Home›Perkins›Perkins 1103A-33TG1

Perkins 1103A-33TG1 Generator Set

The Perkins 1103A-33TG1 is a 39.7 kW (49.6 kVA) diesel standby generator set powered by a Perkins 1103A-33TG1 engine. It is available at 12 V, 50 Hz and rated 65 A. It holds about 8.3 L (2.2 gal) of oil and 10.2 L (2.7 gal) of coolant, with a maximum ambient rating of 53 °C. The set measures 1049×634×951 mm (41.3×25.0×37.4 in), weighs about 420 kg (926 lb) and produces 88.2 dBA. The same 1103A-33TG1 engine also powers generator sets from Caps, FG Wilson and Olympian.

39.7 kW
Standby
3.3 L
Displacement
8.3 L
Oil capacity
4
Document types

How to read your Perkins serial & model number →

Typical fuel consumption for 40–45 kW Diesel generators →

Compare with other 40–45 kW Diesel generators →

Service parts for the 1103A-33TG1

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power39.7 kW
Standby kVA49
Prime power36 kW
Oil capacity8.3 L
Voltage options12 V
Rated current65 A
Power factor0.8
Coolant capacity10.2 L
Max ambient53 °C
Dimensions (L×W×H)1049×634×951 mm
Dry weight420 kg
Sound level88.2 dBA

Engine

Perkins 1103A-33TG1
Oil capacity8.3 L
Coolant capacity10.2 L
Displacement3.3 L
AspirationTurbocharged
Rated speed1800 rpm

Filters for the Perkins 1103A-33TG1

2

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Oil filterP554403Lube Filter, Spin-On Full FlowPERKINS 26540249, NAPA 1806, BALDWIN BT216, VERSATILE 00034778 KuduParts $22.00
Fuel filterP556287Fuel Filter, CartridgePERKINS 2650097, PERKINS 2650125, BALDWIN BF884, RENAULT VI 0003052535 FridayParts $26.90

Same engine, other brands

3 brands

The Perkins 1103A-33TG1 in this set also powers 16 generator sets sold under 3 other brands. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
FG WilsonGTA 201AE20, LLB1514P, P32P3S, P35-1S, P35E3S, P40, P40P3, P44E3, P45P3, P50-1, P50-3, P50-3_50Hz +2 more
CapsCP50-TP1
OlympianGEP50-7

Maintenance & consumables

for the Perkins 1103A-33TG1
ItemSpecCapacityPart #Interval
Air filterReplaceable Element1000051238261 hr Amazon eBay $63.75 NAPA $62.83 FridayParts $24.99
Fuel filterReplaceable Element—1484 hr
Oil filterSpin-On, Full Flow—1200 hr
Battery12/Negative—100 hr
BeltN/A—1200 hr
CoolantWater—
Coolant filterCentrifugal—100 hr
OilAPI CG4 / CH4 15W-408.3 l—300 hr
Spark plugReplaceable Element—300 hr

Service intervals

26
ItemActionHoursMonthsNotes
Air cleaner and dust bowlClean1000 hr12 mo500 hours or yearly
Air filter elementChange1000 hr12 mo500 hours or yearly
Air/fuel/coolant & oil leakageCheck1000 hr12 mo500 hours or yearly
Alternator insulation resistanceTest1000 hr12 moMeasure - 500 hours or yearly
Condition of cooling fan assemblyCheck1000 hr12 mo500 hours or yearly
Condition of vibration dampersCheck1000 hr12 mo500 hours or yearly
CoolersClean1000 hr12 moCheck and clean externally
Door hinges and locksLubricate1000 hr12 moGrease - 500 hours or yearly
Electrolyte level and terminals of batteryCheck500 hr12 mo500 hours or yearly
Engine oilChange1000 hr12 moReplace - 500 hours or yearly
Engine oil filterReplace1000 hr12 mo500 hours or yearly
Filter closed breather systemReplace1000 hr12 mo500 hours or yearly
Fixation of hoses, cables and pipesCheck1000 hr12 mo500 hours or yearly
Fuel filter elementReplace1000 hr12 mo500 hours or yearly
Fuel prefilter elementReplace1000 hr12 mo500 hours or yearly
Glycol level in coolantCheck1000 hr12 moChange coolant every 5 years
Mechanical linksLubricate1000 hr12 moGrease - 500 hours or yearly
Oil and coolant levelCheck1000 hr12 mo500 hours or yearly
PH level of engine coolantCheck1000 hr12 mo500 hours or yearly
Safety cartridgeReplace1000 hr12 mo500 hours or yearly
Tension and condition of the drive beltCheck1000 hr12 mo500 hours or yearly
Water in fuel filterDrain1000 hr12 mo500 hours or yearly
Alternator and starter motorCheck1000 hr
Electrical system: security of cables and wearCheck1000 hr
Engine inlet and outlet valvesAdjust1000 hrCheck/Adjust if necessary
Inspection by Atlas Copco Service technicianInspect1000 hr

