Specifications
Ratings spec sheet not in our library yet — see the documents below.
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Limpiar con un cepillo suave o una aspiradora; si está dañado o es difícil de limpiar, solicitar filtro de repuesto | — |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Service intervals
11| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Enclosure exterior | Clean | 12 mo | Clean with a soft cloth. | |
| Filtro de entrada (A) | Clean | 12 mo | Con un cepillo suave o una aspiradora | |
| Gabinete (exterior) | Clean | 12 mo | Limpie el exterior del gabinete con un paño suave | |
| Intake and exhaust vents | Inspect | 12 mo | Verify vents are clear at all times. | |
| Intake filter | Clean | 12 mo | Annual maintenance. | |
| Surrounding area | Inspect | 12 mo | Ensure area free of leaves, pet hair, or other debris that could obstruct airflow. | |
| Unidad (condiciones de rendimiento y seguridad) | Inspect | 12 mo | Busque ventilaciones obstruidas, filtro sucio, piezas metálicas sueltas o faltantes y conexiones eléctricas sueltas o interrumpidas | |
| Unit | Inspect | 12 mo | Look for blocked vents, dirty intake filter, loose/missing hardware, loose or broken electrical connections. | |
| Ventilación de entrada (A) | Inspect | 12 mo | Verifique que esté despejada en todo momento | |
| Ventilación de escape (B) | Inspect | 12 mo | Verifique que esté despejada en todo momento | |
| Área circundante | Clean | 12 mo | Asegúrese de que no haya hojas, pelo de mascotas u otros residuos que obstruyan el flujo de aire |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
45| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Backup loads disconnect | 50 | A Circuit Breaker | |
| Other | Corriente de REbus | 30 | A, CC | |
| Other | Corriente de cortocircuito de entrada de REbus | 30 | A, CC | |
| Other | Corriente de salida continua de CA, en modo Isla | 45 | A, rms | |
| Other | Corriente de salida continua de CA, inyección directa | 32 | A, rms | |
| Other | Corriente pico de arranque del motor (2 s) | 50 | A, rms | 2 segundos |
| Other | DC bus export fuses (+/-) | 40 | A | |
| Other | DC distribution input breakers | 4 x 2-Pole 30 | A | |
| Other | Dimensions L x W x H | 24.5 x 19.25 x 8 | in (622.3 x 488.9 x 203.2 mm) | |
| Other | Max input current per DC input | 24 | A | |
| Other | Maximum continuous output current | 32 | A, RMS | |
| Other | Peak motor starting current | 50 | A, RMS | 2 sec |
| Other | Weight | 62.7 | lb (28.4 kg) | |
| Speed | Frecuencia de salida normal de CA | 60 | Hz | |
| Speed | OF1 trip frequency (UL 1741-SB / IEEE 1547-2018) | 61.2 | Hz | clearing time 300 s |
| Speed | OF2 trip frequency (UL 1741-SB / IEEE 1547-2018) | 62 | Hz | clearing time 0.16 s |
| Speed | UF1 trip frequency (UL 1741-SB / IEEE 1547-2018) | 58.5 | Hz | clearing time 300 s |
| Speed | UF2 trip frequency (UL 1741-SB / IEEE 1547-2018) | 56.5 | Hz | clearing time 0.16 s |
| Temperature | Operating temperature | -4 to 122 | °F (-20 to 50 °C) | |
| Temperature | Rango de temperatura ambiente de funcionamiento a potencia plena | -20 a +50 | °C (-4 a +122 °F) | |
| Torque | AC wiring terminals, 8 to 6 AWG | 13.3 in-lb to 15.9 in-lb (1.5 Nm to 1.8 Nm) | in-lb | Terminal temp range up to 248 degF (120 degC); wire min temp rating 194 degF (90 degC) |
