Atlas Copco — Starting Qc1001 locally
Operation · Qc1001 control panel
From a Atlas Copco operator's manual covering: 1103A-33TG1, 1103A-33TG2, QAS 30 Pd, QAS 45 Pd, QAS 60 Pd, Qc1001, Qc3001. Check it applies to your exact model before use.
Applies to: Perkins 1103A-33TG1, Perkins 1103A-33TG2, Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine
Procedure
- Switch on the battery switch.
- Switch off circuit breaker Q1 (not needed when a plant contactor is installed between Q1 and the load).
- Put the starter switch in start position; the unit starts a preheating cycle which takes 12 seconds.
- After the preheating period the unit will start; the starting attempt takes maximum 12 seconds.
- Switch on circuit breaker Q1 in case no contactor is installed.
Specs & values
- Preheating cycle 12 seconds
- Starting attempt maximum 12 seconds
Full service-parts list: Perkins 1103A-33TG1 →, Perkins 1103A-33TG2 →, Perkins 1103A-33G2 (QAS 30 Pd); 1103A-33TG1 (QAS 45 Pd); 1103A-33TG2 (QAS 60 Pd) engine →
Source: Atlas Copco operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.