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

8
TypeItemValueUnitCondition
OtherCoolant pH level7 - 9.5pHreplace coolant if below 7 or above 9.5; typical value for EG = 8.6
OtherEarthing rod diffusion resistance1kΩmaximum
OtherGlycol concentration in coolant33 - 68vol.%always above 33 vol.%, not more than 68 vol.%
OtherInsulation monitoring relay factory setting (IT-relay N14)13kΩfactory set
PressureEngine oil pressure shut down0.5baractivates at
ResistanceAlternator insulation resistance5MΩminimum, measured with a 500 V megger between earth terminal and L1
SpeedOverspeed setpoint (Qc3001)1650rpmdefault setting
TemperatureEngine coolant temperature shut down105°Cactivates at

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantPARCOOL EGabove -40°CEthylene glycol based, premixed in optimum 50/50 dilution ratio, antifreeze protection guaranteed to -40°C; free of nitride and amines
Engine oil15W40Marking on generator: Use 15W40 oil only
Engine oilPAROIL 5W30-25°C to 30°CSynthetic ultra high performance diesel engine oil with high viscosity-index
Engine oilPAROIL 15W40-15°C to 40°CMineral based high performance diesel engine oil with high viscosity-index
FueldieselGenerator may be refuelled with diesel fuel only

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

9
Measuring the alternator insulation resistance diagnostic

Tools: 500 V megger

  1. Use a 500 V megger.
  2. If the N-terminal is connected to the earthing system, disconnect it from the earth terminal. Disconnect the AVR.
  3. Connect the megger between the earth terminal and terminal L1 and generate a voltage of 500 V.
  4. The scale must indicate a resistance of at least 5 MΩ.
Connecting the load installation

⚠ For safety, provide an isolating switch or circuit breaker in each load circuit.

Tools: Cable lugs

  1. Check whether frequency, voltage and current comply with the ratings of the generator.
  2. Open the door of the control and indicator panel and the transparent door in front of terminal board X1.
  3. Provide the wire ends with cable lugs suited for the cable terminals.
  4. Loosen the cable clamp and push the wire ends of the load cable through the orifice and clamp.
  5. Connect the wires to terminals L1, L2, L3, N and PE of X1 and tighten the bolts securely.
  6. Tighten the cable clamp.
  7. Close the transparent door in front of X1.
Preparing for operation after storage maintenance
  1. Remove the wrapping, VCI paper and silica gel bags and check the generator thoroughly using the 'Before starting' checklist.
  2. Check that the insulation resistance of the generator exceeds 5 MΩ.
  3. Replace the fuel filter and fill the fuel tank; vent the fuel system.
  4. Reinstall and connect the battery, if necessary after being recharged.
  5. Submit the generator to a test run.
Replacing the coolant maintenance

⚠ Never remove the cooling system filler cap while coolant is hot.

⚠ Never mix different coolants and mix the coolant components outside the cooling system.

  1. Drain: completely drain the entire cooling system and dispose of used coolant per regulations.
  2. Flush: flush twice with clean water.
  3. Determine the amount of PARCOOL EG required and pour into the radiator top tank.
  4. Fill: run the engine until normal engine operation temperature is reached, then turn off and allow to cool.
  5. Recheck coolant level and add if necessary.
Topping up of coolant maintenance

⚠ Topping up the coolant with water only changes the concentration of additives and is therefore not allowed.

  1. Verify the engine cooling system is in good condition (no leaks, clean).
  2. Check the condition of the coolant.
  3. If the coolant condition is outside the limits, replace the complete coolant.
  4. Always top up with PARCOOL EG.
Before starting operation
  1. With generator level, check engine oil level; must be near but not exceed high mark on dipstick.
  2. Check coolant level in expansion tank; must be near the FULL mark.
  3. Drain coolant and sediment from fuel pre-filter; check fuel level and top up.
  4. Check vacuum indicator of air filter; replace element if red part shows completely.
  5. Press the vacuator valve of the air filter to remove dust.
  6. Check generator for leakage and tightness of wire terminals; correct if necessary.
  7. Check that fuse F4 is not activated and emergency stop is in the OUT position.
  8. Check that the load is switched off.
  9. Check that circuit breaker Q1 is switched off.
  10. Check that the earth fault protection (N13) has not tripped (reset if necessary).
Starting Qc1001 locally operation
  1. Switch on the battery switch.
  2. Switch off circuit breaker Q1 (not needed when a plant contactor is installed between Q1 and the load).
  3. Put the starter switch in start position; the unit starts a preheating cycle which takes 12 seconds.
  4. After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
  5. Switch on circuit breaker Q1 in case no contactor is installed.
Starting Qc1001 remotely operation
  1. Put the starter switch in the remote position.
  2. Switch on circuit breaker Q1.
  3. Put the remote start/stop switch in start position; unit starts a 12 second preheating cycle.
  4. After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
Stopping Qc1001 locally operation
  1. Switch off the load.
  2. Switch off circuit breaker Q1.
  3. Let the engine run for about 5 minutes.
  4. Stop the engine by putting the starter switch in position O.
  5. Lock the side doors and the door of the indicators and control panel to avoid unauthorized access.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Perkins 1103A-33TG1?

