Home›Engines›Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd)
Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) Engine
The Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) is a 3.3 L 3-cylinder engine. It powers generator sets from Atlas Copco, including the QAS 30 Pd, QAS 45 Pd, QAS 60 Pd and Qc3001.
Also known as: PERKINS 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd)
Part of the Perkins 1103A engine family — 5 variants share parts & fitment.
Service parts for the 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd)
The cheapest captured merchant offer per filter — see the full cross-reference below for every OEM/aftermarket option.
Prices captured from merchant listings; some links are affiliate links. Verify against your serial number before ordering.
Engine specifications
| Displacement | 3.3 L |
|---|
| Cylinders | 3 |
|---|
Common problems
8- The starter motor turns the engine too slowly
Cause: Battery capacity too low. Bad electrical connection. Fault in starter motor. Wrong grade of lubricating oil. - The engine does not start or is difficult to start
Cause: Starter motor turns engine too slowly. Fuel tank empty. Fault in fuel control solenoid. Restriction in a fuel pipe. Fault in fuel lift pump. Dirty fuel filter element. Air in fuel system. Fault in atomisers. Cold start system used incorrectly. Fault in cold start system. Restriction in fuel tank vent. Wrong type or grade of fuel used. Restriction in exhaust pipe. - Not enough power
Cause: Restriction in a fuel pipe. Fault in fuel lift pump. Dirty fuel filter element. Restriction in air filter/cleaner or induction system. Air in fuel system. Fault in atomisers or atomisers of an incorrect type. - Lower than rated voltage at load
Fix: Voltage potentiometer out of setting. Reset voltage potentiometer. Intervention by protection. - Low voltage at no load
Fix: Voltage potentiometer out of setting. Reset voltage potentiometer. Intervention of protection. Check rpm. Winding failure. Check windings. - High voltage at no load
Fix: Voltage potentiometer out of setting. Reset voltage potentiometer. Failed regulator. Substitute regulator. - Alternator does not excite
Fix: Blown fuse. Replace fuse. Insufficient residual voltage. Increase the speed by 15%. No residual voltage. For an instant apply on the + and – terminals of the electronic regulator a 12 V battery voltage with a 30 Ω resistor in series respecting the polarities. - After being excited alternator does not excite
Fix: Connections are interrupted. Check connection cables as per attached drawings.
Compiled from service & troubleshooting documentation across every generator set that uses the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd).
Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|
| Air filter | | | 901047 | 500 hr | Amazon $154.99 eBay $63.75 FridayParts $24.99 KuduParts $110.00 |
| Fuel filter | Replace | | — | 500 hr | |
| Oil filter | Replace | | — | 500 hr | |
| Battery | | | — | 1200 hr | |
| Belt | | | — | 500 hr | |
| Coolant | | | — | 1000 hr | |
| Coolant filter | Replace | | — | 500 hr | |
| Oil | High-quality, mineral, hydraulic or synthesized hydrocarbon oil with rust and oxidation inhibitors, anti-foam and anti-wear properties is recommended. | | — | 500 hr | |
| Spark plug | | | — | 500 hr | |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
Service intervals
26| Item | Action | Hours | Months | Notes |
|---|
| Air cleaner and dust bowl | Clean | 1000 hr | 12 mo | 500 hours or yearly |
| Air filter element | Change | 1000 hr | 12 mo | 500 hours or yearly |
| Air/fuel/coolant & oil leakage | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Alternator insulation resistance | Test | 1000 hr | 12 mo | Measure - 500 hours or yearly |
| Condition of cooling fan assembly | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Condition of vibration dampers | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Coolers | Clean | 1000 hr | 12 mo | Check and clean externally |
| Door hinges and locks | Lubricate | 1000 hr | 12 mo | Grease - 500 hours or yearly |
| Electrolyte level and terminals of battery | Check | 500 hr | 12 mo | 500 hours or yearly |
| Engine oil | Change | 1000 hr | 12 mo | Replace - 500 hours or yearly |
