Atlas Copco — Preparing for operation after storage
Maintenance · Generator
From a Atlas Copco operator's manual covering: 1103A-33TG1, 1103A-33TG2, QAS 30 Pd, QAS 45 Pd, QAS 60 Pd, Qc1001, Qc3001. Check it applies to your exact model before use.
Applies to: Perkins 1103A-33TG1, Perkins 1103A-33TG2, Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine
Procedure
- Remove the wrapping, VCI paper and silica gel bags and check the generator thoroughly using the 'Before starting' checklist.
- Check that the insulation resistance of the generator exceeds 5 MΩ.
- Replace the fuel filter and fill the fuel tank; vent the fuel system.
- Reinstall and connect the battery, if necessary after being recharged.
- Submit the generator to a test run.
Specs & values
- Insulation resistance exceeds 5 MΩ
Full service-parts list: Perkins 1103A-33TG1 →, Perkins 1103A-33TG2 →, Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine →
Source: Atlas Copco operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.