| Torque | DC wiring terminals, 10 to 6 AWG | 12 in-lb (1.35 Nm) | in-lb | Terminal temp range -40 to 266 degF (-40 to 130 degC); wire min temp rating 194 degF (90 degC) |
| Torque | Grounding bar terminals, 10 AWG wire | 30 in-lb (4 Nm) | in-lb | |
| Torque | Grounding bar terminals, 4-6 AWG wire | 45 in-lb (5 Nm) | in-lb | |
| Torque | Grounding bar terminals, 8 AWG wire | 40 in-lb (4.5 Nm) | in-lb | |
| Torque | Terminales de cableado de CA, 8 a 6 AWG | 1.5 a 1.8 | Nm (13,3 lb-pulg. a 15,9 lb-pulg.) | Rango de temperatura del terminal hasta 120 °C (248 °F); clasificación mínima del hilo 90 °C (194 °F) |
| Torque | Terminales de cableado de CC, 10 a 6 AWG | 1.35 | Nm (12 lb-pulg.) | Rango de temperatura del terminal -40 a 130 °C (-40 a 266 °F); clasificación mínima del hilo 90 °C (194 °F) |
| Torque | Terminales de la barra de conexión a tierra, 10 AWG | 4 | Nm (30 lb-pulg.) | |
| Torque | Terminales de la barra de conexión a tierra, 4 a 6 AWG | 5 | Nm (45 lb-pulg.) | |
| Torque | Terminales de la barra de conexión a tierra, 8 AWG | 4.5 | Nm (40 lb-pulg.) | |
| Voltage | AC frequency | 60 | Hz | |
| Voltage | AC output voltage | 120/240 | VAC, 1Ø | |
| Voltage | DC input voltage range | 360-420 | VDC | |
| Voltage | Nominal DC bus voltage | 380 | VDC | |
| Voltage | OV1 trip voltage (UL 1741-SB / IEEE 1547-2018) | 110 | % of nominal | clearing time 13 s |
| Voltage | OV2 trip voltage (UL 1741-SB / IEEE 1547-2018) | 120 | % of nominal | clearing time 0.16 s |
| Voltage | Rango de voltaje de funcionamiento de CA (L-L) | 212 - 264 | V, rms | nominal 240 |
| Voltage | Rango de voltaje de funcionamiento de CA (L-N) | 106 - 132 | V, rms | nominal 120 |
| Voltage | Reconexión / entrada de servicio (UL 1741 SA, IEEE 1547-2003) L-L | 228.0 - 252.0 | V, RMS | perfil de red UL 1741 SA |
| Voltage | Reconexión / entrada de servicio (UL 1741 SA, IEEE 1547-2003) L-N | 114.0 - 126.0 | V, RMS | perfil de red UL 1741 SA |
| Voltage | Reconexión / entrada de servicio (UL 1741 SB, IEEE 1547-2018) L-L | 220.0 - 252.0 | V, RMS | perfil de red UL 1741 SB |
| Voltage | Reconexión / entrada de servicio (UL 1741 SB, IEEE 1547-2018) L-N | 110.0 - 126.0 | V, RMS | perfil de red UL 1741 SB |
| Voltage | UV1 trip voltage (UL 1741-SB / IEEE 1547-2018) | 88 | % of nominal | clearing time 21 s |
| Voltage | UV2 trip voltage (UL 1741-SB / IEEE 1547-2018) | 50 | % of nominal | clearing time 2 s |
| Voltage | Voltaje de REbus | 360 / 380 / 420 | V CC | mínimo / nominal / máximo |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
35| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 0X770A | Configuration Error Code A | The PWRcell Inverter is configured for 3-phase applications. AC-Coupled PV and AC Generator Integration are only supported with 1-phase applications. | Install a single-phase inverter if the application is for a single phase service. Otherwise set 'ACPVPower' and 'ACGenPower' to '0'. | |
| 0X770B | Configuration Error Code B | The PWRcell Inverter is configured for 1 or more ATS but is not configured for islanding. | If 1 or more ATS is installed, set 'EnaIslanding' to 'on'. If no ATS is installed, set 'NumTranSwtchs' to '0'. | |
| 0X770C | Configuration Error Code C | The PWRcell Inverter is configured for 1 or more ATS but is also configured for 3-phase applications. | Install a single-phase PWRcell Inverter if the application is for a single-phase service. Otherwise ensure 'NumTranSwtchs' is set to '0'. | |
