Home›Repair guides›Cummins/Onan›Test the Float Switch Assembly

Cummins/Onan — Test the Float Switch Assembly

Testing & diagnosis · Day Tank Float Switch Assembly

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFC

Procedure

  1. Remove the fuel pump control cover, disconnect the wiring jack and unscrew the assembly from the top of the day tank.
  2. With an ohmmeter, test continuity between each pair of colored leads while holding the assembly vertical; replace assembly if any switch is open (readings should be zero).
  3. Lift each float in turn to 1/8 inch (3 mm) below the C-clip stop and test for continuity; replace assembly if any switch does not open (readings should be infinity).
  4. Use pipe thread sealant when replacing the assembly.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCC →, Cummins/Onan DGDA →, Cummins/Onan DGDB →, Cummins/Onan DGEA →, Cummins/Onan DGFA →, Cummins/Onan DGFC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →