Home›Engines›Cummins/Onan NTA-855-G2

Cummins/Onan NTA-855-G2 Engine

The Cummins/Onan NTA-855-G2 is a 14 L 6-cylinder turbocharged and aftercooled engine rated at 1800 rpm, producing up to 346.9 kW. It powers generator sets from Cummins/Onan, including the 300 DFCB, 300DFCB-2272, 300NTA2 and DBCB. It holds 31 L (8.2 gal) of oil and 20.8 L (5.5 gal) of coolant.

Also known as: Cummins NTA-855-G2

Part of the Cummins/Onan NTA855 engine family — 17 variants share parts & fitment.

14.0 L
Displacement
6
Cylinders
1800 rpm
Rated speed
346 kW
Gross power

Engine specifications

Oil capacity31.0 L
Coolant capacity20.8 L
Displacement14.0 L
Cylinders6
AspirationTurbocharged and Aftercooled
Rated speed1800 rpm
Gross power346 kW

Generator sets powered by this engine

8
Cummins/Onan 300 DFCBCummins/Onan 300DFCB-2272Cummins/Onan 300NTA2Cummins/Onan DBCBCummins/Onan DFCBCummins/Onan DFCFCummins/Onan DFM 300Cummins/Onan NTA855G2 CP350-6 DFCB

How to read your Cummins/Onan engine serial & model number →

Common problems

15
  • No AC output voltage.
    Fix: 3. Confirm that Exciter Switch is at ON position. Voltage regulator is inoperative. Refer to Initial Start and Checks, and Adjustments sections for voltage check and adjustment procedures. Contact your distributor if voltage build-up is still a problem.
  • LO FUEL lamp lights. Engine continues to run.
    Fix: Check fuel supply and replenish as required.
  • Engine will not crank.
    Cause: Possible fault with control or starting system.
    Fix: A. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Discharged or defective battery. Recharge or replace the battery. d. Contact your distributor for assistance if none of the above applies.
  • Engine starts from generator control panel but will not start automatically or from a remote panel.
    Cause: (Note: The Run/Stop/Remote switch must be in the Remote position for automatic or remote starting).
    Fix: Remote circuit breaker is tripped. Reset breaker and restart. Contact an authorized service center if breaker trips after resetting.
  • Engine runs and then shuts down, OVERSPEED lamp lights.
    Fix: 4. Indicates engine has exceeded normal operating speed. Contact your distributor for service.
  • UNDER FREQUENCY 313
    Fix: Shutdown
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.
    Cause: Standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • SWITCH OFF lamp flashes.
    Fix: Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the Remote position for automatic starting.
  • SHORT CIRCUIT 322
    Fix: Shutdown
  • Over Current 1471
  • LOW OIL PRESSURE 200
    Fix: Shutdown
  • Low Coolant Level 197
  • LOW AC VOLTAGE 303
    Fix: Shutdown
  • LO OIL PRES lamp lights. Engine shuts down.
    Cause: Engine oil pressure has dropped to 12 psi (88 kPa).
    Fix: 5. Check oil level, lines and filters. If oil system is okay but oil level is low, replenish. Reset control and restart. Contact your distributor if oil pressure is not in the range of 40 to 70 psi (276 to 483 kPa).
  • LO FUEL lamp lights. Engine shuts down and LO OIL PRES lamp lights.
    Fix: Check fuel level and replenish as required.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan NTA-855-G2.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter8-7-24—465 hr
Battery127 A/hr—
Belt—
Coolant84.8 Litres—
Oil38.6 Litres38.6 Litres—
Spark plug—

