HomeGeneracGenerac NP-50LP

Generac NP-50LP Generator Set

The Generac NP-50LP is a LP generator set powered by a Generac NP-50G/LP engine. It is available at 120 V and 240 V, single-phase, 60 Hz and rated 37.5 A. It holds about 1.6 L (0.4 gal) of oil. Starting uses battery rated 360 CCA at 12 V.

0.363 L
Displacement
1.6 L
Oil capacity
3
Document types

How to read your Generac serial & model number →

Service parts for the NP-50LP

Grouped by system, with how many of each the parts manual calls for.

Oil system

1 required
70185Oil filter$18.99eBay

Ignition

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelLP
Frequency60.0 Hz
Oil capacity1.6 L
AlternatorNP-50G/LP (2-pole)
Voltage options120 V, 240 V
Phase1
Rated current37.5 A
Battery cranking360 CCA
Battery voltage12 V

Engine

Generac NP-50G/LP
Oil capacity1.6 L
Displacement0.363 L
AspirationNatural
Rated speed3600 rpm

Maintenance & consumables

for the Generac NP-50G/LP
ItemSpecCapacityPart #Interval
Air filterPaper element with foam pre-cleaner
Fuel filter
Oil filterOil Filter70185 Amazon $28.95 eBay $18.99 KuduParts $11.00
Battery12 volt, 70 amp-hour, 360 cold cranking amperes (above 32°F); 95 amp-hour, 450 CCA (below 32°F)
OilSAE 10W-30, For Service SF
Spark plugChampion RC12YCRC12YC Amazon $19.99 eBay $12.90 FridayParts $19.99

Service specifications

46
TypeItemValueUnitCondition
ClearanceExhaust system clearance to combustible material3inches (76mm)
ClearanceGenerator compartment clearance on sides1inch
ClearanceGenerator compartment clearance on top1-1/2inches
GapSpark plug gap0.030inch (0.8mm)
OtherBattery amp-hour rating70amp-hourabove 32°F (0°C)
OtherBattery amp-hour rating95amp-hourbelow 32°F (0°C)
OtherBattery groundingNegative (-)
OtherBattery voltage12volts DC
OtherBattery voltage drop0.12volts per 100 amperes
OtherCold cranking amperes360CCAabove 32°F (0°C)
OtherCold cranking amperes450CCAbelow 32°F (0°C)
OtherCompression ratio8.6 to 1
OtherCrankcase oil capacity1.5U.S. quarts (1.6 liters)
OtherCranking current100DC amperes
OtherDisplacement363cc
OtherDisplacement480cc
OtherDisplacement570cc
OtherExhaust temperature rise maximum117°F (65°C) above ambient
OtherFlexible fuel hose length6inches longer than necessary
OtherFuel line clearance from exhaust2inches
OtherFuel octane87minimum octane ratinggasoline
OtherLP gas connection size3/4inch (female)
OtherMinimum cooling air inlet opening100square inches
OtherMinimum gas flow rate67cubic feet per hour
OtherRated horsepower13horsepowerat 3600 RPM
OtherRated horsepower16horsepowerat 3600 RPM
OtherRated horsepower19horsepowerat 3600 RPM
PressureLP gas pressure at gaseous fuel solenoid valve and secondary regulator inlet11inches water columnoperating
PressureLP gas pressure at inlet to gaseous fuel solenoid11inches water column
PressureLP gas pressure maximum14inches water columndo not exceed
PressureLeak test pressure90psi (620kPa)
SpeedEngine RPM2570rpm
SpeedEngine RPM2700rpm
SpeedFrequency under load58Hertzminimum under load
SpeedFrequency under load minimum58Hzunder load
SpeedNo-load frequency62Hzno-load
SpeedRotor RPM3600rpm
TemperatureHigh oil temperature switch284°F (140°C)
TemperatureHigh oil temperature switch closes284°F (140°C)
TorqueGovernor clamp bolt70inch-pounds (8 N-m)
TorqueGovernor clamp nut70inch-pounds (8 N-m)
VoltageBattery cable voltage drop0.12volts per 100 amperes of cranking currentmaximum
VoltageDual voltage line-to-line no-load voltage244-252volts ACno-load, reconnected dual voltage
VoltageNo-load voltage122-126volts ACno-load
VoltageVoltage regulator adjustment124volts62 Hz, no-load
VoltageVoltage regulator setting124volts ACat 62 Hz no-load

