Service parts for the 5EFKOD
Grouped by system, with how many of each the parts manual calls for.
Fuel system
1 requiredOil system
1 requiredBelts
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 5 kW |
| Prime power | 5 kW |
| Emissions | Tier III |
| Controller | ADC IId, Advanced Digital IId, Advanced Digital IId (ADC IId), Decision-Maker 3500 |
| Oil capacity | 2.5 L |
| Alternator | Fast-Response X (Class Class H insulation) |
| Voltage options | 115/230 V, 230 V, 240 V |
| Phase | 1 |
| Rated current | 43.4 A |
| Battery cranking | 650 CCA |
| Battery voltage | 12 V |
| Coolant capacity | 3 L |
| Dimensions (L×W×H) | 780×528×559 mm |
| Dry weight | 222 kg |
| Wet weight | 185 kg |
Maintenance & consumables
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Fuel filter | Fuel Filter Element | ED0021752880-S | Amazon eBay $49.95 KuduParts $14.00 FridayParts $16.25 | ||
| Oil filter | Oil Filter | ED0021752850-S | Amazon eBay $24.95 NAPA $15.26 | ||
| Belt | GM77898 | Amazon eBay |
Service intervals
32| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Crankcase oil | Change | 250 hr | 3 mo | First service — Replace the oil in the crankcase. Break-in period service indicated. |
| Fuel/water separator | Clean | 250 hr | 3 mo | Fuel/water separator cleaning. |
| Fuel/water separator | Drain | 250 hr | 3 mo | Fuel/water separator draining. Consult local distributor/dealer for service. |
| Lube oil filter element | Replace | 250 hr | 3 mo | First service — Replace the lube oil filter element. Break-in period service indicated. |
| Seawater pump belt tension | Adjust | 250 hr | 3 mo | First service — Check/adjust the seawater pump belt tension. Break-in period service indicated. |
| Battery cables | Clean | 500 hr | 6 mo | Clean the battery cables. |
| Coolant hoses | Inspect | 500 hr | 6 mo | Check the coolant hoses. |
| Electrical connections | Check | 500 hr | 6 mo | Check and tighten the electrical connections. |
| Fuel filter | Replace | 500 hr | 6 mo | Replace the fuel filter element. |
| Generator | Clean | 500 hr | 6 mo | Blow dust out of the generator. |
| Heat exchanger anticorrosion zinc anode (if equipped) | Check | 500 hr | 6 mo | Check the zinc anode. |
| Mounting bolts/vibromounts | Check | 500 hr | 6 mo | Check the mounting bolts/vibromounts and tighten if necessary. |
| Seawater pump impeller | Inspect | 500 hr | 6 mo | Check the seawater pump impeller. |
| Siphon break (if equipped) | Check | 500 hr | 6 mo | Check the function of the siphon break, if equipped. |
| Breather pipe | Check | 1000 hr | 12 mo | Check the breather pipe for obstructions. |
| Coolant | Replace | 1000 hr | 12 mo | Replace the coolant. |
| Coolant hoses | Replace | 1000 hr | 12 mo | Replace the coolant hoses. |
| Exhaust/water mixing elbow | Clean | 1000 hr | 12 mo | Clean the exhaust/water mixing elbow. |
| Fuel injection nozzle pressure | Test | 1000 hr | 12 mo | Inspect the fuel injection nozzle pressure (Engine S/M). |
| Fuel injectors | Test | 1000 hr | 12 mo | Inspect, clean, and test the fuel injectors (Engine S/M). |
| Fuel tank sediment / fuel tank | Drain | 1000 hr | 12 mo | Remove the sediment from the fuel tank and drain the fuel tank. |
| Heat exchanger anticorrosion zinc anode (if equipped) | Replace | 1000 hr | 12 mo | Replace the zinc anode. |
| Heat exchanger tube | Clean | 1000 hr | 12 mo | Clean the heat exchanger tube (Generator S/M). |
| Intake/exhaust valve clearance | Adjust | 1000 hr | 12 mo | Adjust the intake/exhaust valve clearance (Engine S/M). |
| Seawater pump impeller | Replace | 1000 hr | 12 mo | Replace the seawater pump impeller. |
| Slip rings and brushes (6EKOD/5EFKOD models) | Clean | 1000 hr | 12 mo | 6EKOD/5EFKOD Models: Clean the slip rings and inspect the brushes (Generator S/M). |
| Crankcase breather system | Inspect | 1500 hr | Inspect the crankcase breather system (Engine S/M). | |
