Service parts for the NP-50LP
Grouped by system, with how many of each the parts manual calls for.
Oil system
1 requiredIgnition
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | LP |
|---|---|
| Frequency | 60.0 Hz |
| Oil capacity | 1.6 L |
| Alternator | NP-50G/LP (2-pole) |
| Voltage options | 120 V, 240 V |
| Phase | 1 |
| Rated current | 37.5 A |
| Battery cranking | 360 CCA |
| Battery voltage | 12 V |
Maintenance & consumables
for the Generac NP-50G/LP| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Paper element with foam pre-cleaner | — | |||
| Fuel filter | — | ||||
| Oil filter | Oil Filter | 70185 | Amazon $28.95 eBay $18.99 KuduParts $11.00 | ||
| Battery | 12 volt, 70 amp-hour, 360 cold cranking amperes (above 32°F); 95 amp-hour, 450 CCA (below 32°F) | — | |||
| Oil | SAE 10W-30, For Service SF | — | |||
| Spark plug | Champion RC12YC | RC12YC | Amazon $19.99 eBay $12.90 FridayParts $19.99 |
Service specifications
46| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Exhaust system clearance to combustible material | 3 | inches (76mm) | |
| Clearance | Generator compartment clearance on sides | 1 | inch | |
| Clearance | Generator compartment clearance on top | 1-1/2 | inches | |
| Gap | Spark plug gap | 0.030 | inch (0.8mm) | |
| Other | Battery amp-hour rating | 70 | amp-hour | above 32°F (0°C) |
| Other | Battery amp-hour rating | 95 | amp-hour | below 32°F (0°C) |
| Other | Battery grounding | Negative (-) | ||
| Other | Battery voltage | 12 | volts DC | |
| Other | Battery voltage drop | 0.12 | volts per 100 amperes | |
| Other | Cold cranking amperes | 360 | CCA | above 32°F (0°C) |
| Other | Cold cranking amperes | 450 | CCA | below 32°F (0°C) |
| Other | Compression ratio | 8.6 to 1 | ||
| Other | Crankcase oil capacity | 1.5 | U.S. quarts (1.6 liters) | |
| Other | Cranking current | 100 | DC amperes | |
| Other | Displacement | 363 | cc | |
| Other | Displacement | 480 | cc | |
| Other | Displacement | 570 | cc | |
| Other | Exhaust temperature rise maximum | 117 | °F (65°C) above ambient | |
| Other | Flexible fuel hose length | 6 | inches longer than necessary | |
| Other | Fuel line clearance from exhaust | 2 | inches | |
| Other | Fuel octane | 87 | minimum octane rating | gasoline |
| Other | LP gas connection size | 3/4 | inch (female) | |
| Other | Minimum cooling air inlet opening | 100 | square inches | |
| Other | Minimum gas flow rate | 67 | cubic feet per hour | |
| Other | Rated horsepower | 13 | horsepower | at 3600 RPM |
| Other | Rated horsepower | 16 | horsepower | at 3600 RPM |
| Other | Rated horsepower | 19 | horsepower | at 3600 RPM |
| Pressure | LP gas pressure at gaseous fuel solenoid valve and secondary regulator inlet | 11 | inches water column | operating |
| Pressure | LP gas pressure at inlet to gaseous fuel solenoid | 11 | inches water column | |
| Pressure | LP gas pressure maximum | 14 | inches water column | do not exceed |
| Pressure | Leak test pressure | 90 | psi (620kPa) | |
| Speed | Engine RPM | 2570 | rpm | |
| Speed | Engine RPM | 2700 | rpm | |
| Speed | Frequency under load | 58 | Hertz | minimum under load |
| Speed | Frequency under load minimum | 58 | Hz | under load |
| Speed | No-load frequency | 62 | Hz | no-load |
| Speed | Rotor RPM | 3600 | rpm | |
| Temperature | High oil temperature switch | 284 | °F (140°C) | |
| Temperature | High oil temperature switch closes | 284 | °F (140°C) | |
| Torque | Governor clamp bolt | 70 | inch-pounds (8 N-m) | |
| Torque | Governor clamp nut | 70 | inch-pounds (8 N-m) | |
| Voltage | Battery cable voltage drop | 0.12 | volts per 100 amperes of cranking current | maximum |
| Voltage | Dual voltage line-to-line no-load voltage | 244-252 | volts AC | no-load, reconnected dual voltage |
| Voltage | No-load voltage | 122-126 | volts AC | no-load |
| Voltage | Voltage regulator adjustment | 124 | volts | 62 Hz, no-load |
| Voltage | Voltage regulator setting | 124 | volts AC | at 62 Hz no-load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | SAE 10W-30 | For Service SF | 1.5 U.S. quarts | 1.6 liters | |
| Fuel | Commercial propane gas | Vapor withdrawal type system only | |||
| Fuel | UNLEADED gasoline, minimum octane rating 87 | Leaded REGULAR grade gasoline acceptable substitute. For gasoline-powered units. | |||
| Fuel | Unleaded gasoline with minimum octane rating of 87 | Leaded REGULAR grade gasoline is an acceptable substitute |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Adjusting No-Load Frequency (NP-50G/LP) adjustment
⚠ Avoid overspeeding the engine.