| 0X770D | Configuration Error Code D | Bad input phase angle. Phase angle has been detected to be 120 degrees or less. For single-phase services, this should be 180 degrees. | Check voltage measurement and make sure the system is wired up correctly to a 120/240 Vac single-phase (Wye) service. | |
| 0x806A | ct cal = A | Line 2 has multiple CTs on it (or a CT is on the neutral wire) | ||
| 0x806B | ct cal = B | Lines 1 and 2 have multiple or missing CTs on them (or a CT is on the neutral wire) | ||
| 0x806C | ct cal = C | Line 3 has multiple CTs on it (or a CT is on the neutral wire) | ||
| 0x806D | ct cal = D | Lines 1 & 3 have multiple or missing CTs on them (or a CT is on the neutral wire) | ||
| 0x806E | ct cal = E | Lines 2 & 3 have multiple or missing CTs on them (or a CT is on the neutral wire) | ||
| 0x806F | ct cal = F | Lines 1 & 2 & 3 have multiple or missing CTs on them (or a CT is on the neutral wire) | ||
| 0X7700 | Configuration Error Code 0 | AC-Coupled PV is not supported on this inverter hardware version. Newer hardware is needed. | Replace Inverter with an XVT model Inverter (Hardware version 1010 or later) to configure the PWRcell system for AC-Coupled PV. | |
| 0X7701 | Configuration Error Code 1 | The PWRcell Inverter is not configured for islanding. This is required for AC-Coupled PV. | Use the Inverter Mod. Settings to set 'EnaIslanding' to 'on'. | |
| 0X7702 | Configuration Error Code 2 | The PWRcell Inverter is configured for an incorrect number of ATSes. For AC-Coupled PV, 1 ATS should be used. | Verify that only 1 ATS is installed. Use the Inverter 'Mod. Settings' to set 'NumTranSwtchs' to '1'. | |
| 0X7703 | Configuration Error Code 3 | AC Generator integration is not supported on this inverter hardware version. Newer hardware is needed. | Replace Inverter with an XVT model Inverter (Hardware version 1010 or later). | |
| 0X7704 | Configuration Error Code 4 | The PWRcell Inverter is not configured for islanding. This is required for AC Generator Integration. | Use the Inverter 'Mod. Settings' to set 'EnaIslanding' to 'on'. | |
| 0X7705 | Configuration Error Code 5 | The PWRcell Inverter is configured for an incorrect number of ATSes. For AC Generator Integration, 1 or 2 ATSes should be used. | Verify the number of ATSes installed. Use the Inverter Mod. Settings to set 'NumTranSwtchs' to '1' or '2'. | |
| 0X7706 | Configuration Error Code 6 | The PWRcell Inverter is configured for 2 ATSs, but 'ACGenPower' is set to '0'. | Use the Inverter 'Mod. Settings' to set 'ACGenPower' to the correct value based on the nameplate power rating of the integrated generator. | |
| 0X7707 | Configuration Error Code 7 | The PWRcell Inverter is configured for AC Generator Integration, but the installed PWRcell ATS(s) do not have the correct controller. | Use the PWRcell ATS Controller Upgrade Kit (Model G0080060). | |
| 0X7708 | Configuration Error Code 8 | 'ACGenPower' setting is not configured between 9 kW and 26 kW for AC generator integration. | Adjust the value of 'ACGenPower' in 'Mod. Settings' to match the AC generator nameplate power value. Must be at least 9 kW. | |
| 0X7709 | Configuration Error Code 9 | The PWRcell Inverter is configured for both AC-Coupled PV and AC Generator Integration. Only one of these features can be supported on a single system. | If supporting AC Coupled PV, set 'ACGenPower' to '0'. If supporting AC Generator Integration, set 'ACPVPower' to '0'. | |
| 0X7720 | Wiring Error Code 0 | The PWRcell Inverter is configured for AC Generator Integration but no ATS has been detected. | Check the ATS & CTs Cat 5 cables are intact and connected to the correct ports. Check the ATS limit switch is connected to the 'Auxiliary Contact' port. | |
| 0X7721 | Wiring Error Code 1 | The PWRcell Inverter is NOT configured for an ATS, but an ATS has been detected. | Verify the number of ATSes installed. Use the Inverter 'Mod. Settings' to set 'NumTranSwtchs' to '1' or '2'. | |
| 0X7722 | Wiring Error Code 2 | The Line 1 and Line 2 wires are swapped somewhere between the 'N' terminals of the PWRcell ATS and the Protected Loads terminals of the inverter. | Check that phase wiring does not cross over or change along each respective path from N1, N2 to L1, L2. | |
| 0X7724 | Wiring Error Code 4 | The Line 1 and Line 2 wires are swapped somewhere between the 'E' terminals of the PWRcell ATS and the Protected Loads terminals of the inverter. | Check that phase wiring does not cross over or change along each respective path from E1, E2 to L1, L2. | |
| 0X7726 | Wiring Error Code 6 | The inverter ATS did not transfer back to the utility/grid-connected position (UP position). | Verify wiring to the 'N' terminals of the inverter ATS is correct. Verify the Cat 5 cable for Inverter ATS Control is terminated properly. Verify factory wiring at the transfer mechanism closing coils and relays. | |
| 0X7727 | Wiring Error Code 7 | The inverter ATS did not transfer to the backup power source position (DOWN position). | Verify wiring to the 'E' terminals of the inverter ATS is correct. Verify the Cat 5 cable for Inverter ATS Control is terminated properly. Verify wiring to the inverter AC Grid Connection terminals. | |
| 0x8061 | ct cal = 1 | Line 1 doesn't have a valid CT calibration | ||
| 0x8062 | ct cal = 2 | Line 2 doesn't have a valid CT calibration | ||
| 0x8063 | ct cal = 3 | Line 1 & 2 don't have a valid CT calibration | ||
| 0x8064 | ct cal = 4 | Line 3 doesn't have a valid CT calibration | ||
| 0x8065 | ct cal = 5 | Line 1 & 3 don't have a valid CT calibration | ||
| 0x8066 | ct cal = 6 | Line 2 & 3 don't have a valid CT calibration | ||
| 0x8067 | ct cal = 7 | Line 1 & 2 & 3 don't have a valid CT calibration | ||
| 0x8069 | ct cal = 9 | Line 1 has multiple CTs on it (or a CT is on the neutral wire) | ||
| 0x8070 | ct cal success | Calibration was successful | Info |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Calibración de transformadores de corriente (CT) adjustment
⚠ Solo conecte CT aprobados por Generac.
- Instale los CT antes de encender el inversor; el inversor los detecta automáticamente al encenderse.
- Confirme que CT1 esté conectado a la Línea 1 y CT2 a la Línea 2, todos orientados en la misma dirección.
- Navegue a la página de dispositivo del inversor, acceda al menú y seleccione Calibrate CTs.
- Verifique que la pantalla LCD muestre “ct cal success”; si muestra “ct cal = X” consulte la tabla de solución de problemas.
Cableado de los terminales de DETENCIÓN (instalación solo fotovoltaica) installation
⚠ Si la instalación incluye batería PWRcell, sus terminales de DETENCIÓN deben conectarse en serie o en paralelo a los del inversor.
- Verifique que el sistema PWRcell esté apagado.
- Retire el puente de los terminales de DETENCIÓN del inversor.
- Use un cable de dos conductores de calibre 20 a 14 AWG con aislamiento clasificado para 600 V.
- Conecte un interruptor con bloqueo, certificado por UL, con clasificación de al menos 12 V CC, 5 mA.
- Coloque el interruptor en la posición OFF; la pantalla mostrará “Shutdown Initiated”.
Configuring Static IP Settings installation
Tools: Smartphone or laptop
- From the REbus Beacon device page on the inverter screen, select the Installer Tool.
- After logging into the Installer Configuration Tool, select 'Beacon' from the menu.
- Select 'Simple IP Network Settings'.
- Adjust Name, Config, Address, Netmask, Gateway, DNS1, DNS2, MAC as needed.
- Press Submit to commit settings.
Descripción general de la puesta en servicio installation
⚠ Si se instalan varios inversores PWRcell, no encienda la alimentación de CA a más de un inversor a la vez.
- Encienda la alimentación de CA al inversor.
- Compruebe los voltajes de CA.
- Verifique la conexión a Internet.
- Registre el sistema.
- Seleccione el modo de sistema inversor.
- Configure los ajustes del inversor y active el inversor.
- Configure los dispositivos REbus y actívelos.
- Pruebe el modo Isla.
Montaje del inversor installation
⚠ Monte el inversor en una superficie resistente y estable; nunca en paneles de yeso, enlucido u otros tratamientos no estructurales.
- Verifique que la ubicación de montaje cumpla todos los requisitos de la Sección 3.
- El inversor debe montarse en una pared vertical; nunca obstruya las ventilaciones de entrada o escape.
- Fije la superficie de montaje del soporte a través de los orificios de montaje con sujetadores adecuados.
- Inserte las lengüetas del soporte de montaje (A) en la ranura del cuerpo del inversor (B).
- Fije la parte inferior del inversor a la pared con dos sujetadores a través de los orificios de montaje (C).
Mounting the Inverter installation
⚠ Equipment damage. Mount inverter to a strong, stable surface. Never mount to drywall, plaster, or other non-structural wall treatments.
Tools: 1/4 in fasteners, Anchors or blocking as needed
- Verify mounting location meets all PWRcell Inverter requirements in Section 3.
- Mount inverter upright on a vertical wall. Never obstruct or allow water into intake or exhaust vents.
- Secure mounting bracket to mounting surface through mounting holes.
- Insert mounting bracket tabs into inverter body slot.
- Secure bottom of inverter to wall with two fasteners through mounting holes spaced 11 1/4 in apart.
Puesta en servicio de sistemas múltiples inversores installation
⚠ No energice dos o más inversores antes de la puesta en servicio: provocará intermodulación.
- Realice los pasos 1 al 6 de la descripción general de la puesta en servicio.
- Modifique el canal PLM del inversor a 0 en Mod. Settings para mantener comunicación durante la programación.
- Seleccione un canal exclusivo del 2 al 12 para ese inversor y sus dispositivos REbus.
- Cambie el canal PLM de cada PV Link y batería PWRcell al canal seleccionado.
- Ajuste el canal PLM del inversor para que coincida con el de los dispositivos REbus.
- Desactive el sistema manteniendo presionado el botón rojo de apagado.
- Apague el interruptor de desconexión de la batería de cada batería PWRcell.
- Apague el inversor abriendo su disyuntor de inversión de CA o desconexión de CA.
- Repita los pasos 1 al 8 en el siguiente inversor con un canal PLM distinto.
- Restaure la alimentación de CA a todos los inversores, actívelos y active los dispositivos REbus.
- Complete la puesta en servicio de todos los sistemas según sea necesario.
STOP Terminal Wiring (PV only, without PWRcell Battery) installation
Tools: 20-14 AWG two-conductor cable (600 V insulation)
- Verify the PWRcell system is powered down.
- Remove the jumper from the inverter STOP terminals.