| Timing belt | Replace | 4000 hr | Replace the timing belt (Engine S/M). | |
| Starter motor | Check | 5000 hr | Check the starter motor. | |
| Engine | Other | 10000 hr | Total engine overhaul (Engine S/M). | |
| Complete exhaust system | Inspect | 12 mo | Inspect the complete exhaust system. | |
| Remote start panel (if equipped) | Check | First service — Check the remote start panel operation. Break-in period service indicated. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
32| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Anticorrosion zinc anode dimensions | 10 (0.39) x 17 (0.67) | mm (in.) | diameter x length |
| Gap | Seawater pump belt deflection | 10 | mm (0.4 in.) | pressing with approx. 10 kg (22 lbs.) force at midpoint of longest span; recheck new belt after 10 minutes of operation |
| Other | Anticorrosion zinc anode replacement threshold | <50 | % of length/diameter | replace when percent of zinc remaining is below 50% |
| Pressure | Crank oil pressure (locked rotor) | 69 | kPa | locked rotor condition |
| Pressure | Low oil pressure shutdown trip point | 117 | kPa | at or below |
| Pressure | Low oil pressure warning trip point | 138 | kPa | at or below |
| Speed | Engine over speed shutdown trip point | 115 | % of rated speed | engine speed exceeds |
| Speed | Engine under speed shutdown trip point | 85 | % of rated speed | engine speed falls below |
| Speed | Overfrequency default setting | 110 | % of nominal | setting range 102%-140% of nominal; time delay 10 sec |
| Speed | Underfrequency default setting | 90 | % of nominal | inhibit time 10 sec; delay time 5 sec |
| Temperature | Coolant freeze protection (50% ethylene glycol) | -37 | °C (-34 °F) | 50% ethylene glycol solution |
| Temperature | Coolant overheating protection (50% ethylene glycol) | 129 | °C (265 °F) | 50% ethylene glycol solution |
| Temperature | High coolant temperature shutdown trip point | 110 | °C (230 °F) | trip point |
| Temperature | High coolant temperature warning trip point | 105 | °C (221 °F) | trip point |
| Torque | Hex head bolt 1/2-13 (Grade 5) | 103 | Nm | assembled into cast iron or steel |
| Torque | Hex head bolt 1/4-20 (Grade 5) | 11.6 | Nm | assembled into cast iron or steel |
| Torque | Hex head bolt 3/8-16 (Grade 5) | 42 | Nm | assembled into cast iron or steel |
| Torque | Hex head bolt 5/16-18 (Grade 5) | 24.0 | Nm | assembled into cast iron or steel |
| Torque | Hex head bolt 7/16-14 (Grade 5) | 68 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M10 (Grade 10.9) | 70 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M10 (Grade 8.8) | 50 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M12 (Grade 10.9) | 123 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M12 (Grade 8.8) | 87 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M6 (Grade 10.9) | 14.7 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M6 (Grade 8.8) | 10.4 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M8 (Grade 10.9) | 36 | Nm | assembled into cast iron or steel |
| Torque | Metric bolt M8 (Grade 8.8) | 25 | Nm | assembled into cast iron or steel |
| Voltage | High battery voltage default setting (12 V system) | 15 | V | range 13.2-16.2 |
| Voltage | Low battery voltage default setting (12 V system) | 12 | V | range 9.6-12.6 |
| Voltage | Overvoltage default setting | 120 | % of nominal | inhibit time 10 sec; delay time 2 sec |
| Voltage | Undervoltage default setting | 80 | % of nominal at 10 sec | inhibit time 10 sec; delay time 10 sec |
| Voltage | Voltage adjust range | ±10 | % of system voltage | upper limit +10%, lower limit -10% |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | 50% ethylene glycol and 50% clean, softened water | above -37°C | Provides freezing protection to -37 °C (-34 °F) and overheating protection to 129 °C (265 °F). Coolant capacities (including 0.24 L (8 oz.) recovery tank): 6EKOD/5EFKOD 3.0 L (3.2 Qts.); 9EKOZD/7EFKOZD 3.0 L (3.2 Qts.); 11EKOZD/9EFKOZD (1 Phase) 4.3 L (4.5 Qts.); 11EKOZD/9EFKOZD (3 Phase) 4.3 L (4.5 Qts.). Do not use alcohol or methanol antifreeze. | ||
