Home›Repair guides›Cummins/Onan›Day Tank Control Voltage Conversion (240 VAC to 120 VAC)

Cummins/Onan LS-15M — Day Tank Control Voltage Conversion (240 VAC to 120 VAC)

Installation · Day tank fuel transfer pump control

For the Cummins/Onan LS-15M, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DFAA, Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFE

Before you start

  • Diesel fuel is highly combustible. Do not smoke near fuel and keep flames, sparks and other sources of ignition well away.

Procedure

  1. Remove the two jumpers between terminals TB1-6 and TB1-7 and connect one between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  2. Move selector switch S103 on the control PCB to the up position for 120V.
  3. If equipped with a transformer, remove the two jumpers between terminals H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
  4. Attach a tag to the control box indicating the supply voltage.

Specs & values

  • Control set up at factory for 240 VAC

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →