Generac S2502HC / XVT076A03 — Replacing Fuses

Repair & overhaul · PWRcell Inverter DC main fuses

For the Generac S2502HC / XVT076A03, from the Generac service manual.

Browse Generac generators & specs →

Before you start

  • Never replace a fuse with a different size or style. Doing so will void the inverter warranty.
  • Never remove DC fuses under load.

Procedure

  1. Initiate an inverter shutdown.
  2. Open all PWRcell DC Disconnects. Verify DC voltage reported on LCD screen has dropped below 10 VDC.
  3. Disconnect all sources of AC and DC power.
  4. Remove wiring compartment cover.
  5. Locate DC fuse holders.
  6. Using a multi-meter, verify all PWRcell DC and AC terminals are below 10 V.
  7. Press fuse holder up and turn counterclockwise to release.
  8. Remove fuse from fuse holder and check for continuity using a multi-meter.
  9. Insert replacement fuse into fuse holder.
  10. Reinstall fuse holder. Turn clockwise until tight.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Verify terminals below 10 V

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.