Tools: Pliers, Wrench
- Loosen governor clamp bolt.
- Push spring end of governor lever clockwise to wide open throttle position.
- Hold governor lever at wide open throttle. With pliers, rotate governor shaft fully counterclockwise.
- While holding shaft fully clockwise and lever at wide open throttle, tighten governor clamp bolt to 70 inch-pounds (8 N-m).
- Start engine, let it stabilize and warm up at no-load.
- Turn adjuster nut to obtain frequency reading of 62 Hertz.
- Check governor spring location in slot of governor lever. Move spring down one slot for excessive droop; up one slot for greater stability.
- After repositioning spring, recheck frequency and readjust adjuster nut if necessary.
- Check AC voltage reading. If incorrect, voltage regulator may require adjustment.
Adjusting No-Load Frequency (Q-40G, NP-66G/LP, Q-55G/LP, Q-70G/LP) adjustment
⚠ Avoid overspeeding the engine.
Tools: Screwdriver, Wrench
- Loosen governor clamp nut.
- Push spring end of governor lever all the way up to wide open throttle position.
- Hold governor lever at wide open throttle. Insert screwdriver into slotted end of governor shaft. Rotate governor shaft fully counterclockwise.
- While holding governor shaft fully counterclockwise and lever at wide open throttle, tighten governor clamp nut to 70 inch-pounds (8 N-m).
- Start engine, let it stabilize and warm up at no-load.
- Turn adjuster nut to obtain frequency reading of 62 Hertz.
- Check governor spring location. Move spring left on bracket teeth for excessive droop; right for greater stability.
- After repositioning spring, recheck frequency and readjust adjuster nut if necessary.
- Check AC voltage reading. If incorrect, voltage regulator may require adjustment.
Adjusting No-Load Frequency for NP-50G/LP adjustment
Tools: pliers
- Loosen governor clamp bolt.
- Push spring end of governor lever clockwise to wide open throttle position of lever.
- Hold governor lever at wide open throttle and, with pliers, rotate governor shaft fully counterclockwise.
- While holding governor shaft fully clockwise and governor lever at wide open throttle, tighten governor clamp bolt to 70 inch-pounds (8 N-m).
- Start engine; let it stabilize and warm up at no-load.
- Turn adjuster nut to obtain a frequency reading of 62 Hertz.
- Check governor spring location in slot of governor lever.
- If droop is excessive, move governor spring down one slot on lever.
- For greater stability, move governor spring up one slot on lever.
- Recheck frequency reading; readjust adjuster nut if necessary to obtain 62 Hertz at no-load.
- When frequency is correct at no-load, check AC voltage; voltage regulator may require adjustment.
Adjusting No-Load Frequency for Q-40G, NP-66G/LP, Q-55G/LP, Q-70G/LP adjustment
Tools: screwdriver
- With engine stopped, inspect anti-lash spring. Replace if broken or damaged; attach if disconnected.
- Loosen governor clamp nut.
- Push spring end of governor lever all the way up to wide open throttle position.
- Hold governor lever at wide open throttle and insert screwdriver into slotted end of governor shaft.
- Rotate governor shaft fully counterclockwise (CCW).
- While holding shaft fully counterclockwise and lever at wide open throttle, tighten governor clamp nut to 70 inch-pounds (8 N-m).
- Start engine; let it stabilize and warm up at no-load.
- Turn adjuster nut to obtain a frequency reading of 62 Hertz.
- Check governor spring location in notched teeth of governor adjustment bracket.
- If droop is excessive, move governor spring to the left on notched teeth of bracket.
- For greater stability, move governor spring to the right on notched teeth of bracket.
- Recheck frequency reading; readjust adjuster nut if necessary to obtain 62 Hertz at no-load.
- When frequency is correct at no-load, check AC voltage; voltage regulator may require adjustment.
Voltage Regulator Adjustment adjustment
Tools: screwdriver
- Remove generator control panel cover and front panel.
- With frequency at 62 Hertz, AC voltage should read 124 volts.
- If voltage is incorrect, slowly turn VOLTAGE ADJUST POT on voltage regulator until AC voltage is correct.
Checking No-Load Voltage and Frequency diagnostic
Tools: AC voltmeter, AC frequency meter
- Connect an accurate AC voltmeter and AC frequency meter across generator AC output leads.
- With generator running, stabilized, and warm, check AC frequency and voltage. Frequency should be about 62 Hz; voltage about 122-126 volts AC.
- If frequency is high or low, adjust engine governor to obtain 62 Hertz at no-load; then recheck voltage reading.
- If frequency is good but voltage is high or low, adjust voltage regulator to obtain 124 volts at 62 Hz no-load.
LP Gas Leakage Test diagnostic
⚠ Do not use any flame to test for leaks.
⚠ No leakage is permitted.
Tools: separate 12 volts DC source, soap and water or equivalent solution
- Use a separate source of 12 volts DC to open the gaseous fuel solenoid valve.
- Test all connections, hoses, valves, regulators, fittings, and other fuel system parts under gas or air pressure of not less than 90 psi (620 kPa).
- Use soap and water or equivalent solution to check for leaks.
- Do not use any flame to test for leaks.
- Comply with NFPA Paragraph 318.
Leakage Tests diagnostic
⚠ Do not use any flame to test for leaks.
Tools: Soap and water solution, 12 volts DC source
- Do not place generator into service until gas system properly tested for leaks.
- Use separate source of 12 volts DC to open gaseous fuel solenoid valve.
- Test all connections, hoses, valves, regulators, fittings under gas or air pressure of not less than 90 psi (620kPa).
- Use soap and water or equivalent solution to check for leaks.
- Do not use any flame to test for leaks.
Testing Under Load diagnostic
Tools: AC frequency meter
- Apply electrical loads equal to about 75-100% of unit's rated wattage/amperage capacity.
- Check frequency with electrical load applied; frequency should not drop below about 58 Hz under load.
- Let unit run at least 30 minutes with load applied; check unit is not running excessively hot and adequate cooling air flow is available.
- Do not allow unit to overheat during prolonged operation.
Battery Cable Connections installation
- Connect battery cable from battery POSITIVE, POS or (+) post to large lug on starter contactor.
- Connect battery cable from battery NEGATIVE, NEG or (-) post to frame ground connection.
- Connect cables so connectors are clean and tight. Check battery cable boot for starter cable has been installed.
Reconnection Procedure installation
⚠ Units reconnected for 120/240 volts dual voltage output will not be listed per RVIA.
⚠ Not applicable to Q-40G model.
- Remove generator cover and front panel.
- Disconnect stator leads 11 and 33, T1 (red) and T3 (black) from main circuit breakers CB1 and CB2.
- Set aside leads T1 (red) and T3 (black) for later use.
- Disconnect stator leads 11 and 33 from 4-tab terminal connector (TC).
- Disconnect stator leads 22 and 44 from grounding terminal (GT).
- Disconnect one of the two T2 (white) leads from grounding terminal.
- Remove existing circuit breakers CB1 and CB2; install new appropriately rated circuit breaker.
- Connect stator leads 11 and 44 to new circuit breaker; attach leads T1 (red) and T3 (black).
- Connect stator leads 22 and 33 to grounding terminal (GT).
- Be sure a neutral lead is installed and routed from grounding terminal for connection loads.
- Route leads T1 (red), T3 (black), and grounded neutral lead through conduit clamp and out of panel.
- Reassemble panel and generator cover.