- Use 20-14 AWG two-conductor cable with 600 V insulation to connect a switch that is lockable, UL listed, and rated at least 12 VDC, 5 mA.
Acceso al compartimiento de cableado maintenance
⚠ Inicie una desconexión en todo el sistema y apague el interruptor de desconexión de CC PWRcell en todas las baterías conectadas.
⚠ El interior del inversor no es impermeable; no abra la cubierta cuando esté húmeda, llueva o nieve.
Tools: Multímetro
- Para abrir la cubierta delantera, levante la parte inferior hasta posición horizontal y empújela hacia adentro.
- Ubique la cubierta del compartimiento de cableado (D).
- Retire los cinco tornillos M4X10 (E) y la cubierta del compartimiento de cableado.
- Con un multímetro, verifique que todos los terminales de CA y CC de PWRcell estén bajo 10 V.
Accessing Wiring Compartment maintenance
⚠ The inverter interior is not weather-proof. Do not open the inverter front cover when wet or during rain/snowfall.
Tools: Multi-meter
- Open inverter front cover by lifting the bottom to just beyond horizontal and pushing inward.
- Locate wiring compartment cover.
- Remove five M4X10 screws and wiring compartment cover.
- Verify all PWRcell DC and AC terminals are below 10 V using a multi-meter.
Cleaning Intake Filter maintenance
Tools: Soft brush, Vacuum cleaner
- Clean intake filter with a soft brush or vacuum cleaner.
- If air filter is damaged or difficult to clean, contact an IASD or Generac Customer Service for a replacement filter.
Activación del inversor operation
⚠ Al activar el inversor habrá alto voltaje en los terminales de CC de REbus y en el cableado de CC donde las desconexiones estén ENCENDIDAS.
- Use la tecla de flecha derecha para desplazarse a la página del dispositivo inversor.
- Verifique que las lecturas de estado del inversor estén desactivadas.
- Presione el botón central y resalte “Enable”.
- Mueva la flecha hacia la derecha y presione el botón central para confirmar.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| CT1+ / CT1- | Clavijas 4 y 5 del RJ-45 (Azul, Blanco/Azul en T-568A y T-568B) | Asignación de clavijas de CT RJ-45 (Tabla 5-5); clavijas 7 y 8 no se usan | ||
| CT2+ / CT2- | Clavijas 3 y 6 del RJ-45 (T-568A: Blanco/Naranja, Naranja; T-568B: Blanco/Verde, Verde) | Asignación de clavijas de CT RJ-45 (Tabla 5-5) | ||
| CT3+ / CT3- | Clavijas 1 y 2 del RJ-45 (T-568A: Blanco/Verde, Verde; T-568B: Blanco/Naranja, Naranja) | Asignación de clavijas de CT RJ-45 (Tabla 5-5) | ||
| Conexión a tierra (TIERRA) | Verde | Estándar de colores del cableado de CC de REbus (Tabla 3-1) | ||
| REbus + (RE+) | Rojo | Estándar de colores del cableado de CC de REbus (Tabla 3-1) | ||
| REbus - (RE-) | Negro | Estándar de colores del cableado de CC de REbus (Tabla 3-1) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Repair guides
6- Accessing Wiring Compartment
- Configuring Static IP Settings
- Mounting the Inverter
- Perform an AC Generator Manual Override
- Replacing Fuses
- STOP Terminal Wiring (PV only, without PWRcell Battery)
Step-by-step procedures compiled from the Generac service manual for this model.
Parts
3model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 10000005117 | 240 VAC, 6.3 Amps, 10,000 AIC | 1 | Fuse | Amazon eBay $19.99 |
| A0002532225 | Contrôleur d’ATS PWRcell (réf. A0002532225) | Service part / kit | Amazon eBay $99.99 | |
| G0080060 | Nécessaire de mise à niveau (modèle G0080060) | 1 | Service part / kit | Amazon eBay $160.00 |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Available documents