Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 300 kW |
| Standby kVA | 375 |
| Oil capacity | 39.7 L |
| Phase | 3 |
| Power factor | 0.8 |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 64 L |
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil | SAE 10W-30 (-13°F to 95°F); SAE 15W-40 (-14°F and above); SAE 20W-40 (32°F and above) | 42.0 quarts | — |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Common questions
What is the power rating of the Cummins/Onan 300 DFCB?
The Cummins/Onan 300 DFCB is rated 300 kW standby (375.0 kVA).
What engine does the Cummins/Onan 300 DFCB use?
The Cummins/Onan 300 DFCB is powered by the Cummins/Onan NTA855-G6 engine.
What fuel does the Cummins/Onan 300 DFCB use?
The Cummins/Onan 300 DFCB runs on Diesel.
Troubleshooting
19Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Green RUN lamp lights following engine startup. | Indicates all engine systems are normal. No corrective action required. | |
| PRE HI ENGINE TEMP lamp lights. Engine continues to operate. | Indicates engine has begun to overheat and engine temperature has risen to approximately 215°F (102°C). If generator is powering non-critical and critical loads and cannot be shut down, use the following: a. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow procedure in step 3. | |
| HI ENG TEMP lamp lights. Engine shuts down. | Indicates engine has overheated (engine temperature has risen above 222°F/106°C) or coolant level is low (sets with coolant level sensor). Allow engine to cool down completely before proceeding with the following checks: a. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt and tighten if loose. d. Reset control and restart after locating and correcting problem. Contact an authorized service center if none of the above. | |
| PRE LO OIL PRES lamp lights. Engine continues to operate. | Indicates engine oil pressure has dropped to 20 psi (138 kPa). If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedures in step 5. | |
| LO OIL PRES lamp lights. Engine shuts down. | Indicates engine oil pressure has dropped to 14 psi (97 kPa). Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Contact an authorized service center if oil pressure is not in the range of 25 to 40 psi (172 to 275 kPa). | |
| OVERCRANK lamp lights and engine stops cranking. | Indicates possible fuel system problem. a. Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. b. Check for dirty fuel filter and replace if necessary (see Maintenance section). c. Check for dirty or plugged air filter and replace if necessary (see Maintenance section). d. Reset the control and restart after correcting the problem. Contact an authorized service center for service if none of the above. | |
| Engine runs and then shuts down, OVERSPEED lamp lights. | Indicates engine has exceeded normal operating speed. Contact an authorized service center for service. | |
| SWITCH OFF lamp flashes. | Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the Remote position for automatic starting. | |
| LO FUEL lamp lights. Engine continues to run. | Indicates diesel fuel supply is running low. Check fuel supply and replenish as required. | |
| LO FUEL LAMP lights. Engine shuts down and LO OIL PRES lamp lights. | Indicates engine has run out of fuel. Check fuel level and replenish as required. | |
| LO ENG TEMP lamp lights. Set is in standby mode but is not operating. | Lamp lights when engine coolant temperature is 70° F (21° C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm even during initial generator set operation. | |
| Engine runs and then shuts down, LO ENG TEMP lamp lights. | Indicates engine coolant heater is not operating or is not circulating coolant. Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an authorized service center if none of the above. | |
| Engine monitor activates a fault lamp | Low oil pressure or high coolant temperature | Make adjustments or corrections and restart the set |
| The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. | Standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay. | |
| Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature, and frequency (speed) are within normal limits. | The monitor board or a sensor may be at fault. Contact an authorized service center for service. | |
| Engine starts from generator control panel but will not start automatically or from a remote panel. | (Note: The Run/Stop/Remote switch must be in the Remote position for automatic or remote starting). | Remote circuit breaker is tripped. Reset breaker and restart. Contact an authorized service center if breaker trips after resetting. |
| Engine will not crank. | Indicates possible fault with control or starting system. Check for the following conditions: | A. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Discharged or defective battery. Recharge or replace the battery. d. Emergency stop button (if equipped) pushed in. To reset, pull switch out and move Run/Stop/Remote switch to Stop position. Then push test switch to Reset/Lamp position. e. Contact an authorized service center if none of the above. |
| No AC output voltage. | Field breaker is tripped. Reset breaker. Contact an authorized service center if voltage buildup causes breaker to trip. | |
| Green RUN lamp does not light following engine startup. | Indicates possible Start/Disconnect relay failure. | Contact an authorized service center for assistance. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Available documents
Operator's manual — 960-0138 Cummins DFBF DFCB DFCC Operator's Manual (1-2003) (Cummins/Onan)