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

34
ItemActionHoursMonthsNotes
Generator setInspect8 hrCheck for oil, fuel, cooling and exhaust leaks; check exhaust system audibly and visually with set running
GensetInspect8 hrInspect for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running (footnote X1).
Air CleanerCheck50 hrClean if required. Perform more often in dusty conditions (footnote X2).
Air cleanerClean50 hrClean if required; more often in extremely dusty conditions
Battery Charging SystemCheck50 hr
Charge Air PipingCheck50 hr
Coolant HeaterCheck50 hrColumn alignment in source table is ambiguous; interval as printed in schedule columns.
Coolant LevelCheck50 hr
Crankcase oilChange50 hrFirst service — Break-in: drain and replace crankcase oil after first 50 hours on new generator sets
Drive belt tensionCheck100 hrVisually check belts for evidence of slippage
Exhaust condensation trapDrain50 hr
Fuel LevelCheck50 hr
Oil LevelCheck50 hr
Anti-freeze and DCA ConcentrationCheck100 hrRefer to engine operation and maintenance manual for procedure (footnote X5).
Battery level/specific gravityCheck100 hr
Exhaust Condensate TrapDrain100 hr
Fuel Filter(s)Drain100 hrDrain 1 cup or more of fuel to remove water and sediment (footnote X4); refer to engine operation and maintenance manual (footnote X5).
Fuel tanks water/sedimentDrain100 hrDrain 1 cup or more of fuel to remove water and sediment
Generator air outletCheck100 hr
Water and Sediment from Fuel TankDrain100 hrDrain 1 cup or more of fuel to remove water and sediment (footnote X4).
Air Cleaner ElementChange500 hr12 moPerform more often in dusty conditions (footnote X2).
Antifreeze and DCA concentrationCheck250 hr6 mo
Coolant FilterChange500 hr12 moRefer to engine operation and maintenance manual for procedure (footnote X5).
Crankcase BreatherClean500 hr12 moRefer to engine operation and maintenance manual for procedure (footnote X5).
Crankcase oil and filterChange250 hr12 moFirst service — Table 7-1. If genset used for prime power, change every 6 months or 250 hours. If standby, change every 12 months or 250 hours, whichever comes first.
Generator assemblyClean250 hr6 mo
Heat exchanger plugsCheck250 hr6 moIf equipped
Starting BatteriesCheck250 hr
Cooling SystemClean500 hr12 moRefer to engine operation and maintenance manual for procedure (footnote X5).
Fuel FiltersChange500 hr12 moRefer to engine operation and maintenance manual for procedure (footnote X5).
Radiator Hoses for Wear & CracksCheck500 hr12 mo
Generator bearingInspect1000 hr
Generator bearingReplace10000 hr24 moPrime power: every 10,000 hours or two years; standby power: every five years
Rupture basin leak detect switchTest12 moSome areas may require weekly inspections by safety code.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceAngular alignment maximum T.I.R.0.001inch per inch of radius (center of shaft to indicator axis)measuring deflection to bolt heads
ClearanceCoolant level below radiator cap openingabout two inches (50 mm)in (mm)engine cold
ClearanceExhaust pipe clearance to combustible wall or partition12inches (305 mm)minimum
ClearanceExhaust pipe clearance to combustible wall or partitionat least 12 inches (305 mm)inch
ClearanceExhaust thimble spacing9inch (230 mm)minimum
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
ClearanceMPU sensor to gear tooth adjustmentback out one quarter turnturnafter contacting gear tooth
ClearanceMounting base surface height above floorat least 6 inches (152 mm)inch
ClearanceVibration isolator base elevation difference0.25inch (6 mm)all isolator bases within this elevation of each other
ClearanceVibration isolator base elevation variation0.25inch (6 mm)shimmed or grouted
ClearanceVibration isolator top plate to base clearance0.25inch (6 mm)nominal, or greater
GapAir cleaner cleaning nozzle distance1inch (25 mm)at least
GapAir cleaner element cleaning nozzle distanceat least 1 inch (25 mm)inchlow pressure compressed air 30 psi (207 kPa)
GapFloat switch lift to test open1/8inchbelow C-clip stop
GapMPU sensor to flywheel ring gear toothback it out one quarter turnturnsensor threaded in until it just touches gear tooth
OtherAVR Droop setting5% at full load, 0 PF
OtherAVR voltage regulation (load regulation)approximately ±0.5% RMS
OtherAir cleaner element solvent soak time15minutesDonaldson D1400 solvent or equivalent
OtherAngular alignment maximum T.I.R..001inch per inch of radiuscenter of shaft to indicator axis