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilSAE 10W-30For Service SF1.5 U.S. quarts1.6 liters
FuelCommercial propane gasVapor withdrawal type system only
FuelUNLEADED gasoline, minimum octane rating 87Leaded REGULAR grade gasoline acceptable substitute. For gasoline-powered units.
FuelUnleaded gasoline with minimum octane rating of 87Leaded REGULAR grade gasoline is an acceptable substitute

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting No-Load Frequency (NP-50G/LP) adjustment

⚠ Avoid overspeeding the engine.

Tools: Pliers, Wrench

  1. Loosen governor clamp bolt.
  2. Push spring end of governor lever clockwise to wide open throttle position.
  3. Hold governor lever at wide open throttle. With pliers, rotate governor shaft fully counterclockwise.
  4. While holding shaft fully clockwise and lever at wide open throttle, tighten governor clamp bolt to 70 inch-pounds (8 N-m).
  5. Start engine, let it stabilize and warm up at no-load.
  6. Turn adjuster nut to obtain frequency reading of 62 Hertz.
  7. Check governor spring location in slot of governor lever. Move spring down one slot for excessive droop; up one slot for greater stability.
  8. After repositioning spring, recheck frequency and readjust adjuster nut if necessary.
  9. Check AC voltage reading. If incorrect, voltage regulator may require adjustment.
Adjusting No-Load Frequency (Q-40G, NP-66G/LP, Q-55G/LP, Q-70G/LP) adjustment

⚠ Avoid overspeeding the engine.

Tools: Screwdriver, Wrench

  1. Loosen governor clamp nut.
  2. Push spring end of governor lever all the way up to wide open throttle position.
  3. Hold governor lever at wide open throttle. Insert screwdriver into slotted end of governor shaft. Rotate governor shaft fully counterclockwise.
  4. While holding governor shaft fully counterclockwise and lever at wide open throttle, tighten governor clamp nut to 70 inch-pounds (8 N-m).
  5. Start engine, let it stabilize and warm up at no-load.
  6. Turn adjuster nut to obtain frequency reading of 62 Hertz.
  7. Check governor spring location. Move spring left on bracket teeth for excessive droop; right for greater stability.
  8. After repositioning spring, recheck frequency and readjust adjuster nut if necessary.
  9. Check AC voltage reading. If incorrect, voltage regulator may require adjustment.
Adjusting No-Load Frequency for NP-50G/LP adjustment

Tools: pliers

  1. Loosen governor clamp bolt.
  2. Push spring end of governor lever clockwise to wide open throttle position of lever.
  3. Hold governor lever at wide open throttle and, with pliers, rotate governor shaft fully counterclockwise.
  4. While holding governor shaft fully clockwise and governor lever at wide open throttle, tighten governor clamp bolt to 70 inch-pounds (8 N-m).
  5. Start engine; let it stabilize and warm up at no-load.
  6. Turn adjuster nut to obtain a frequency reading of 62 Hertz.
  7. Check governor spring location in slot of governor lever.
  8. If droop is excessive, move governor spring down one slot on lever.
  9. For greater stability, move governor spring up one slot on lever.
  10. Recheck frequency reading; readjust adjuster nut if necessary to obtain 62 Hertz at no-load.
  11. When frequency is correct at no-load, check AC voltage; voltage regulator may require adjustment.
Adjusting No-Load Frequency for Q-40G, NP-66G/LP, Q-55G/LP, Q-70G/LP adjustment

