Kohler — Procedure to Assign Configurable I/O (APM603)

Adjustments · Optional 4 input/15 output I/O module

From a Kohler service manual covering: 11EKOZD, 5EFKOD, 9EFKOZD. Check it applies to your exact model before use.

Applies to: Kohler 11EKOZD, Kohler 5EFKOD, Kohler 9EFKOZD

Before you start

  • If a mistake is entered, click Back or Cancel, or click Delete Last Row and start over.

Procedure

  1. Click on Configurable I/O near the top of the SiteTech screen.
  2. Click on + New Row near the bottom of the screen.
  3. In the output box, click on Add Output.
  4. Select Control Digital Output.
  5. From Relay K1 through Relay K14, select the relay connected to the output and click Finished.
  6. In the Function box, click Setup Function and choose Assign, And, Or, TOn, TOff, or Tp; click Finished.
  7. In the Input(s) box, select Set up Inputs and choose a digital input or event to activate the output relay.
  8. When asked Apply negation to input?, select No to trigger when active, Yes to trigger when NOT active.
  9. If more than one signal is assigned, click Add Another Input and repeat for each input; click Finished.
  10. Repeat the process for each connected relay output on the four input/fifteen output module.

Specs & values

  • Relay K15 is factory set to Common Fault and is not adjustable

Full service-parts list: Kohler 11EKOZD →, Kohler 5EFKOD →, Kohler 9EFKOZD →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.