OtherAngular alignment maximum T.I.R..001 inches per inch of radiusin/incenter of shaft to indicator axis
OtherBattery electrolyte specific gravity, charge if below1.215
OtherBattery electrolyte specific gravity, fully charged (corrected)1.260corrected; add 0.004 per 10°F above 80°F (27°C)
OtherBattery specific gravity1.260specific gravity1.225 recommended above 95 F (35 C) ambient; 1.280 at 80 F (27 C)
OtherBattery specific gravity (high ambient, above 95F/35C)1.225recommended to reduce electrolyte loss
OtherBattery specific gravity (recharge threshold)below 1.260
OtherBattery specific gravity, fully chargedapproximately 1.260specific gravityat 80 F (27 C)
OtherBreather cleaning compressed air30psimaximum (OSHA)
OtherControl circuit wire size, distance 1000 to 2000 ft (305 to 610 m)16gauge stranded copper
OtherControl circuit wire size, distance less than 1000 ft (305 m)18gauge stranded copper
OtherCool-down at idle timer range0 to 30minutes
OtherCooling air inlet size relative to radiator duct outlet1-1/2times largerradiator cooled models
OtherCycle cranking option15-second crank, 15-second rest, 3 cycles
OtherEngine belt driven charging alternator output35ampere, 24 VDC
OtherFuel lift height limit6feet(1.8 meters) between fuel lift pump and bottom of dip tube
OtherFuel pump lifting capacity5 feet (1.525 m)feet
OtherFuel pump maximum lift5ft (1.5 m)
OtherFuel tank capacity for continuous full load operation36hoursminimum
OtherGOV GAIN default value for paralleling applications70%
OtherLoad balance line current tolerance10percent of median valuewith loads connected
OtherMaximum cranking voltage drop2voltsdifference between battery and starter terminals while cranking
OtherMaximum sulphated ash content of lubricating oil1.85percent
OtherMounting base surface above floor6inches (152 mm)minimum for servicing
OtherMounting bolt size3/4inchanchored to floor
OtherOver/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal55Hzreset 53 Hz
OtherOver/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal65Hzreset 63 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal45Hzreset 47 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal55Hzreset 57 Hz
OtherOver/Under Voltage Sensor Module time delaytypically 25 percent, approximately 2.5seconds
OtherOvercrank crank cycle15 seconds crank / 15 seconds rest, 80-second limitseconds
OtherOvercrank cranking limit75secondsthree 15-second cranking cycles with two 15-second rest periods
OtherOvercrank cranking limit (standard control)75seconds
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherRated To Idle delay range0 to 10secondsdefault = 0; Beginning Version 2.303
OtherStart Delay setting range0 to 300secondsdefault = 0
OtherStart delay adjustment range0 to 300seconds
OtherStop Delay setting range0 to 600secondsdefault = 0
OtherStop delay adjustment range0 to 600seconds
OtherUnder Frequency Roll Off (UFRO) knee point, 50 Hz units48 to 49Hz
OtherUnder Frequency Roll Off (UFRO) knee point, 60 Hz units58 to 59Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantBalanced coolant mixture of water, antifreeze and coolant additives; refer to Cummins engine Operation and Maintenance ManualGensets are shipped with coolant added. Check coolant level before initial start.
CoolantEthylene glycol base permanent antifreezePrecharge coolant filter compatible with plain water and ethylene glycol base coolants; refer to engine manufacturer for methoxy propanal base antifreeze.
CoolantWater/antifreeze mixture precharged with Diesel Coolant Additive (DCA)Engine manufacturer's coolant requirements; do not use antifreeze with anti-leak additives62.0 LStandard radiator capacity 16.5 gallons (62 L) for 275 DFBF
CoolantWater/antifreeze mixture with DCAPermanent type antifreeze per supplier proportion; water clean, low mineral content, free of chloride, sulphate or acid; do not use anti-leak additive antifreeze15.5 U.S. GalCooling system with standard set mounted radiator; engine only capacity 5.0 U.S. Gal (19 Litres) for NT models, 5.5 U.S. Gal (20.8 Litres) for NTA/NTTA models
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
Engine oilAPI Class CC/CD42.0 quartsOil capacity with filters (all models)
Engine oilSAE 5W grade syntheticAPI class CC/CD; sulphated ash max 1.85 percent; pour point 9 F (5 C) below lowest expected temperature; viscosity 10,000 mPa.s max at -31 F (-35 C) and 4.1 mm2/s min at 212 F (100 C)below -25°CFor ambient consistently below -13 F (-25 C) with no provision to keep engine warm. Do not use petroleum base 5W.