Tools: screwdriver

  1. With engine stopped, inspect anti-lash spring. Replace if broken or damaged; attach if disconnected.
  2. Loosen governor clamp nut.
  3. Push spring end of governor lever all the way up to wide open throttle position.
  4. Hold governor lever at wide open throttle and insert screwdriver into slotted end of governor shaft.
  5. Rotate governor shaft fully counterclockwise (CCW).
  6. While holding shaft fully counterclockwise and lever at wide open throttle, tighten governor clamp nut to 70 inch-pounds (8 N-m).
  7. Start engine; let it stabilize and warm up at no-load.
  8. Turn adjuster nut to obtain a frequency reading of 62 Hertz.
  9. Check governor spring location in notched teeth of governor adjustment bracket.
  10. If droop is excessive, move governor spring to the left on notched teeth of bracket.
  11. For greater stability, move governor spring to the right on notched teeth of bracket.
  12. Recheck frequency reading; readjust adjuster nut if necessary to obtain 62 Hertz at no-load.
  13. When frequency is correct at no-load, check AC voltage; voltage regulator may require adjustment.
Voltage Regulator Adjustment adjustment

Tools: screwdriver

  1. Remove generator control panel cover and front panel.
  2. With frequency at 62 Hertz, AC voltage should read 124 volts.
  3. If voltage is incorrect, slowly turn VOLTAGE ADJUST POT on voltage regulator until AC voltage is correct.
Checking No-Load Voltage and Frequency diagnostic

Tools: AC voltmeter, AC frequency meter

  1. Connect an accurate AC voltmeter and AC frequency meter across generator AC output leads.
  2. With generator running, stabilized, and warm, check AC frequency and voltage. Frequency should be about 62 Hz; voltage about 122-126 volts AC.
  3. If frequency is high or low, adjust engine governor to obtain 62 Hertz at no-load; then recheck voltage reading.
  4. If frequency is good but voltage is high or low, adjust voltage regulator to obtain 124 volts at 62 Hz no-load.
LP Gas Leakage Test diagnostic

⚠ Do not use any flame to test for leaks.

⚠ No leakage is permitted.

Tools: separate 12 volts DC source, soap and water or equivalent solution

  1. Use a separate source of 12 volts DC to open the gaseous fuel solenoid valve.
  2. Test all connections, hoses, valves, regulators, fittings, and other fuel system parts under gas or air pressure of not less than 90 psi (620 kPa).
  3. Use soap and water or equivalent solution to check for leaks.
  4. Do not use any flame to test for leaks.
  5. Comply with NFPA Paragraph 318.
Leakage Tests diagnostic

⚠ Do not use any flame to test for leaks.

Tools: Soap and water solution, 12 volts DC source

  1. Do not place generator into service until gas system properly tested for leaks.
  2. Use separate source of 12 volts DC to open gaseous fuel solenoid valve.
  3. Test all connections, hoses, valves, regulators, fittings under gas or air pressure of not less than 90 psi (620kPa).
  4. Use soap and water or equivalent solution to check for leaks.
  5. Do not use any flame to test for leaks.
Testing Under Load diagnostic

Tools: AC frequency meter

  1. Apply electrical loads equal to about 75-100% of unit's rated wattage/amperage capacity.
  2. Check frequency with electrical load applied; frequency should not drop below about 58 Hz under load.
  3. Let unit run at least 30 minutes with load applied; check unit is not running excessively hot and adequate cooling air flow is available.
  4. Do not allow unit to overheat during prolonged operation.
Battery Cable Connections installation
  1. Connect battery cable from battery POSITIVE, POS or (+) post to large lug on starter contactor.
  2. Connect battery cable from battery NEGATIVE, NEG or (-) post to frame ground connection.
  3. Connect cables so connectors are clean and tight. Check battery cable boot for starter cable has been installed.
Reconnection Procedure installation

⚠ Units reconnected for 120/240 volts dual voltage output will not be listed per RVIA.

⚠ Not applicable to Q-40G model.

  1. Remove generator cover and front panel.
  2. Disconnect stator leads 11 and 33, T1 (red) and T3 (black) from main circuit breakers CB1 and CB2.
  3. Set aside leads T1 (red) and T3 (black) for later use.
  4. Disconnect stator leads 11 and 33 from 4-tab terminal connector (TC).
  5. Disconnect stator leads 22 and 44 from grounding terminal (GT).
  6. Disconnect one of the two T2 (white) leads from grounding terminal.
  7. Remove existing circuit breakers CB1 and CB2; install new appropriately rated circuit breaker.
  8. Connect stator leads 11 and 44 to new circuit breaker; attach leads T1 (red) and T3 (black).
  9. Connect stator leads 22 and 33 to grounding terminal (GT).
  10. Be sure a neutral lead is installed and routed from grounding terminal for connection loads.
  11. Route leads T1 (red), T3 (black), and grounded neutral lead through conduit clamp and out of panel.
  12. Reassemble panel and generator cover.
Reconnection for Dual Voltage installation

⚠ Units reconnected for 120/240 volts dual voltage output will not be listed per RVIA.

