Service parts for the 1103A-33TG1
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 39.7 kW |
| Standby kVA | 49 |
| Prime power | 36 kW |
| Oil capacity | 8.3 L |
| Voltage options | 12 V |
| Rated current | 65 A |
| Power factor | 0.8 |
| Coolant capacity | 10.2 L |
| Max ambient | 53 °C |
| Dimensions (L×W×H) | 1049×634×951 mm |
| Dry weight | 420 kg |
| Sound level | 88.2 dBA |
Engine
| Oil capacity | 8.3 L |
|---|---|
| Coolant capacity | 10.2 L |
| Displacement | 3.3 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Filters for the Perkins 1103A-33TG1
2Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P554403 | Lube Filter, Spin-On Full Flow | PERKINS 26540249, NAPA 1806, BALDWIN BT216, VERSATILE 00034778 | KuduParts $22.00 |
| Fuel filter | P556287 | Fuel Filter, Cartridge | PERKINS 2650097, PERKINS 2650125, BALDWIN BF884, RENAULT VI 0003052535 | FridayParts $26.90 |
Same engine, other brands
3 brandsThe Perkins 1103A-33TG1 in this set also powers 16 generator sets sold under 3 other brands. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| FG Wilson | GTA 201AE20, LLB1514P, P32P3S, P35-1S, P35E3S, P40, P40P3, P44E3, P45P3, P50-1, P50-3, P50-3_50Hz +2 more |
| Caps | CP50-TP1 |
| Olympian | GEP50-7 |
Maintenance & consumables
for the Perkins 1103A-33TG1| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Replaceable Element | 1000051238 | 261 hr | Amazon eBay $63.75 NAPA $62.83 FridayParts $24.99 | |
| Fuel filter | Replaceable Element | — | 1484 hr | ||
| Oil filter | Spin-On, Full Flow | — | 1200 hr | ||
| Battery | 12/Negative | — | 100 hr | ||
| Belt | N/A | — | 1200 hr | ||
| Coolant | Water | — | |||
| Coolant filter | Centrifugal | — | 100 hr | ||
| Oil | API CG4 / CH4 15W-40 | 8.3 l | — | 300 hr | |
| Spark plug | Replaceable Element | — | 300 hr |
Service intervals
26| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Air cleaner and dust bowl | Clean | 1000 hr | 12 mo | 500 hours or yearly |
| Air filter element | Change | 1000 hr | 12 mo | 500 hours or yearly |
| Air/fuel/coolant & oil leakage | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Alternator insulation resistance | Test | 1000 hr | 12 mo | Measure - 500 hours or yearly |
| Condition of cooling fan assembly | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Condition of vibration dampers | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Coolers | Clean | 1000 hr | 12 mo | Check and clean externally |
| Door hinges and locks | Lubricate | 1000 hr | 12 mo | Grease - 500 hours or yearly |
| Electrolyte level and terminals of battery | Check | 500 hr | 12 mo | 500 hours or yearly |
| Engine oil | Change | 1000 hr | 12 mo | Replace - 500 hours or yearly |
| Engine oil filter | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Filter closed breather system | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Fixation of hoses, cables and pipes | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Fuel filter element | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Fuel prefilter element | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Glycol level in coolant | Check | 1000 hr | 12 mo | Change coolant every 5 years |
| Mechanical links | Lubricate | 1000 hr | 12 mo | Grease - 500 hours or yearly |
| Oil and coolant level | Check | 1000 hr | 12 mo | 500 hours or yearly |
| PH level of engine coolant | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Safety cartridge | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Tension and condition of the drive belt | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Water in fuel filter | Drain | 1000 hr | 12 mo | 500 hours or yearly |
| Alternator and starter motor | Check | 1000 hr | ||
| Electrical system: security of cables and wear | Check | 1000 hr | ||
| Engine inlet and outlet valves | Adjust | 1000 hr | Check/Adjust if necessary | |
| Inspection by Atlas Copco Service technician | Inspect | 1000 hr |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
8| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Coolant pH level | 7 - 9.5 | pH | replace coolant if below 7 or above 9.5; typical value for EG = 8.6 |
| Other | Earthing rod diffusion resistance | 1 | kΩ | maximum |
| Other | Glycol concentration in coolant | 33 - 68 | vol.% | always above 33 vol.%, not more than 68 vol.% |
| Other | Insulation monitoring relay factory setting (IT-relay N14) | 13 | kΩ | factory set |
| Pressure | Engine oil pressure shut down | 0.5 | bar | activates at |
| Resistance | Alternator insulation resistance | 5 | MΩ | minimum, measured with a 500 V megger between earth terminal and L1 |
| Speed | Overspeed setpoint (Qc3001) | 1650 | rpm | default setting |
| Temperature | Engine coolant temperature shut down | 105 | °C | activates at |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | PARCOOL EG | above -40°C | Ethylene glycol based, premixed in optimum 50/50 dilution ratio, antifreeze protection guaranteed to -40°C; free of nitride and amines | ||
| Engine oil | 15W40 | Marking on generator: Use 15W40 oil only | |||
| Engine oil | PAROIL 5W30 | -25°C to 30°C | Synthetic ultra high performance diesel engine oil with high viscosity-index | ||
| Engine oil | PAROIL 15W40 | -15°C to 40°C | Mineral based high performance diesel engine oil with high viscosity-index | ||
| Fuel | diesel | Generator may be refuelled with diesel fuel only |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
9Measuring the alternator insulation resistance diagnostic
Tools: 500 V megger
- Use a 500 V megger.
- If the N-terminal is connected to the earthing system, disconnect it from the earth terminal. Disconnect the AVR.
