Before you start

  • Observe the safety precautions in the generator set installation manual.

Procedure

  1. Measure the actual utility voltage across L1 and L2 using a digital voltmeter.
  2. Click on Calibrate in the ribbon at the top of the SiteTech screen.
  3. Type the measured voltage into the Device Calibration window.
  4. Click the Calibrate button in the Device Calibration window.
  5. View the utility voltage in the Source 1 metering group (Voltage L1-L2 and average line-to-line).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Controller firmware version 2.04 or higher required for calibration
  • SiteTech software version 2.2 or higher required for the calibration function

Full service-parts list: Kohler 11EKOZD →, Kohler 5EFKOD →, Kohler 9EFKOZD →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.