Engine oilSAE 5W syntheticAPI Class CC/CD; pour point 9 F (5 C) below lowest expected temperature; viscosity 10,000 mPa-s max at -31 F (-35 C) and 4.1 mm2/s min at 212 F (100 C)below -25°CExtreme cold: consistently below -13 F (-25 C) with no provision to keep engine warm
Engine oilSAE 20W-40API Class CC/CD, maximum sulphated ash 1.85 percentabove -32°C10.5 U.S. GalPrinted as 'Normal duty -32 F (0 C) and above - SAE 20W-40'. Refer to Cummins Engine Manual for extreme conditions. Do not mix oils of another classification or brand.
Engine oil10W-30Multigrade oil meeting API classification-25°C to 25°COil viscosity grade selection table: -13 to 95 F (-25 to 25 C) = 10W-30
Engine oilSAE 10W-30API Class CC/CD, max 1.85% sulphated ash-23°C to -10°CTable 5-2; Specification section lists 10W-30 for -13 F to 95 F (-25 C to 35 C)
Engine oilSAE 15W-40API Class CC/CD, max 1.85% sulphated ashabove -10°CTable 5-2: 14 F (-10 C) and above; Specification section: -14 F (-10 C) and above
FuelDiesel fuelDo not use zinc coated or copper fuel lines with diesel fuel. Fuel connection at the engine should be made with an approved flexible line.
FuelASTM No. 2 DieselAlternate diesel fuels allowed within engine manual specifications. Do not use galvanized or copper lines, fittings or fuel tanks.
FuelASTM No. 2 Diesel Engine FuelRefer to Cummins Engine Manual for analysis limits; will also operate on No. 1 or similar diesel fuelsNever use galvanized fuel lines, fittings or fuel tanks
FuelASTM No. 2 diesel fuelASTM No. 2Cummins engines normally use ASTM No. 2 diesel fuel; they will operate on alternate diesel fuels within the specifications shown in the Cummins engine Operation and Maintenance Manual. Never use galvanized or copper fuel lines, fittings or fuel tanks.
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
FuelNo. 2 Diesel Fuel; Bio-Diesel B5-B20 approved with recommendationsASTM D975 (post-storage purge fuel)Bio-diesel not recommended for Emergency Standby RV use (low annual hours, critical start nature).
FuelNo. 2 diesel (No. 1 acceptable)Filter or strain fuel as tank is filled; keep tanks full to avoid condensation
FuelNumber 2 diesel fuelDirect injection fuel system
GreaseLithium based greaseMobilux No. 2 or Shell Alvania R32.74 oz (81 ml)Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity.
GreaseLithium based-30°C to 120°C81.0 mlMobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.WarningRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPLocal or remote Emergency Stop.ShutdownTurn the switch clockwise and allow it to pop out (local only); move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can be reset only at the PCC front panel.
1122Rated/Idle Trans
1123Shutdown After BSShutdown fault occurred while Battle Short was enabled and then disabled.ShutdownReview Fault History and perform corrective action.
1124Delayed ShutdownShutdown fault became active while Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131Battle Sh ActiveControl is in Battle Short mode.WarningBypasses several critical fault shutdowns for emergency operation.
121Speed Signal LostMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on the digital display.
1311Customer Input #1The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure, etc.Enable/disable input (Default: enable); Status, Warning or Shutdown (Default: #1-None, #2 thru #4-Warning); Active closed or open (Default: closed [ground]); change display name up to 19 characters (Default: #1-Customer Fault 1).
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.WarningCheck external wiring and active input (closed/open) selection.
1312Customer Input #2Default display name: Ground Fault.Configurable input; defaults #2 thru #4 = Warning.
1317Customer Input #3Default display name: Low Fuel.Configurable input; defaults #2 thru #4 = Warning.
1318Customer Input #4Default display name: Rupture Basin Fault.Configurable input; defaults #2 thru #4 = Warning.
1334Crit Scaler ORIncorrect feature or calibration entered into control.ShutdownReload correct calibration.
1335Noncrit Scaler ORIncorrect feature or calibration entered into control.WarningReload correct calibration.
1337No Message
135Oil Pressure Sensor HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires.
141Oil Pressure Sensor LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires.
1416Fail To ShutdownGenset continues to run after shutdown command.WarningCheck Battle Short feature enabled condition.
1417Powr Down ErrorIndicates that the controller can not power down because of some unknown condition. Possible drain on battery.WarningContact an authorized service center for service.
143Pre-Low Oil PresIndicates engine oil pressure has dropped to an unacceptable level. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.WarningIf powering critical loads and cannot be shut down, wait until next shutdown period and follow code 415 procedure.
1433Emergency StopLocal Emergency Stop.ShutdownTo reset: pull the button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required.
1434Remote E-StopRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435Low Coolant TempWarning occurs when engine coolant temperature is 70°F (21°C) or lower. In applications where the ambient temperature falls below 40°F (4°C), Low Coolant Temp may be indicated even though the coolant heaters are operating.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check that coolant heater is connected to power supply (check for blown fuse or disconnected heater cord). Check for low coolant level and replenish if required; look for possible coolant leakage points and repair as required.
1438Fail To CrankIndicates possible fault with control, speed sensing or starting system.ShutdownSee code 441 for corrective action.
144Coolant Sensor HighEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires.
1442Weak BatteryIndicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time.WarningSee code 441 for corrective action.
1443Battery FailedDead battery - engine will not start.ShutdownSee code 441 for corrective action.
1444KW OverloadGenerator output power exceeded 105% of genset rating.WarningCheck load and load lead connections; check CTs.
1445Short CircuitGenerator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
1446High AC VoltageOne or more phase voltages exceeded 130% of nominal.ShutdownCheck fault simulation, load removal, threshold settings, Base board/generator.
1447Low AC VoltagePhase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck overload, output terminal connections, PMG/field wiring, rectifier diodes.
1448Under FrequencyEngine speed dropped below 90% of nominal for 10 seconds.ShutdownCheck fuel supply, intake air supply and load.
1449Over FrequencyFrequency is 10% above base frequency for 20 seconds.WarningCheck fuel or air delivery; check connections.
145Coolant Sensor LowEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires.
1452Gen CB Not CloseGenset circuit breaker (S2) failed to close when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1453Gen CB Not OpenGenset circuit breaker (S2) failed to open when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1459Reverse PowerImproper CT phasing.ShutdownCheck wiring to voltage sense circuit; refer to CT Installation in Section 6.
146Pre-High Coolant TempIndicates engine has begun to overheat (coolant temperature has risen to an unacceptable level).WarningReduce load; check air inlets/outlets; follow code 151 if engine can be stopped.
1461Loss Of FieldLoss of field (electric) due to reverse kVAR.ShutdownCheck excitation circuit.
1466Modem FailureControl cannot communicate with the modem.WarningCheck for open, short to ground and loose connections to the modem.
1468Network ErrorMomentary loss of communication from the LonWorks Network.WarningRefer to LonWorks Network publications.
1469Speed/Hz MatchMeasured speed and measured AC output frequency do not agree.ShutdownCheck calibration file.
1471Over CurrentGenerator output current exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
1472Over CurrentOutput current exceeded 110% of rated and time/current calculation initiated shutdown.ShutdownCheck load and load lead connections.
151High Coolant TempIndicates engine has overheated (coolant temperature has risen above the shutdown trip point). Allow engine to cool down completely before proceeding.ShutdownCheck coolant level and replenish if low; look for coolant leakage points and repair. Check for obstructions to cooling airflow. Check fan belt and repair or tighten if necessary. Check blower fan and circulation pumps on remote radiator installations. Reset control and restart after correcting problem.