| Engine oil filter | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Filter closed breather system | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Fixation of hoses, cables and pipes | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Fuel filter element | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Fuel prefilter element | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Glycol level in coolant | Check | 1000 hr | 12 mo | Change coolant every 5 years |
| Mechanical links | Lubricate | 1000 hr | 12 mo | Grease - 500 hours or yearly |
| Oil and coolant level | Check | 1000 hr | 12 mo | 500 hours or yearly |
| PH level of engine coolant | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Safety cartridge | Replace | 1000 hr | 12 mo | 500 hours or yearly |
| Tension and condition of the drive belt | Check | 1000 hr | 12 mo | 500 hours or yearly |
| Water in fuel filter | Drain | 1000 hr | 12 mo | 500 hours or yearly |
| Alternator and starter motor | Check | 1000 hr | | |
| Electrical system: security of cables and wear | Check | 1000 hr | | |
| Engine inlet and outlet valves | Adjust | 1000 hr | | Check/Adjust if necessary |
| Inspection by Atlas Copco Service technician | Inspect | 1000 hr | | |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
8| Type | Item | Value | Unit | Condition |
|---|
| Other | Coolant pH level | 7 - 9.5 | pH | replace coolant if below 7 or above 9.5; typical value for EG = 8.6 |
| Other | Earthing rod diffusion resistance | 1 | kΩ | maximum |
| Other | Glycol concentration in coolant | 33 - 68 | vol.% | always above 33 vol.%, not more than 68 vol.% |
| Other | Insulation monitoring relay factory setting (IT-relay N14) | 13 | kΩ | factory set |
| Pressure | Engine oil pressure shut down | 0.5 | bar | activates at |
| Resistance | Alternator insulation resistance | 5 | MΩ | minimum, measured with a 500 V megger between earth terminal and L1 |
| Speed | Overspeed setpoint (Qc3001) | 1650 | rpm | default setting |
| Temperature | Engine coolant temperature shut down | 105 | °C | activates at |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|
| Coolant | PARCOOL EG | | above -40°C | | Ethylene glycol based, premixed in optimum 50/50 dilution ratio, antifreeze protection guaranteed to -40°C; free of nitride and amines |
| Engine oil | 15W40 | | | | Marking on generator: Use 15W40 oil only |
| Engine oil | PAROIL 5W30 | | -25°C to 30°C | | Synthetic ultra high performance diesel engine oil with high viscosity-index |
| Engine oil | PAROIL 15W40 | | -15°C to 40°C | | Mineral based high performance diesel engine oil with high viscosity-index |
| Fuel | diesel | | | | Generator may be refuelled with diesel fuel only |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
9Measuring the alternator insulation resistance diagnostic
Tools: 500 V megger
- Use a 500 V megger.
- If the N-terminal is connected to the earthing system, disconnect it from the earth terminal. Disconnect the AVR.
- Connect the megger between the earth terminal and terminal L1 and generate a voltage of 500 V.
- The scale must indicate a resistance of at least 5 MΩ.
Connecting the load installation
⚠ For safety, provide an isolating switch or circuit breaker in each load circuit.
Tools: Cable lugs
- Check whether frequency, voltage and current comply with the ratings of the generator.
- Open the door of the control and indicator panel and the transparent door in front of terminal board X1.
- Provide the wire ends with cable lugs suited for the cable terminals.
- Loosen the cable clamp and push the wire ends of the load cable through the orifice and clamp.
- Connect the wires to terminals L1, L2, L3, N and PE of X1 and tighten the bolts securely.
- Tighten the cable clamp.
- Close the transparent door in front of X1.
Preparing for operation after storage maintenance
- Remove the wrapping, VCI paper and silica gel bags and check the generator thoroughly using the 'Before starting' checklist.
- Check that the insulation resistance of the generator exceeds 5 MΩ.
- Replace the fuel filter and fill the fuel tank; vent the fuel system.
- Reinstall and connect the battery, if necessary after being recharged.
- Submit the generator to a test run.
Replacing the coolant maintenance
⚠ Never remove the cooling system filler cap while coolant is hot.
⚠ Never mix different coolants and mix the coolant components outside the cooling system.
- Drain: completely drain the entire cooling system and dispose of used coolant per regulations.
- Flush: flush twice with clean water.
- Determine the amount of PARCOOL EG required and pour into the radiator top tank.