| Engine oil | API classification CD or CF | See SAE viscosity selection chart (SAE 20W, 30, 40 mineral base; SAE 10W-30, 10W-40, 10W-60, 15W-40, 20W-60 semi-synthetic base; SAE 5W-30, 0W-30, 10W, 5W-40 synthetic base) | Oil capacities: 6EKOD and 5EFKOD 2.5 L (2.6 Qts.); 9EKOZD and 7EFKOZD 2.5 L (2.6 Qts.); 11EKOZD and 9EFKOZD (1 Phase) 3.4 L (3.6 Qts.); 11EKOZD and 9EFKOZD (3 Phase) 3.4 L (3.6 Qts.). Maintain level between Min and Max marks on dipstick. | ||
| Fuel | Diesel fuel oil | Cetane number minimum 51; viscosity 2.0/4.5 centistokes at 40 °C; density 0.835/0.855 kg/litre; distillation 85% at 350; sulphur maximum 0.05% of weight | Fuel with low sulphur content: API CF4, CG4. Fuel with high sulphur content: API CF, CD, CE. Never store diesel fuel in galvanized containers. Avoid storing fuel for more than one month. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
30| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| AC Sens Loss Low Shutdwn | AC Sensing Loss (Shutdown) | Loss of AC voltage shutdown occurs when the controller does not detect the nominal generator AC output voltage for more than 3 seconds after crank disconnect. | Shutdown | Contact an authorized distributor/dealer for service. |
| AC Sens Loss Warning | AC Sensing Loss Warning | Loss of AC voltage warning occurs when the controller does not detect the nominal generator set AC output voltage after crank disconnect. | Warning | Contact an authorized distributor/dealer for service. |
| Aux Input Shutdwn | Auxiliary Input Shutdown | Auxiliary fault input shutdown; input from a customer-supplied switch that closes when the fault is active. | Shutdown | Check the cause of the auxiliary fault. |
| Backup Pars Status | Backup Parameters Loaded | Backup parameter firmware is now loaded on the controller. | Info | |
| Battery High Warning | High Battery Voltage Warning | High battery voltage warning; the fault condition clears when the battery voltage returns within limits (above 125% of nominal 12 V). | Warning | Check the battery rating and condition. |
| Battery Low Warning | Low Battery Voltage Warning | Low battery voltage warning; the fault condition clears when the battery voltage returns within limits (at or below 100% of nominal 12 V). | Warning | Check the battery rating and condition. Charge or replace the battery. |
| Coolnt Temp High Shutdwn | High Coolant Temperature Shutdown | Occurs if the engine coolant temperature exceeds the default setting (at or above 110 °C / 230 °F). | Shutdown | Check for a low engine coolant level. Check seawater pump impeller, strainers, and seacock. |
| Coolnt Temp High Warning | High Coolant Temperature Warning | High coolant temperature warning (at or above 105 °C / 221 °F). | Warning | Check for a low engine coolant level. Check seawater system for reduced flow. Allow the generator set to cool down before checking. |
| Eng Speed High Shutdwn | Engine Over Speed Shutdown | Occurs if the engine speed exceeds the default setting (above 115% of rated speed). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Eng Speed Low Shutdwn | Engine Under Speed Shutdown | Occurs if the engine speed falls below the default setting (below 85% of rated speed). | Shutdown | Contact an authorized distributor/dealer for service. |
| Engine Start Status | Engine Started | Generator set start circuit is closed allowing the engine to crank and run. | Info | |
| Engine Stop Status | Engine Stopped | Generator set start circuit is open causing the engine to shut down. | Info | |
| Exh Temp High Shutdwn | High Exhaust Temperature Shutdown | Occurs if the engine exhaust temperature exceeds the default setting. | Shutdown | Check the wiring to the sensor. Check for a clogged seawater intake or sea strainer. Check for a damaged seawater pump impeller. Check the exhaust system. |
| Frequency High Shutdwn | Overfrequency Shutdown | Occurs when the governed frequency exceeds the default setting of the system's frequency setpoint (above 110% of nominal). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Frequency Low Shutdwn | Underfrequency Shutdown | Occurs when the governed frequency falls below the default setting of the system's frequency setpoint (below 90% of nominal). | Shutdown | Reduce the load and restart the generator set. Contact an authorized distributor/dealer if problem continues. |
| Gen Running Notice | Generator Running | Generator set has started and is running. | Info | |
| Lo Crank Vlt Warning | Low Cranking Voltage Warning | Low cranking voltage warning (battery voltage drops below 60% of nominal 12 V). | Warning | Check the battery rating and condition. Charge or replace the battery. |
| Locked Rotor Shutdwn | Locked Rotor (Overcrank) Shutdown | Overcrank (locked rotor) shutdown; engine speed below 10 rpm and oil pressure below crank oil pressure (69 kPa). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Oil Pres Low Shutdwn | Low Oil Pressure Shutdown | Occurs if a low oil pressure condition exists (at or below 117 kPa). Note: does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| Oil Pres Low Warning | Low Oil Pressure Warning | Low engine oil pressure warning (at or below 138 kPa). | Warning | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| Over Crank Shutdwn | Overcrank Shutdown | Occurs after 3 unsuccessful starting attempts. | Shutdown | Check the fuel supply and battery. Also check for loose connections. Contact an authorized distributor/dealer if problem continues. |
| Preheat | Engine Start Aid Active | Start aid is active and will energize an engine equipped preheat or ether system during the crank cycle. | Info | |
| Remote Start Status | Remote Start | Generator set start circuit was closed from a remote location allowing the engine to crank and run. | Info | |
| RunRelCoil Shutdwn | Run Relay Coil Shutdown | Overload or perceived overload on the DC circuits provided through the controller (70 Run, 71 Crank, FP/FN Flash). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Sea Pressure Low Shutdwn | Low Seawater Pressure Shutdown | Occurs after a loss of seawater pressure is detected (5 seconds after detection). | Shutdown | Check for a clogged seawater intake or sea strainer. Check for a damaged seawater pump impeller. |
| Start Delay Notice | Engine Start Delay Active | The delay for engine start is active; the unit will start cranking after the time delay times out. | Info | |
| System Ready Status | System Ready | Generator set is in the AUTO mode and available to start if the start circuit is closed. | Info | |
| Timer Error Notice | System Timer Failed | Controller timer logic has failed to time out a designated function. | Info | |
| Volts xx-xx High Shutdwn | Overvoltage Shutdown | Occurs if the voltage exceeds the default setting of the voltage regulator setpoint (exceeds 120% of the AC system voltage). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| Volts xx-xx Low Shutdwn | Undervoltage Shutdown | Occurs if the voltage falls below the default setting of the voltage regulator setpoint (below 80% of the AC system voltage). | Shutdown | Reduce the load and restart the generator set. Check the F1 fuse. Contact an authorized distributor/dealer if problem continues. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Calibration Procedure (RDC/DC) adjustment
⚠ Observe the safety precautions in the generator set installation manual.
Tools: Digital voltmeter
- Measure the actual utility voltage across L1 and L2 using a digital voltmeter.
- Click on Calibrate in the ribbon at the top of the SiteTech screen.
- Type the measured voltage into the Device Calibration window.
- Click the Calibrate button in the Device Calibration window.
- View the utility voltage in the Source 1 metering group (Voltage L1-L2 and average line-to-line).
Procedure to Assign Configurable I/O (APM603) adjustment
⚠ If a mistake is entered, click Back or Cancel, or click Delete Last Row and start over.
- Click on Configurable I/O near the top of the SiteTech screen.
- Click on + New Row near the bottom of the screen.
- In the output box, click on Add Output.
- Select Control Digital Output.
- From Relay K1 through Relay K14, select the relay connected to the output and click Finished.
- In the Function box, click Setup Function and choose Assign, And, Or, TOn, TOff, or Tp; click Finished.
- In the Input(s) box, select Set up Inputs and choose a digital input or event to activate the output relay.
- When asked Apply negation to input?, select No to trigger when active, Yes to trigger when NOT active.
- If more than one signal is assigned, click Add Another Input and repeat for each input; click Finished.
- Repeat the process for each connected relay output on the four input/fifteen output module.
Seawater Pump Belt Tensioning Procedure adjustment
⚠ Hazardous voltage. Moving parts. Operate the generator set only when all guards and electrical enclosures are in place.
- Remove the belt guard.
- Check the belt tension at the midpoint of the longest span by pressing with approx. 10 kg (22 lbs.) of force.
- Recheck a new belt tension after 10 minutes of operation.
- Loosen the pivot and adjusting screws.
- While prying the seawater pump outward, tighten the adjusting screw.
- Tighten the pivot screw.
- Recheck and adjust as necessary.
- Replace the belt guard.
Étalonnage du contrôleur RDC/DC adjustment
⚠ Observer les précautions de sécurité indiquées dans le manuel d'installation de groupe électrogène.
Tools: Voltmètre numérique
- Mesurer la tension réelle du secteur au niveau de L1 et L2 avec un voltmètre numérique.
- Cliquer sur Calibrate (Étalonner) dans le ruban en haut de l'écran SiteTech.
- Tapez la tension mesurée dans la fenêtre d'étalonnage d'appareil.
- Cliquer sur le bouton Calibrate (Étalonner) dans la fenêtre d'étalonnage.
Connexion USB d'un appareil installation
⚠ Ne pas utiliser de connecteur micro-B.
Tools: Câble USB (type-B ou mini-B)
- Connecter un câble USB doté du connecteur approprié (type-B standard pour ADC IId, mini-B pour les autres appareils).
- Sélectionner No, not at this time (Non pas pour le moment) et cliquer sur Next (Suivante).
- Sélectionner Install the software automatically (Installer le logiciel automatiquement) et cliquer sur Next.
- Cliquer sur Finish (Terminer).
Download and Install the .NET Framework installation
- Click the Download button to link to the Microsoft website (Internet access required).
- Follow the onscreen instructions to download and install .NET Framework 4.0.
- Restart the computer if necessary, then start the SiteTech installation again.
Install SiteTech installation
- Click the KohlerSiteTech32BitSetup.msi or KohlerSiteTech64BitSetup.msi file to start the installation.
- Read the software license agreement, then click the checkbox to accept the terms.
- Click Install to proceed and wait as the program installs on your PC.
- Click Finish.
Installer SiteTech installation
- Lire l'écran de contrat de licence et cocher la case indiquant l'acceptation des termes.
- Cliquer sur Install (Installer) et patienter pendant l'installation.
- Cliquer sur Finish (Terminer).
Steps for common hardware application installation
⚠ Do not substitute inferior grade hardware; replacement grade should be equal to or better than the original.
- Determine entry hole type: round or slotted.
- Determine exit hole type: fixed female thread (weld nut), round, or slotted.
- For round and slotted exit holes, determine if hardware is greater than 1/2 inch in diameter, or 1/2 inch or less.
- Hardware greater than 1/2 inch in diameter takes a standard nut and SAE washer.
- Hardware 1/2 inch or less in diameter can take a properly torqued whiz nut or spiralock nut.
- Always use a washer between hardware and a slot.
- Always use a washer under a nut.
- Use a washer under a bolt when the female thread is fixed (weld nut).
USB Connection (Found New Hardware) installation
⚠ Do not use a micro-B connector.
Tools: USB cable with male USB type-A connector on PC side; male standard type-B connector for ADC IId controller; male mini-B connector for all other devices
- When the first window asks about searching for software, select No, not at this time.
- Click Next.
- When the second window asks about installing the software, select Install the software automatically.
- Click Next and wait while the software is installed.
- Click Finish.
Anticorrosion Zinc Anode Replacement maintenance
Tools: Wire brush
- With the generator set cooled, close the seacock, open the petcock on the engine, and drain the coolant.
- Remove the anticorrosion zinc anode (plug) from the heat exchanger.
- Use a wire brush to remove loose corrosion; replace the anode when <50% of length/diameter remains.
- Clean the threaded hole and coat the anode threads with pipe sealant suitable for marine applications.
- Cut the anticorrosion zinc to the correct length and install it into the heat exchanger.
- Close the petcock, open the seacock, and refill the cooling system.
- Start the generator set and check for leaks at the anticorrosion zinc anode location.
Firmware Update Procedure maintenance
⚠ Do not attempt to update firmware on RSA II remote serial annunciators with version 1.0 firmware.
⚠ The Decision-Maker 550 and 6000 controllers require Program Loader software to update firmware (see TT-1285).
Tools: USB cable, Firmware file (.bin)
- Download the new firmware file from the Service Support page, software section, on KPRC. Save it on your PC and note the file location.
- Use a USB cable to connect the device to a USB port on your PC.
- Start SiteTech (Start>Programs>Kohler SiteTech).
- Wait for the program to recognize the connected device.
- Click on Update Firmware near the top of the screen.
- Click Browse and navigate to the directory where the firmware file is stored and click Open.
- Verify the current version number, new version number, and file name; click Update Firmware.
- When the message Firmware Updated Successfully appears, click Close.
- For RDC2, DC2, or VSC with a blank display: disconnect the USB cable, disconnect the starting battery negative lead first, wait 1 minute, then reconnect the battery negative lead last.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Kohler 5EFKOD?
The Kohler 5EFKOD is rated 5 kW standby.
Is the Kohler 5EFKOD diesel or gas?
The Kohler 5EFKOD runs on diesel.
What is the cooling system capacity of the Kohler 5EFKOD?
The Kohler 5EFKOD cooling system holds 3 liters (0.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the oil capacity of the Kohler 5EFKOD?
The Kohler 5EFKOD has an engine oil capacity of 2.5 liters (2.6 US quarts), per the manufacturer specification sheet.
How much does the Kohler 5EFKOD weigh?
The Kohler 5EFKOD has a dry weight of 222 kg (489 lb).
What voltage does the Kohler 5EFKOD produce?
The Kohler 5EFKOD is offered in 115/230 V, 230 V, 240 V, 1-phase.
How many cold cranking amps does the Kohler 5EFKOD require?
The Kohler 5EFKOD uses 12 V each, 650 CCA, per the manufacturer specification sheet.
Which alternator is fitted to the Kohler 5EFKOD?
The Kohler 5EFKOD uses a Fast-Response X alternator. Insulation class Class H.
What oil filter fits the Kohler 5EFKOD?
The Kohler 5EFKOD uses oil filter part number ED0021752850-S.
What fuel filter does the Kohler 5EFKOD use?
