Home›Repair guides›Generac›Checking No-Load Voltage and Frequency

Generac — Checking No-Load Voltage and Frequency

Testing & diagnosis · Generator AC output

From a Generac service manual covering: NP-50G, NP-50LP, NP-66G/LP, Q-40G, Q-55G/LP, Q-70G/LP. Check it applies to your exact model before use.

Applies to: Generac NP-50G, Generac NP-50LP, Generac Q-40G, Generac NP-50G/LP engine

Procedure

  1. Connect an accurate AC voltmeter and AC frequency meter across generator AC output leads.
  2. With generator running, stabilized, and warm, check AC frequency and voltage. Frequency should be about 62 Hz; voltage about 122-126 volts AC.
  3. If frequency is high or low, adjust engine governor to obtain 62 Hertz at no-load; then recheck voltage reading.
  4. If frequency is good but voltage is high or low, adjust voltage regulator to obtain 124 volts at 62 Hz no-load.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 62 Hz no-load
  • 122-126 volts AC no-load
  • 124 volts at 62 Hz no-load

Full service-parts list: Generac NP-50G →, Generac NP-50LP →, Generac Q-40G →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.