Before you start

  • Continued operation with a HI FUEL fault present can lead to spillage of large quantities of fuel if the high-fuel float switch fails.

Procedure

  1. Push the control switch to the ON position for automatic operation; the green SYSTEM READY light will come on and the pump will fill the tank.
  2. When filling an empty tank, the red LO SHUTDOWN and LO FUEL lights will come on; push the panel RESET switch to turn them off after the tank has been filled.
  3. The green PUMP ON light indicates when the pump is running.
  4. Push the control switch to the EMERGENCY RUN position (momentary contact) to pump fuel if the control fails to operate automatically.
  5. Press the TEST switch to test the indicator lights and pump operating circuits.
  6. Press the reset button of the AC or DC circuit breaker if either has tripped.

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.