Kohler — Procedure to Assign Configurable I/O (APM603)
Adjustments · Optional 4 input/15 output I/O module
From a Kohler service manual covering: 11EKOZD, 5EFKOD, 9EFKOZD. Check it applies to your exact model before use.
Applies to: Kohler 11EKOZD, Kohler 5EFKOD, Kohler 9EFKOZD
Before you start
- If a mistake is entered, click Back or Cancel, or click Delete Last Row and start over.
Procedure
- Click on Configurable I/O near the top of the SiteTech screen.
- Click on + New Row near the bottom of the screen.
- In the output box, click on Add Output.
- Select Control Digital Output.
- From Relay K1 through Relay K14, select the relay connected to the output and click Finished.
- In the Function box, click Setup Function and choose Assign, And, Or, TOn, TOff, or Tp; click Finished.
- In the Input(s) box, select Set up Inputs and choose a digital input or event to activate the output relay.
- When asked Apply negation to input?, select No to trigger when active, Yes to trigger when NOT active.
- If more than one signal is assigned, click Add Another Input and repeat for each input; click Finished.
- Repeat the process for each connected relay output on the four input/fifteen output module.
Specs & values
- Relay K15 is factory set to Common Fault and is not adjustable
Full service-parts list: Kohler 11EKOZD →, Kohler 5EFKOD →, Kohler 9EFKOZD →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.