Generac S2502HC / XVT076A03 — STOP Terminal Wiring (PV only, without PWRcell Battery)

Installation · Inverter STOP terminals

For the Generac S2502HC / XVT076A03, from the Generac service manual.

Browse Generac generators & specs →

Procedure

  1. Verify the PWRcell system is powered down.
  2. Remove the jumper from the inverter STOP terminals.
  3. Use 20-14 AWG two-conductor cable with 600 V insulation to connect a switch that is lockable, UL listed, and rated at least 12 VDC, 5 mA.

Tools required

  • 20-14 AWG two-conductor cable (600 V insulation) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.