Home›Repair guides›Generac›LP Gas Leakage Test

Generac — LP Gas Leakage Test

Testing & diagnosis · Propane fuel system

From a Generac service manual covering: NP-50G, NP-50LP, NP-66G/LP, Q-40G, Q-55G/LP, Q-70G/LP. Check it applies to your exact model before use.

Applies to: Generac NP-50G, Generac NP-50LP, Generac Q-40G, Generac NP-50G/LP engine

Before you start

  • Do not use any flame to test for leaks.
  • No leakage is permitted.

Procedure

  1. Use a separate source of 12 volts DC to open the gaseous fuel solenoid valve.
  2. Test all connections, hoses, valves, regulators, fittings, and other fuel system parts under gas or air pressure of not less than 90 psi (620 kPa).
  3. Use soap and water or equivalent solution to check for leaks.
  4. Do not use any flame to test for leaks.
  5. Comply with NFPA Paragraph 318.

Tools required

  • separate 12 volts DC source Amazon
  • soap and water or equivalent solution Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 90 psi (620 kPa) minimum test pressure

Full service-parts list: Generac NP-50G →, Generac NP-50LP →, Generac Q-40G →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.