197Low Coolant LevelIndicates engine coolant level has fallen below the warning trip point (optional).WarningIf powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf powering critical loads, wait until next shutdown period then follow 201 procedure.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart; contact service center.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected. Contact service center.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReduce load; check air inlets/outlets and remove obstructions.
212Oil Temp Sensor HIndicates engine has overheated (coolant temperature has risen above the shutdown trip point: 215 F (102 C) - standby or 207 F (97 C) - primary).WarningCheck sender/connectors/wires.
213Oil Temp Sensor LResistance of the coolant temperature sender is out of range.WarningContact an authorized service center.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCheck coolant level in radiator and coolant recovery bottle; replenish if low; look for leaks.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownAllow engine to cool; check coolant level and replenish; look for leaks and repair; reset and restart. Shutdown will not occur in Idle mode.
220MAG PICKUPMag pickup speed indication not sensed or does not match generator set output frequency.ShutdownRestart and check RPM; check PCC model setting; inspect and test MPU.
221FAIL TO CRANKPossible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board; check battery cable connections; recharge or replace the battery.
222OVERCRANKPossible fuel system problem.ShutdownCheck for empty fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filter; reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed. (115% ±1% of nominal).ShutdownContact an authorized service center.
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningLower battery charger float level if applicable; check engine DC alternator.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningSee Warning message 230, LOW DC VOLTAGE.
2327PTC FaultPTC module or communication link is not working properly.WarningCheck PTC module power, ground shield, cycle control power.
2329Low S1 FrequencyLow utility (S1) frequency.WarningCheck S1 AC inputs and wiring to PTC at TB5; check sensor set points.
2331Low S1 VoltageLow utility (S1) voltage.WarningCheck S1 AC inputs and wiring to PTC at TB5; check pickup/dropout set points.
2335Excitation FaultLoss of all three voltage sense leads or failure in excitation circuit.ShutdownCheck field wiring (X1 and X2) for shorts or opens.
2336Memory ErrorControl memory error; data corruption of critical operating parameters.ShutdownTry reloading calibration file.
2337Pwr Tran DisabledPTC module available but PTC feature not enabled.WarningEnable PTC feature with InPower; cycle control power.
2338Pwr Tran FailureControl could not communicate with the PTC module.WarningCheck PTC module power and cable ground shield; cycle control power.
2339Pwr Down EnabledPower Down (sleep) enabled but PTC module or network board is active.WarningNone required.
234OverspeedEngine has exceeded normal operating speed.ShutdownCheck for large block load removal, flammable vapors or leaking turbocharger seals.
2341High Control TempControl temperature above 158 F (70 C) for longer than set time.WarningCheck genset room air flow.
2342Too Long In Idle (10 min.)Indicates genset has been in Idle mode too long (10 minutes maximum).WarningExit idle mode.
235Low Coolant LevelIndicates engine coolant level has fallen below the shutdown trip point (optional). Allow engine to cool down completely before proceeding.ShutdownCheck coolant level and replenish if low; reset control.
2358High S1 VoltageUtility (S1) voltage increased above the over-voltage threshold.WarningMeasure S1 AC inputs at PTC module; check sensor set points.
2396S1 CB Not CloseUtility contact (S1) failed to close with PTC enabled.WarningRefer to Section 5 troubleshooting charts.
2397S1 CB Not OpenUtility contact (S1) failed to open with PTC enabled.WarningRefer to Section 5 troubleshooting charts.
240LOW FUEL−DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting Values/Parameters (PCC Adjust Menu) adjustment
  1. Press the button next to the arrow symbol in the display until the + and - symbols are displayed.
  2. If necessary, press the button next to the arrows to move to the numeric character to change.
  3. Press + to increase the value or select the parameter; press - to decrease the value or select the parameter.
  4. Press the save symbol to save changes; changes are not saved if Home or Previous Main Menu is pressed first.
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