The Perkins 1103A-33TG1 is rated 39.7 kW standby (49.6 kVA).

Which engine powers the Perkins 1103A-33TG1?

The Perkins 1103A-33TG1 is powered by the Perkins 1103A-33TG1 engine.

Is the Perkins 1103A-33TG1 diesel or gas?

The Perkins 1103A-33TG1 runs on diesel.

What is the oil capacity of the Perkins 1103A-33TG1?

The Perkins 1103A-33TG1 engine in the Perkins 1103A-33TG1 has an oil capacity of 8.3 liters.

How much coolant does the Perkins 1103A-33TG1 hold?

The Perkins 1103A-33TG1 cooling system holds 10.2 liters (2.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the prime power rating of the Perkins 1103A-33TG1?

The Perkins 1103A-33TG1 is rated 36 kW prime (45 kVA), against 39.7 kW standby.

What is the sound level of the Perkins 1103A-33TG1?

The Perkins 1103A-33TG1 is rated at 88.2 dBA, per the manufacturer specification sheet.

How much does the Perkins 1103A-33TG1 weigh?

The Perkins 1103A-33TG1 has a dry weight of 420 kg (925 lb).

What voltage does the Perkins 1103A-33TG1 produce?

The Perkins 1103A-33TG1 is offered in 12 V.

Which air filter part number does the Perkins 1103A-33TG1 take?

The Perkins 1103A-33TG1 uses air filter part number 1000051238.

Parts

2model family
Part #DescriptionQtySystem
1103A-33TG1LL2014C10.6 (2.8) 11.9 (3.1)Service part / kit Amazon eBay $209.00 FridayParts $58.99
1106A-70TAGPerkins 1106A-70TAG ElectropaKService part / kit Amazon eBay $165.89

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime25%8.11.78

Available documents

Engine spec — 00-00 NGT-50-LS- (Perkins)Engine spec — 1103A-33TG1 ElectropaK (PN1781 Jan08) (Perkins)Engine spec — 1103A-33TG1 ElectropaK (PN1781 Nov08) (Perkins)Engine spec — 1103A-33TG1 ElectropaK PN1781 (Perkins)Engine spec — 1103A-33TG1-ElectropaK-PN1781-signed (Perkins)Engine spec — 1103A-33TG1-ElectropaK-PN1781 (Perkins)Engine spec — 1103A-33TG1-Electropak (Perkins)Engine spec — 1103A-33TG1 ElectropaK Preliminary (pn1781-09-04) (Perkins)Engine spec — 1103a-33tg1 electropak (pn1781 - jan06) (Perkins)Engine spec — Perkins Engines Guide www.engine.od.ua (Perkins)Spec sheet — Catalogue-Perkins-1103A-33TG1 (Perkins)Spec sheet — GenSet Power Selector Unregulated PN3012 (Perkins)Spec sheet — Pramac-Generators (Pramac)Operator's manual — 1680 (Atlas Copco)Reference — 2284FG WILSON KITS (Perkins)Reference — GenSet Power Selector Chart Unregulated Territories (PN1542 75th) (Perkins)Reference — GenSet Power Selector Chart Unregulated Territories(pn1542 - Oct06) (Perkins)Reference — GenSet Selector Unregulated (PN1542 Feb09) (Perkins)Reference — GenSet Selector Unregulated Iss2 PN1542 Jan10 (Perkins)Reference — Perkins In China EP PN3014 (chi)-crosspage (Perkins)Reference — Powernews MEE 2014Reference — Pramac 1.500 rpm (Pramac)Parts manual — 6260eba29ea145aaa7b92519 Perkins Catalogue (Perkins)Service manual — perkins-1103a-33tg1 (Perkins)

This page was generated from the 24 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Air filter 1000051238$62.83