Cummins/Onan — Operating PowerCommand in Droop Mode

Adjustments · PowerCommand Control

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCC, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGEA, Cummins/Onan DGFA, Cummins/Onan DGFC

Procedure

  1. Set the no load speed and voltage at the desired level (bus must be de-energized or disconnect Bus PT module).
  2. Apply 100% load and adjust KW load sharing gain for desired full load frequency; adjust KVAR load sharing gain for desired full load voltage.
  3. Repeat the process for other generator sets in the system.
  4. Test the system with all available load and verify approximately equal load sharing at no load and maximum load.

Specs & values

  • Connect a 5K resistor across A40-TB1-54 and 55 (KVAR) to cause voltage droop.
  • Connect a 5K resistor across A40-TB1-56 and 57 (KW) to cause frequency droop.