Cummins/Onan — Insulation Resistance (Megger) & Polarization Index (PI) Testing

Testing & diagnosis · Generator windings

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFAA, Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DFE

Before you start

  • The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.

Procedure

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from A37 and AC control leads 4,5,6,7,8.
  3. If RTD option installed, ground all six RTD temperature leads (18 leads).
  4. Perform Insulation Resistance Test and PI Test for desired windings.
  5. Megger test: apply voltage for up to one minute.
  6. PI test: apply voltage for ten minutes; record 1-minute and 10-minute readings.
  7. PI ratio of 2 or greater is good for new and in-service sets.
  8. Investigate and correct low readings before returning set to service.

Tools required

  • Megger or insulation resistance meter Amazon
  • Grounding cluster Amazon
  • High voltage gloves Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • PI = ten minute reading (megohms) divided by one minute reading (megohms). Ratio of two or greater is considered good.

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.