⚠ Not applicable to Q-40G model.

Tools: Screwdriver, Pliers

  1. Gain access to generator panel interior by removing generator cover and front panel.
  2. Disconnect stator leads 11 and 33, T1 (red) and T3 (black) from main circuit breakers CB1 and CB2. Set aside T1 and T3.
  3. Disconnect stator leads 11 and 33 from the 4-tab terminal connector (TC).
  4. Disconnect stator leads 22 and 44 from the grounding terminal (GT).
  5. Disconnect one of the two T2 (white) leads from the grounding terminal.
  6. Remove existing circuit breakers CB1 and CB2. Install new appropriately rated circuit breaker.
  7. Connect stator leads 11 and 44 to new circuit breaker. Attach leads T1 (red) and T3 (black) to circuit breaker.
  8. Connect stator leads 22 and 33 to grounding terminal (GT).
  9. Be sure a neutral lead is installed and routed from grounding terminal for connection loads.
  10. Route leads T1 and T3 and grounded neutral lead through conduit clamp and out of panel.
  11. Reassemble panel and generator cover.
  12. Loads may be connected: T3 to Neutral 120 volts; T1 to Neutral 120 volts; T1 to T3 240 volts.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
1201T1 (red) to NeutralT1, neutralAfter dual voltage reconnection.
1201T1 (red) to T2 (white)T1, T2Line-to-neutral; protected by circuit breaker CB1; up to 3600 watts.
1201T1 (red) to T2 (white) neutralT1, T2Protected by circuit breaker CB1; use separately for 120 volts, 1-phase, 60 Hz loads up to 3600 watts (3.6 kW).
1201T3 (black) to NeutralT3, neutralAfter dual voltage reconnection.
1201T3 (black) to T2 (white)T3, T2Line-to-neutral; protected by circuit breaker CB2.
1201T3 (black) to T2 (white) neutralT3, T2Protected by circuit breaker CB2; total unit load must not exceed maximum rating.
120/2401Stator leads 11 and 44 to new circuit breaker; 22 and 33 to grounding terminal11, 44, 22, 33Reconnection procedure for dual voltage output.
120/2401Stator leads 11 and 44 to new circuit breaker; stator leads 22 and 33 to grounding terminal11, 44, 22, 33Dual voltage reconnection procedure. Not applicable to Q-40G.
2401T1 (red) to T3 (black)T1, T3Dual voltage; neutral T2.
2401T1 to T3T1, T3After dual voltage reconnection. Replace CB1 and CB2 with a single suitably rated circuit breaker.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What engine does the Generac NP-50LP use?

The Generac NP-50LP is powered by the Generac NP-50G/LP engine.

What fuel type does the Generac NP-50LP take?

The Generac NP-50LP runs on LP.

What's the oil capacity on a Generac NP-50LP?

The Generac NP-50G/LP engine in the Generac NP-50LP has an oil capacity of 1.6 liters.

What alternator does the Generac NP-50LP use?

The Generac NP-50LP uses a NP-50G/LP alternator. It has 2 poles.

What oil filter fits the Generac NP-50LP?

The Generac NP-50LP uses oil filter part number 70185.

Parts

6
Part #DescriptionQtySystem
70185FILTER, OIL1Oil filter Amazon $28.95 eBay $18.99 KuduParts $11.00
77643Exhaust Outlet Gasket2Gasket Amazon $15.55 eBay $13.87
95277Outlet Adaptor Gasket1Gasket eBay
RC12YCSpark Plug1Spark plug Amazon $19.99 eBay $12.90 FridayParts $19.99
52108Muffler1Service part / kit Amazon eBay
92675AExhaust Muffler1Service part / kit eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Continuous25%0.610.16
Continuous50%1.210.32
Continuous75%1.740.46
Continuous100%2.380.63