Tools: Dial indicator, Wooden shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Record maximum positive and negative dial indicator readings as the engine completes one revolution.
  5. T.I.R. equals the sum of the maximum positive and negative readings.
  6. Maximum T.I.R. should not be more than .001 inch for each inch of radius.
  7. Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (750 kW Gensets and Larger) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

⚠ Do not bar engine over by prying on fan blade.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan, with the sensing point on the capscrew head or drive disc flat surface at bolt circle diameter.
  3. Bar the engine over clockwise as viewed from the engine flywheel; do not allow it to roll back on compression.
  4. Total indicator reading (T.I.R.) is the sum of the maximum positive and negative readings as the engine completes one revolution.
  5. To lower the generator, remove equal shims from under both generator mounting feet; approximate shim amount from the distance ratio.
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure adjustment

Tools: Dial indicator, Magnetic base or clamp

  1. Check axial alignment only when an objectionable vibration is present after angular alignment.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with a magnetic base or clamp; rest sensor on generator shaft hub.
  3. Bar the engine over clockwise through a couple of rotations; record indicator readings at eight equally spaced points around the shaft diameter.
  4. To correct out-of-tolerance T.I.R., remove the drive disc capscrews, mark discs and flywheel, rotate 180 degrees from original location, retorque, and recheck.
  5. If unchanged, rotate the discs to 30, 60 or 90 degrees from their original location.
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Electric Governor Preliminary Adjustment adjustment

Tools: Frequency meter or tachometer

  1. Idle Speed potentiometer: turn counterclockwise 20 turns, then clockwise 10 turns (mid position).
  2. Run Speed potentiometer: turn counterclockwise 20 turns, then clockwise 10 turns (mid position).
  3. Gain potentiometer: turn screw fully counterclockwise.
  4. Droop potentiometer: fully counterclockwise for isochronous, approx. 40 for 3 percent droop, approx. 80 for 5 percent droop.
Governor Calibration Checks adjustment

Tools: Frequency meter or tachometer, Jumper wire

  1. Start the generator set.
  2. Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
  3. With no load, turn GAIN clockwise slowly until engine speed oscillates.
  4. Reduce GAIN slowly counterclockwise until engine speed is stable.
  5. Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
  6. Apply and remove loads to check generator set response.
Governor Gain Adjustment adjustment

Tools: Frequency meter or tachometer

  1. Close main line circuit breaker and apply approximately 1/4 of rated load.
  2. Make sure engine speed is constant.
  3. Turn Gain potentiometer clockwise slowly until engine speed is not constant.
  4. Slowly turn potentiometer counterclockwise until constant speed is achieved.
  5. Turn potentiometer counterclockwise an additional 1/2 division.
HC4-7 Axial Alignment Procedure adjustment

Tools: Dial indicator with magnetic base or clamp

  1. Check only when an objectionable vibration is present.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
  3. Position sensor point on the generator shaft hub.
  4. Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
  5. Record indicator readings in eight equally spaced points around the shaft diameter.
  6. Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
  7. Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
  8. Put capscrews back in and retorque. Recheck shaft alignment.
  9. If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
  10. If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
  1. Check only when an objectionable vibration is present.
  2. Remove the capscrews connecting drive discs and flywheel.
  3. Mark the drive discs and flywheel with respect to each other.
  4. Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
  5. Put capscrews back in and retorque. Recheck/record vibration levels.
  6. Repeat this test until drive disc holes are repositioned 180 degrees from original location.
  7. Review vibration data and position drive disc in lowest recorded level location.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
110 V - 120 V L-N1Single phase, 2-wirePTC module jumper locations
110/1903Wye12-lead generator
110/2201Double delta (single phase)12-lead generator
115/2003Wye12-lead generator
115/2301Double delta (single phase)12-lead generator
120/2083Wye12-lead generator
120/2401Double delta (single phase)U1, V1, W1, U2, V2, W2, U5, V5, W5, U6, V6, W6Single phase, double delta connection will reduce set rating and may not work with 3-phase meters
127/2203Wye12-lead generator
139/2403Wye12-lead generator
190 V - 240 V L-L3Three phaseUse PTC module 0300-5382-01; 50/60 Hz
200 V - 240 V L-L1Single phase, 3-wirePTC module jumper locations
200/3463Wye12-lead generator
220/3803Wye (High/Low Wye)12-lead generator60 Hz and 50 Hz listed
230/4003Wye12-lead generator60 Hz and 50 Hz listed
240/4163Wye12-lead generator60 Hz and 50 Hz listed
254/4403Wye12-lead generator60 Hz and 50 Hz listed
277/4803Wye12-lead generator
380 V - 600 V L-L3Three phaseUse PTC module 0300-5382-02; 50/60 Hz
Medium voltage (601V to 15kV)36 lead generator6-lead generatorDrawing number 3052056 (sht. 2) pertains to medium voltage, 6 lead generators, where applicable

