Generac — Initial Start

Operation · Generator

From a Generac service manual covering: NP-50G, NP-50LP, NP-66G/LP, Q-40G, Q-55G/LP, Q-70G/LP. Check it applies to your exact model before use.

Applies to: Generac NP-50G, Generac NP-50LP, Generac Q-40G, Generac NP-50G/LP engine

Before you start

  • Do not make any unnecessary adjustments. Factory settings are correct for most applications. Avoid overspeeding the engine.

Procedure

  1. Turn off all electrical loads by setting generator main circuit breakers to OFF or OPEN.
  2. Refer to Owner's Manual for cranking and starting instructions.
  3. Let engine warm up about five minutes to allow internal temperatures to stabilize.
  4. Inspect engine-generator for fuel, oil, and exhaust system leaks. Correct any leakage immediately.
  5. Check no-load voltage and frequency.
  6. Apply electrical loads and check operation under load. Run unit at least 30 minutes with loads applied.
  7. Turn off all electrical loads by setting generator main circuit breakers to OFF or OPEN.
  8. Let unit run at no-load for a few minutes to stabilize temperatures. Shut down engine.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • No-load frequency about 62 Hz
  • No-load voltage 122-126 volts AC

Full service-parts list: Generac NP-50G →, Generac NP-50LP →, Generac Q-40G →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →