Home›Repair guides›Cummins/Onan›Testing the PMG

Cummins/Onan PCC Control 3100 Series — Testing the PMG

Testing & diagnosis · Permanent Magnet Generator (PMG)

For the Cummins/Onan PCC Control 3100 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFAA, Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFE

Before you start

  • HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control and power output boxes will result in severe personal injury or death.

Procedure

  1. Disconnect plug J10 from the voltage regulator output stage module.
  2. Start the engine at the set and let the speed stabilize.
  3. Measure voltage across lead pairs J10-1 & J10-4, J10-4 & J10-5, and J10-5 & J10-1.
  4. Voltage should be at least 150 VAC for 50 Hz sets and at least 180 VAC for 60 Hz sets, approximately the same for each set of leads.
  5. If voltages are low or uneven, check all leads and connections between A37 and the PMG and repair as necessary.
  6. Stop the set and measure electrical resistance across lead pairs J10-1 & J10-4, J10-4 & J10-5, and J10-5 & J10-1 with a Wheatstone bridge or digital ohmmeter.

Tools required

  • Wheatstone bridge or digital ohmmeter Amazon
  • Voltmeter Amazon
  • Elbow length insulating gloves Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • PMG stator resistance: HC4 = 2/6 ohms; HC5/HC6/HC7 = 4.6 ohms

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.