Atlas Copco — Before starting

Operation · Generator

From a Atlas Copco operator's manual covering: 1103A-33TG1, 1103A-33TG2, QAS 30 Pd, QAS 45 Pd, QAS 60 Pd, Qc1001, Qc3001. Check it applies to your exact model before use.

Applies to: Perkins 1103A-33TG1, Perkins 1103A-33TG2, Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine

Procedure

  1. With generator level, check engine oil level; must be near but not exceed high mark on dipstick.
  2. Check coolant level in expansion tank; must be near the FULL mark.
  3. Drain coolant and sediment from fuel pre-filter; check fuel level and top up.
  4. Check vacuum indicator of air filter; replace element if red part shows completely.
  5. Press the vacuator valve of the air filter to remove dust.
  6. Check generator for leakage and tightness of wire terminals; correct if necessary.
  7. Check that fuse F4 is not activated and emergency stop is in the OUT position.
  8. Check that the load is switched off.
  9. Check that circuit breaker Q1 is switched off.
  10. Check that the earth fault protection (N13) has not tripped (reset if necessary).

Full service-parts list: Perkins 1103A-33TG1 →, Perkins 1103A-33TG2 →, Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine →

Source: Atlas Copco operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.