Cummins/Onan — Connecting the Load

Installation · Generator terminal block

From a Cummins/Onan service manual covering: 275 DFBF, 300 DFCB, 350 DFCC. Check it applies to your exact model before use.

Applies to: Cummins/Onan 275 DFBF, Cummins/Onan 300 DFCB, Cummins/Onan 350 DFCC, Cummins/Onan NT-855-G6 engine, Cummins/Onan NTA-855-G2 engine, Cummins/Onan NTA855-G3 engine

Before you start

  • Do not connect generator set directly to any building electrical system; connect only through an approved isolation switch or paralleling device.

Procedure

  1. Bolt load wires to the appropriate terminals on the generator terminal block.
  2. Terminals are stamped U, V, W and N (U, V, W = L1, L2, L3; N = L0).
  3. Route generator output leads through current transformers CT21, CT22 and CT23 for meter operation.
  4. Balance loads so current from each line terminal is about the same.
  5. Ensure each line current is within 10 percent of median value and below nameplate rating.

Specs & values

  • Line current within 10 percent of median value

Full service-parts list: Cummins/Onan 275 DFBF →, Cummins/Onan 350 DFCC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.