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan NTA855 family

51
Part #DescriptionCategory
122-0526Bypass Hood, Air Inlet (Used on Heavy Duty Air Cleaner)Air filter
140-1346Air Cleaner (Includes Element)Air filter
140-2391Element - Air Cleaner (Standard)Air filter
140-2392Element, Air Cleaner - PrimaryAir filter
140-2393Element, Air Cleaner - SafetyAir filter
511-0084Belt, Charging AlternatorBelt
511-0160Belt, Drive - V (Fan)Belt
319-2236Bracket, MountingBracket
518-0548-58Clamp, HoseClamp
130-3537CE 1 130-3541 3318318 CE 1 4 501-0551 1 5 503-1467-07 1 503-0189 2 505-0022 1 502-0827Coolant filter
130-3541Filter, Water - w/Corrosion Inhibiting Chemical DCA4 (Pre-Charging)Coolant filter
0300-4623-09DFCB (600V)Current transformer
0300-4623-10DFCC (600V)Current transformer
0300-4623-24DFCB BR (0-480V)Current transformer
0300-4623-27DFCC BR (0-480V)Current transformer
155-2287-02Gasket, Flange (used with 155-2281 Elbow)Gasket
501-0551Line, Fuel - Flexible (Bypass line)Hose
503-1467-07Hose, Rubber (3/4" ID x 33" LG) Radiator to Filter HousingHose
503-1679-02Hose, Rubber - UpperHose
505-1414-01Hose, Rubber - LowerHose
122-0755Lube & Bypass Filter (Latest Style Used In Engine Manufacturing)Oil filter
LF3000Lube, Spin-OnOil filter
100-1359Engine, Replacement (Cummins NTA855G)Service part / kit
102-1335Plug, Oil DrainService part / kit
305-0813-02CUMMINS battery charger 208VAC/24VDC/10AService part / kit
307-2621-02Relay, Start Solenoid (K4)Service part / kit
309-0437(222"F)Service part / kit
504-0011Valve, Shutoff (1/2”)Service part / kit
505-0019Bushing, Pipe - Reducer 1/2” to 3/8”, DFBF (1/2” to 3/8”) 505-0131 DFCB, DFCC, DFCE (3/4” to 3/8”)Service part / kit
505-0100Nipple, Pipe - Close (1/2”)Service part / kit
526-0029*Washer, Flat (1/2")Service part / kit
526-0219Washer, Flat (1/2)Service part / kit
800-0048Screw, Cap - Hex Head (3/8-16 x 3/4”)Service part / kit
800-0092Screw, Cap - Hex Head (1/2-13 x 1.5)Service part / kit
850-0050Washer, Lock - Spring (3/8”)Service part / kit
870-0212Nut, Locking (1/4-20)Service part / kit
903-0124NAService part / kit
903-0204NAService part / kit
903-0500NAService part / kit
903-0604NAService part / kit
E204747Coolant heater 240/480V 6420W 1PHService part / kit
508-0292Washer, Sealing - CopperSeal
151-0411Pickup, MagneticSensor
193-0244Sender, Pressure - 0i1Sensor
193-0375# Sender, Water TemperatureSensor
193-0432Sender, Oil Temperature (S2 Engine Block, E4 Oil Pan)Sensor
309-0179Switch, High Water TemperatureSensor
309-0269Sender, Temperature-Lo EngineSensor
333-0407Switch, Pressure - Oil, 14# PSI (SHUTDOWN) With Dual TerminalsSensor
960-0504PCC Control Service ManualService manual
960-0507Detector Control Service ManualService manual

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan NTA-855-G2?

The Cummins/Onan NTA-855-G2 engine has an oil capacity of 31.0 liters.

What is the displacement of the Cummins/Onan NTA-855-G2?

The Cummins/Onan NTA-855-G2 has a displacement of 14.0 liters with 6 cylinders.

Which generators use the Cummins/Onan NTA-855-G2 engine?

The Cummins/Onan NTA-855-G2 powers 8 generator set(s), including Cummins/Onan 300 DFCB, Cummins/Onan 300DFCB-2272, Cummins/Onan 300NTA2, Cummins/Onan DBCB, Cummins/Onan DFCB.

What is a common problem with the Cummins/Onan NTA-855-G2 engine?

A commonly reported issue on generators using the Cummins/Onan NTA-855-G2 is: No AC output voltage.. Fix: 3. Confirm that Exciter Switch is at ON position. Voltage regulator is inoperative. Refer to Initial Start and Checks, and Adjustments sections for voltage check and adjustment procedures. Contact your distributor if voltage build-up is still a problem..