Cummins/Onan LS-15M — Generator Set Grounding Procedure

Maintenance

For the Cummins/Onan LS-15M, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFAA, Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFE

Before you start

  • Do not perform these procedures unless fully trained in medium voltage grounding procedures and have necessary safety equipment. Severe injury or death due to high voltage electrical shock may result.
  • Hazardous voltage. After DC voltage from the test equipment has been applied to the windings and ground, there will be a definite static charge on the windings. Reconnect Grounding Cluster to remove static charge from the winding after each generator test.

Procedure

  1. Open, lock-out and tag-out all sources of power to the immediate work area.
  2. Disable the starting system: disconnect battery charger from AC source.
  3. Remove the negative battery cable and install a lockout device on the cable end.
  4. Put on high voltage gloves with leather protectors.
  5. Using two pre-tested voltage detection devices, verify de-energized condition.
  6. Remove the metal cover from the generator output box to access load terminals.
  7. Install the Grounding Cluster ground clamp to a verified grounded conductor.
  8. Leave grounds connected for at least one minute so static charge can dissipate.
  9. When work is complete, remove the Grounding Cluster in reverse order.
  10. After clearance from all personnel, remove all lock-out devices in reverse order.

Tools required

  • Two pre-tested voltage detection devices Amazon
  • High voltage gloves with leather protectors Amazon
  • Grounding Cluster Amazon
  • Lockout device Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →