Kohler — Controller Resetting (Following System Fault Shutdown)
Repair & overhaul · Advanced Digital Control IId
From a Kohler operator's manual covering: 11EKOD, 11EKOZD, 5EFKOD, 5EFKOZD, 6EKOD, 6EKOZD, 7- 9EFKOZD, 7EFKOZD, 9- 11EKOZD, 9EFKOD, 9EFKOZD, 9EKOZD. Check it applies to your exact model before use.
Applies to: Kohler 11EKOZD, Kohler 5EFKOD, Kohler 6EKOD, Kohler 7EFKOZD, Kohler 9EFKOZD, Kohler 9EKOZD
Before you start
- Always identify and correct the cause of a fault shutdown before resetting the controller.
Procedure
- Disconnect the generator set from the load.
- Identify and correct the cause of the fault shutdown.
- Use the pushbutton/rotary selector dial to select the Overview page.
- Press the dial to view the active fault; press again and use the dial to CONFIRM CLR FAULT: YES.
- Push the pushbutton/rotary selector dial.
- Start the generator set by pressing the start/stop button to START; test operate.
- Shut the generator off by pressing the start/stop to the STOP position.
- Reconnect the generator set to the load.
Full service-parts list: Kohler 11EKOZD →, Kohler 5EFKOD →, Kohler 6EKOD →, Kohler 7EFKOZD →, Kohler 9EFKOZD →, Kohler 9EKOZD →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.