Reconnection for Dual Voltage installation
⚠ Units reconnected for 120/240 volts dual voltage output will not be listed per RVIA.
⚠ Not applicable to Q-40G model.
Tools: Screwdriver, Pliers
- Gain access to generator panel interior by removing generator cover and front panel.
- Disconnect stator leads 11 and 33, T1 (red) and T3 (black) from main circuit breakers CB1 and CB2. Set aside T1 and T3.
- Disconnect stator leads 11 and 33 from the 4-tab terminal connector (TC).
- Disconnect stator leads 22 and 44 from the grounding terminal (GT).
- Disconnect one of the two T2 (white) leads from the grounding terminal.
- Remove existing circuit breakers CB1 and CB2. Install new appropriately rated circuit breaker.
- Connect stator leads 11 and 44 to new circuit breaker. Attach leads T1 (red) and T3 (black) to circuit breaker.
- Connect stator leads 22 and 33 to grounding terminal (GT).
- Be sure a neutral lead is installed and routed from grounding terminal for connection loads.
- Route leads T1 and T3 and grounded neutral lead through conduit clamp and out of panel.
- Reassemble panel and generator cover.
- Loads may be connected: T3 to Neutral 120 volts; T1 to Neutral 120 volts; T1 to T3 240 volts.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120 | 1 | T1 (red) to Neutral | T1, neutral | After dual voltage reconnection. |
| 120 | 1 | T1 (red) to T2 (white) | T1, T2 | Line-to-neutral; protected by circuit breaker CB1; up to 3600 watts. |
| 120 | 1 | T1 (red) to T2 (white) neutral | T1, T2 | Protected by circuit breaker CB1; use separately for 120 volts, 1-phase, 60 Hz loads up to 3600 watts (3.6 kW). |
| 120 | 1 | T3 (black) to Neutral | T3, neutral | After dual voltage reconnection. |
| 120 | 1 | T3 (black) to T2 (white) | T3, T2 | Line-to-neutral; protected by circuit breaker CB2. |
| 120 | 1 | T3 (black) to T2 (white) neutral | T3, T2 | Protected by circuit breaker CB2; total unit load must not exceed maximum rating. |
| 120/240 | 1 | Stator leads 11 and 44 to new circuit breaker; 22 and 33 to grounding terminal | 11, 44, 22, 33 | Reconnection procedure for dual voltage output. |
| 120/240 | 1 | Stator leads 11 and 44 to new circuit breaker; stator leads 22 and 33 to grounding terminal | 11, 44, 22, 33 | Dual voltage reconnection procedure. Not applicable to Q-40G. |
| 240 | 1 | T1 (red) to T3 (black) | T1, T3 | Dual voltage; neutral T2. |
| 240 | 1 | T1 to T3 | T1, T3 | After dual voltage reconnection. Replace CB1 and CB2 with a single suitably rated circuit breaker. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What engine does the Generac NP-50LP use?
The Generac NP-50LP is powered by the Generac NP-50G/LP engine.
What fuel type does the Generac NP-50LP take?
The Generac NP-50LP runs on LP.
What's the oil capacity on a Generac NP-50LP?
The Generac NP-50G/LP engine in the Generac NP-50LP has an oil capacity of 1.6 liters.
What alternator does the Generac NP-50LP use?
The Generac NP-50LP uses a NP-50G/LP alternator. It has 2 poles.
What oil filter fits the Generac NP-50LP?
The Generac NP-50LP uses oil filter part number 70185.
Parts
6| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 70185 | FILTER, OIL | 1 | Oil filter | Amazon $28.95 eBay $18.99 KuduParts $11.00 |
| 77643 | Exhaust Outlet Gasket | 2 | Gasket | Amazon $15.55 eBay $13.87 |
| 95277 | Outlet Adaptor Gasket | 1 | Gasket | eBay |
| RC12YC | Spark Plug | 1 | Spark plug | Amazon $19.99 eBay $12.90 FridayParts $19.99 |
| 52108 | Muffler | 1 | Service part / kit | Amazon eBay |
| 92675A | Exhaust Muffler | 1 | Service part / kit | eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Continuous | 25% | 0.61 | 0.16 |
| Continuous | 50% | 1.21 | 0.32 |
| Continuous | 75% | 1.74 | 0.46 |
| Continuous | 100% | 2.38 | 0.63 |