- Fill: run the engine until normal engine operation temperature is reached, then turn off and allow to cool.
- Recheck coolant level and add if necessary.
Topping up of coolant maintenance
⚠ Topping up the coolant with water only changes the concentration of additives and is therefore not allowed.
- Verify the engine cooling system is in good condition (no leaks, clean).
- Check the condition of the coolant.
- If the coolant condition is outside the limits, replace the complete coolant.
- Always top up with PARCOOL EG.
Before starting operation
- With generator level, check engine oil level; must be near but not exceed high mark on dipstick.
- Check coolant level in expansion tank; must be near the FULL mark.
- Drain coolant and sediment from fuel pre-filter; check fuel level and top up.
- Check vacuum indicator of air filter; replace element if red part shows completely.
- Press the vacuator valve of the air filter to remove dust.
- Check generator for leakage and tightness of wire terminals; correct if necessary.
- Check that fuse F4 is not activated and emergency stop is in the OUT position.
- Check that the load is switched off.
- Check that circuit breaker Q1 is switched off.
- Check that the earth fault protection (N13) has not tripped (reset if necessary).
Starting Qc1001 locally operation
- Switch on the battery switch.
- Switch off circuit breaker Q1 (not needed when a plant contactor is installed between Q1 and the load).
- Put the starter switch in start position; the unit starts a preheating cycle which takes 12 seconds.
- After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
- Switch on circuit breaker Q1 in case no contactor is installed.
Starting Qc1001 remotely operation
- Put the starter switch in the remote position.
- Switch on circuit breaker Q1.
- Put the remote start/stop switch in start position; unit starts a 12 second preheating cycle.
- After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
Stopping Qc1001 locally operation
- Switch off the load.
- Switch off circuit breaker Q1.
- Let the engine run for about 5 minutes.
- Stop the engine by putting the starter switch in position O.
- Lock the side doors and the door of the indicators and control panel to avoid unauthorized access.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Parts cataloged across the Perkins 1103A family
16| Part # | Description | Category |
|---|
| LL2014J | Filtre Raccor | Filter |
| 266-6830 | Fuel injector | Injector |
| 1103A-33 | OIL FILTER | Oil filter |
| 1002T | 1002T Series Control Panel | Service part / kit |
| 1006TAG | LL3014F | Service part / kit |
| 1006TG2A | LL3014B | Service part / kit |
| 1103A-33G1 | LL1014S | Service part / kit |
| 1103A-33TG1 | LL2014C | Service part / kit |
| 1104A-44TG2 | LL2014L | Service part / kit |
| 12/Negative | Engine Electrical System | Service part / kit |
| 1306-E87TA300 | LL5014H | Service part / kit |
| 1306-E87TA330 | LL5014J | Service part / kit |
| DCP-10 | Control Panel | Service part / kit |
| IP23 | Enclosure rating | Service part / kit |
| R250 | AVR Model | Service part / kit |
| SD80 | Silencer | Service part / kit |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
Filters for this engine
- Air filter: Perkins 901047 Donaldson P772579 Wix 46652 Baldwin PA1608
Cross-referenced via Donaldson + OEM/engine-maker interchange — options to verify against your serial number, not confirmed for every exact variant.
Also used in
2- Fg Wilson XP 44 E3 — Generator Set
- Fg Wilson XP 65 E3 — Generator Set
Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.
Common questions
What is the displacement of the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd)?
The Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) has a displacement of 3.3 liters with 3 cylinders.
Which generators use the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine?
The Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) powers 4 generator set(s), including Atlas Copco QAS 30 Pd, Atlas Copco QAS 45 Pd, Atlas Copco QAS 60 Pd, Atlas Copco Qc3001.
What air filter does the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) use?
The Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) uses air filter part numbers Perkins 901047, Donaldson P772579, Wix 46652.
How often should you change the oil in the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd)?
The Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) oil change interval is every 500 hours.
What is a common problem with the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine?
A commonly reported issue on generators using the Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) is: The starter motor turns the engine too slowly. Cause: Battery capacity too low. Bad electrical connection. Fault in starter motor. Wrong grade of lubricating oil..