The Kohler 5EFKOD uses fuel filter part number ED0021752880-S.
Repair guides
22- Anticorrosion Zinc Anode Replacement
- Calibration Procedure (RDC/DC)
- Changing Settings
- Controller Resetting (Following System Fault Shutdown)
- Download and Install the .NET Framework
- File Export Procedure
- File Import Procedure
- Firmware Update Procedure
- Fuel Filter Cleaning/Replacement Procedure
- Fuel System Bleed Procedure
- Fuel System Bleed Procedure (Preferred)
- Generator Set Storage Procedure
- Impeller Inspection and Replacement Procedure
- Install SiteTech
- Procedure to Assign Configurable I/O (APM603)
- Reset with Personality Profile Procedure
- Seawater Pump Belt Tensioning Procedure
- Sound Shield Roof and Door Removal
- Starting the Generator Set (Local)
- Steps for common hardware application
Step-by-step procedures compiled from the Kohler service manual for this model.
Parts
30| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 102086 | HYDRAULIC TOWER | 1 | Gasket | Amazon eBay |
| 102089 | Snap ring tongue jack | 1 | Belt | Amazon eBay |
| 229125 | V-Belt (Seawater Pump) | 1 | Belt | Amazon eBay $22.07 NAPA $17.52 FridayParts $62.70 |
| 229826 | Seawater Pump Impeller Kit | 1 | Impeller | Amazon eBay $45.71 NAPA $40.56 FridayParts $33.59 |
| ED001780 | Belt | Belt | Amazon eBay | |
| ED0017801 | Belt | Belt | Amazon eBay | |
| ED0021752850-S | Oil Filter | 1 | Oil filter | Amazon eBay $24.95 NAPA $15.26 |
| ED0021752880-S | Fuel Filter Element | 1 | Fuel filter | Amazon eBay $49.95 KuduParts $14.00 FridayParts $16.25 |
| ED002816 | Belt | Belt | Amazon eBay | |
| ED0028162 | Belt | Belt | Amazon eBay | |
| ED007051 | Belt | Belt | Amazon eBay | |
| ED0070511 | Belt | Belt | Amazon eBay | |
| ED009732 | Belt | Belt | Amazon eBay | |
| ED0097320 | Belt | Belt | Amazon eBay | |
| ED009865 | Belt | Belt | Amazon eBay | |
| ED0098653 | Belt | Belt | Amazon eBay | |
| ED009881 | Belt | Belt | Amazon eBay | |
| ED0098816 | Belt | Belt | Amazon eBay | |
| GM102086 | Gasket | Gasket | Amazon eBay | |
| GM102089 | Belt | Belt | Amazon eBay | |
| GM74543 | Gasket | Gasket | Amazon eBay | |
| GM75706 | Gasket | Gasket | Amazon eBay | |
| GM77080 | Gasket | Gasket | Amazon eBay | |
| GM77379 | Glow plug | Glow plug | Amazon eBay | |
| GM77898 | Belt | Belt | Amazon eBay | |
| 103000 | Uniball assembly | 1 | Service part / kit | Amazon eBay FridayParts $99.99 |
| 239298 | Fuse: Customer Connection (F3) 5 Amp | 1 | Service part / kit | Amazon eBay $7.74 NAPA $2632.97 |
| 358337 | Fuse: Auxiliary Winding (F1) 10 Amp | 1 | Service part / kit | Amazon eBay $45.17 NAPA $65.06 |
| ED0090802150-S | ZINC ANODE KIT | 1 | Service part / kit | Amazon eBay $60.67 |
| GM39266 | Fuse: Controller, Fuel Pump, and Fuel Shutoff Solenoid (F2) 20 Amp | 5 | Service part / kit | Amazon eBay $14.88 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 1.1 | 0.3 |
| Prime | 50% | 1.5 | 0.4 |
| Prime | 75% | 1.9 | 0.5 |
| Prime | 100% | 2.3 | 0.6 |
Available documents
This page was generated from the 18 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.