- Connect the megger between the earth terminal and terminal L1 and generate a voltage of 500 V.
- The scale must indicate a resistance of at least 5 MΩ.
Connecting the load installation
⚠ For safety, provide an isolating switch or circuit breaker in each load circuit.
Tools: Cable lugs
- Check whether frequency, voltage and current comply with the ratings of the generator.
- Open the door of the control and indicator panel and the transparent door in front of terminal board X1.
- Provide the wire ends with cable lugs suited for the cable terminals.
- Loosen the cable clamp and push the wire ends of the load cable through the orifice and clamp.
- Connect the wires to terminals L1, L2, L3, N and PE of X1 and tighten the bolts securely.
- Tighten the cable clamp.
- Close the transparent door in front of X1.
Preparing for operation after storage maintenance
- Remove the wrapping, VCI paper and silica gel bags and check the generator thoroughly using the 'Before starting' checklist.
- Check that the insulation resistance of the generator exceeds 5 MΩ.
- Replace the fuel filter and fill the fuel tank; vent the fuel system.
- Reinstall and connect the battery, if necessary after being recharged.
- Submit the generator to a test run.
Replacing the coolant maintenance
⚠ Never remove the cooling system filler cap while coolant is hot.
⚠ Never mix different coolants and mix the coolant components outside the cooling system.
- Drain: completely drain the entire cooling system and dispose of used coolant per regulations.
- Flush: flush twice with clean water.
- Determine the amount of PARCOOL EG required and pour into the radiator top tank.
- Fill: run the engine until normal engine operation temperature is reached, then turn off and allow to cool.
- Recheck coolant level and add if necessary.
Topping up of coolant maintenance
⚠ Topping up the coolant with water only changes the concentration of additives and is therefore not allowed.
- Verify the engine cooling system is in good condition (no leaks, clean).
- Check the condition of the coolant.
- If the coolant condition is outside the limits, replace the complete coolant.
- Always top up with PARCOOL EG.
Before starting operation
- With generator level, check engine oil level; must be near but not exceed high mark on dipstick.
- Check coolant level in expansion tank; must be near the FULL mark.
- Drain coolant and sediment from fuel pre-filter; check fuel level and top up.
- Check vacuum indicator of air filter; replace element if red part shows completely.
- Press the vacuator valve of the air filter to remove dust.
- Check generator for leakage and tightness of wire terminals; correct if necessary.
- Check that fuse F4 is not activated and emergency stop is in the OUT position.
- Check that the load is switched off.
- Check that circuit breaker Q1 is switched off.
- Check that the earth fault protection (N13) has not tripped (reset if necessary).
Starting Qc1001 locally operation
- Switch on the battery switch.
- Switch off circuit breaker Q1 (not needed when a plant contactor is installed between Q1 and the load).
- Put the starter switch in start position; the unit starts a preheating cycle which takes 12 seconds.
- After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
- Switch on circuit breaker Q1 in case no contactor is installed.
Starting Qc1001 remotely operation
- Put the starter switch in the remote position.
- Switch on circuit breaker Q1.
- Put the remote start/stop switch in start position; unit starts a 12 second preheating cycle.
- After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
Stopping Qc1001 locally operation
- Switch off the load.
- Switch off circuit breaker Q1.
- Let the engine run for about 5 minutes.
- Stop the engine by putting the starter switch in position O.
- Lock the side doors and the door of the indicators and control panel to avoid unauthorized access.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Perkins 1103A-33TG1?
The Perkins 1103A-33TG1 is rated 39.7 kW standby (49.6 kVA).
Which engine powers the Perkins 1103A-33TG1?
The Perkins 1103A-33TG1 is powered by the Perkins 1103A-33TG1 engine.
Is the Perkins 1103A-33TG1 diesel or gas?
The Perkins 1103A-33TG1 runs on diesel.
What is the oil capacity of the Perkins 1103A-33TG1?
The Perkins 1103A-33TG1 engine in the Perkins 1103A-33TG1 has an oil capacity of 8.3 liters.
How much coolant does the Perkins 1103A-33TG1 hold?
The Perkins 1103A-33TG1 cooling system holds 10.2 liters (2.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Perkins 1103A-33TG1?
The Perkins 1103A-33TG1 is rated 36 kW prime (45 kVA), against 39.7 kW standby.
What is the sound level of the Perkins 1103A-33TG1?
The Perkins 1103A-33TG1 is rated at 88.2 dBA, per the manufacturer specification sheet.
How much does the Perkins 1103A-33TG1 weigh?
The Perkins 1103A-33TG1 has a dry weight of 420 kg (925 lb).
What voltage does the Perkins 1103A-33TG1 produce?
The Perkins 1103A-33TG1 is offered in 12 V.
Which air filter part number does the Perkins 1103A-33TG1 take?
The Perkins 1103A-33TG1 uses air filter part number 1000051238.
Repair guides
8- Before starting
- Connecting the load
- Measuring the alternator insulation resistance
- Preparing for operation after storage
- Starting Qc1001 locally
- Starting Qc1001 remotely
- Stopping Qc1001 locally
- Topping up of coolant
Step-by-step procedures compiled from the Perkins service manual for this model.
Parts
2model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 1103A-33TG1 | LL2014C | 10.6 (2.8) 11.9 (3.1) | Service part / kit | Amazon eBay $209.00 FridayParts $58.99 |
| 1106A-70TAG | Perkins 1106A-70TAG ElectropaK | Service part / kit | Amazon eBay $165.89 |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 8.1 | 1.78 |
Available documents
This page was generated from the 24 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.