. Third pass: tighten to 90-120 ft-lbs (122-162 Nm).
  5. Re-torque lug nuts in sequence after first road use.
Trailer Wheel Bearings maintenance

⚠ Use only a high quality grease made specifically for lubrication of wheel bearings.

Tools: Standard grease gun

  1. Remove the small rubber plug on the grease cap.
  2. Attach a standard grease gun fitting to the grease zerk fitting and pump grease until new grease is visible around the nozzle.
  3. Wipe any excess grease from the hub with a clean cloth and replace the rubber plug.
Auto (Remote) Starting of the Unit operation

⚠ Verify that the contacts on any remote switch linked to the unit are OPEN before entering Auto mode.

Tools: Jumper wire (minimum 16 gauge)

  1. Perform a manual start of the generator at least once to verify the engine operates correctly.
  2. To check the remote start circuit, remove the remote start terminal block wires, press Auto, and attach a jumper wire (minimum 16 gauge) across the two terminals.
  3. The engine should crank, start and run.
  4. Remove the jumper wire; the engine stops. Reconnect any necessary remote start switch wires.
  5. Confirm the unit is in Auto mode; the LCD window should have AUT highlighted.
  6. Close the main circuit breaker (set to ON (I) position).
  7. Secure the generator by closing and locking all access doors.
Auto Exercise Timer operation

⚠ The controller must be in Auto mode to run at the programmed time. Use a trickle battery charger or solargizer to prevent the controller from draining the battery while in Auto mode.

  1. Press PAGE SELECT until Password appears at the top of the screen.
  2. Press down arrow until Date/Time is selected and press ENTER.
  3. Press down arrow until Timer1 Repeat is selected and press ENTER.
  4. Choose the day or days the unit should run and press ENTER.
  5. Press down arrow until Timer1 ON Time is selected and press ENTER.
  6. Adjust the desired time to start running and press ENTER.
  7. Press down arrow until Timer1Duration is selected and press ENTER.
  8. Adjust the run period length and press ENTER.
  9. Press PAGE SELECT three times to return to the Main menu.
  10. Press AUTO to switch modes to automatic.
Manual Starting of the Unit operation

⚠ CARBON MONOXIDE: USING A GENERATOR INDOORS CAN KILL YOU IN MINUTES.

  1. Move the Control Power switch to the ON (I) position.
  2. The LCD window displays system information and all LEDs flash.
  3. The Ready screen is displayed and the LCD indicates Manual mode; Ready/Manual LED lit.
  4. Press ENGINE START. The Prestart screen is displayed and a countdown begins from 20 seconds to 0.
  5. The Starting screen is displayed. The engine cranks and starts running.
  6. The Running screen displays. The 45 second V Detect time delay begins counting down.
  7. The LCD window toggles from the Running screen to the Generator screen then the Engine screen.
  8. If the engine does not start, it pauses 15 seconds; up to three crank cycles are made.
  9. If the engine does not start, LCD shows SD START FAIL. Press FAULT RESET to clear the controller.
  10. Once started, the engine speeds up to a constant 1800 rpm.
  11. Check for excessive noise, vibration, and coolant, oil or fuel leaks before applying loads.
  12. Check that the AC output voltage is correct; fine adjust with the fine voltage adjustment screw.
  13. Check that the frequency is correct; with no loads it should read approximately 60 Hz.
  14. Switch the main circuit breaker to ON (I), then add convenience receptacle loads via their breakers.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
1201GFCI Duplex receptacle L-NGFCI duplex receptacles read 120V in the 120/208V 3-phase and 120/240V positions; twist-locks 208V / 120V (3-phase) or 240V / 120V (1-phase).
120/208V3L1-L2, L2-L3, L3-L1Black (L1), Blue (L2), Red (L3), White (N), Green (G)L-L = 208V; L-N = 120V. Voltage selector switch 120/208V 3-phase position.
120/240V1L3-L1, L1-NBlack (L1), Red (L3), White (N), Green (G)L3-L1 = 240V; L1-N = 120V; L3-N = 120V. 120/240V 1-phase selector position (4 position switch option).
120/240V3L1-L2, L2-L3, L3-L1Black (L1), Blue (L2), Red (L3), White (N), Green (G)L1-L2 = 240V, L1-N = 120V; L2-L3 = 240V, L2-N = 208V; L3-L1 = 240V, L3-N = 120V. 120/240V 3-phase selector position.
1391GFCI Duplex receptacle L-NGFCI duplex receptacles read 139V when the voltage selector switch is in the 277/480V 3-phase position; twist-locks 240V / 139V. Not recommended for normal use.
277/480V3L1-L2, L2-L3, L3-L1Black (L1), Blue (L2), Red (L3), White (N), Green (G)L-L = 480V; L-N = 277V. Voltage selector switch 277/480V 3-phase position; switch is lockable.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Filters for this engine

  • Air filter: Isuzu 8972319000 Donaldson P827653 Wix 46671
  • Fuel filter: Isuzu 8981527372 Donaldson P502163 Donaldson P502424 Wix 33393 Wix 33740
  • Oil filter: Isuzu X13201002 Donaldson P557780 Wix 51452 Ac Delco PF960

Cross-referenced via Donaldson + OEM/engine-maker interchange — options to verify against your serial number, not confirmed for every exact variant.

Also used in

5
  • Hitachi ZX40U — Excavator Compact
  • Hitachi ZX50U — Excavator Compact
  • Kobelco SK80 — Excavator Tracked
  • Sany SY70C — Excavator
  • Sany SY75C — Excavator

Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.

Common questions

What is the oil capacity of the Isuzu 4LE2XAGV01?

The Isuzu 4LE2XAGV01 engine has an oil capacity of 10.4 liters.

What is the displacement of the Isuzu 4LE2XAGV01?

The Isuzu 4LE2XAGV01 has a displacement of 2.2 liters with 4 cylinders.

Which generators use the Isuzu 4LE2XAGV01 engine?

The Isuzu 4LE2XAGV01 powers 2 generator set(s), including Generac MMG45IF4, Generac MMG50ITM.

What oil filter does the Isuzu 4LE2XAGV01 use?

The Isuzu 4LE2XAGV01 uses oil filter part numbers Isuzu X13201002, Donaldson P557780, Wix 51452.

What fuel filter does the Isuzu 4LE2XAGV01 use?

The Isuzu 4LE2XAGV01 uses fuel filter part numbers Isuzu 8981527372, Donaldson P502163, Donaldson P502424.

What air filter does the Isuzu 4LE2XAGV01 use?

The Isuzu 4LE2XAGV01 uses air filter part numbers Isuzu 8972319000, Donaldson P827653, Wix 46671.

What is a common problem with the Isuzu 4LE2XAGV01 engine?

A commonly reported issue on generators using the Isuzu 4LE2XAGV01 is: Unit will not start in AUTO with 2-wire start signal.. Cause: See if screen says unit not activated..