  • Improper installation of CTs will cause a “335 Reverse Power” shutdown error.

Procedure

  1. Orient CT dot toward the generator (conventional current into dot).
  2. Route U/A, V/B, W/C load leads through CT21, CT22, CT23.
  3. 6 lead sets: route generator output leads through the CTs.
  4. 12 lead sets: route load wires through the CTs.
  5. Connect CT secondary wire 1 to CT pin 1; 2/3 to pin 2 (high voltage) or pin 3 (low voltage).

Specs & values

  • CT21 - U load leads (A phase)
  • CT22 - V load leads (B phase)
  • CT23 - W load leads (C phase)