Cummins/Onan PCC Control 3100 Series — Drying the Windings

Repair & overhaul · Generator windings

For the Cummins/Onan PCC Control 3100 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFAA, Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFE

Before you start

  • Voltage must begin at zero volts and be gradually increased or equipment damage will result.

Procedure

  1. Bolt the generator three phase output terminals together.
  2. Remove the accessory box housing cover and remove plug P10 from connector J10 of A37.
  3. Connect positive and negative leads of a variable 12 VDC source to P10 (positive to red wire P10-6 X, negative to brown wire P10-3 XX).
  4. Attach a clamp-on ammeter to the generator leads, adjust the 12 VDC source for zero voltage, start the set and slowly increase excitation voltage.
  5. Obtain the highest current possible without exceeding generator rating.
  6. Run the genset for approximately one hour, then repeat the insulation resistance tests.
  7. If further drying time is indicated, continue the drying process.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.