HomeEnginesCummins/Onan HDKAS

Cummins/Onan HDKAS Engine

The Cummins/Onan HDKAS is a 0.9 L 3-cylinder liquid-cooled engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the HDKA. It holds 4.5 L (1.2 gal) of oil and 4.73 L (1.2 gal) of coolant.

Also known as: Cummins HDKAS

0.898 L
Displacement
3
Cylinders
1800 rpm
Rated speed
4.5 L
Oil capacity

Engine specifications

Oil capacity4.5 L
Coolant capacity4.73 L
Displacement0.898 L
Cylinders3
AspirationLiquid-cooled
Rated speed1800 rpm

Troubleshooting

4

Symptoms & remedies

SymptomCauseRemedy
NO AC OUTPUT VOLTAGE AT RATED ENGINE RPMLoad circuit breakers closed, overload in the load circuit, open circuit between brush block and voltage regulator, brushes stuck or not making good contact with slip rings, opens or grounds in rotor or stator, incorrect field voltage, wrong connections of F1 and F2 leadsLocate cause of overload and correct as required. Reset breaker, or replace if bad. Check continuity of circuit breakers and replace if necessary. Is circuit open between brush block and voltage regulator? Check for continuity and correct if circuit is open. Are brushes stuck in holder or not making good contact with slip rings? Release brushes if jammed in holder. Clean slip rings if dirty. Test continuity of rotor, stator per Tests [B], [C]. Are there opens or grounds? Replace component if defective. Test field voltage per TEST [A]. Is there correct field voltage? Examine brush block connections. Are F1 and F2 leads installed on correct terminals? Perform TEST [D]. Connect brush leads to correct terminals.
UNSTABLE OUTPUT VOLTAGE, ENGINE SPEED STABLEBroken wires or loose connections on voltage regulator assembly, brushes not OKAre there any broken wires or loose connections on voltage regulator assembly? Check wiring harness from regulator assembly to end bell per TEST [F]. Check OK? Repair as required. Inspect brushes per procedure in Manual Section 4. Brushes OK? Repair wiring or replace as required.
Engine does not crank.Is battery dead? Check CB11 circuit breaker. If okay, jumper battery cable B+ connection to B1 starter so- lenoid terminal. Does engine crank? With S11 in Start position, is battery voltage present between K11 terminal S and ground? If K11 does not energize, test per Checkout [D] and replace if bad. Is battery voltage present at B1 solenoid terminal with S11 in Start position? Check battery per Checkout [A] and recharge or replace. Check battery charger operation per Checkout [C]. Check battery cables for clean tight connections (ref. Checkout [B]). Check B1 starter so- lidoid and motor: if bad, repair or replace. Check B+ wiring to S11, and between S11 and K11. Check NC contacts of A11-K15. Replace if bad.
Unbalanced generator set output voltageRemove load at generator set terminals. Are generator set leads connected and grounded properly? See Test [C]. Is generator set stator winding continuous per TEST [C]? Check load for ground faults and correct as necessary. Check for correct grounding of generator set and load. Correct as necessary. Replace stator assembly.

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing.

Common problems

15
  • Weakness and Sleepiness
    Fix: IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
  • Vomiting
    Fix: IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
  • Voltage Sense Code 27
  • UNSTABLE OUTPUT VOLTAGE, ENGINE SPEED STABLE
    Cause: Broken wires or loose connections on voltage regulator assembly, brushes not OK
    Fix: Check wiring harness from regulator assembly to end bell per TEST [F]. Inspect brushes per procedure in Manual Section 4. Repair as required.
  • Under Voltage Code 13
  • Under Frequency Code 15
  • Unbalanced generator set output voltage
    Fix: Remove load at generator set terminals. Are generator set leads connected and grounded properly? See Test [C]. Is generator set stator winding continuous per TEST [C]? Check load for ground faults and correct as necessary. Check for correct grounding of generator set and load. Correct as necessary. Replace stator assembly.
  • UNBALANCED GENERATOR OUTPUT VOLTAGE
    Cause: Generator leads not connected and grounded properly, generator stator winding not continuous
    Fix: Remove load at generator terminals. Check if generator leads are connected and grounded properly per TEST [C]. Test generator stator winding continuity.
  • The indicator light in the Start/Stop switch turns off
    Fix: Confirm that the correct connection diagram (Figures 5 - 7) was used, then check EC 30 wiring connections. Confirm that the correct voltages are present on each terminal. Check all terminal connections on both ends of the wiring harness. Are harness connectors properly joined?
  • The genset stops
    Fix: Does the genset operate correctly from the genset controls? If it does not, the problem is in the genset, not the EC-20 controller. See the genset Operator, Installation, and Service Manuals.
  • STATUS INDICATOR LIGHT STAYS ON
    Cause: Reversed battery connections
    Fix: Corrective Action: Reconnect the battery correctly (Page 17).
  • STATUS INDICATOR LIGHT DEAD
    Cause: Faulty connections, no battery voltage
    Fix: 1. Try the genset Start Switch if the remote Start Switch does not work, and vice versa. 2. Replace Fuse F1 (B+) if blown (Page 7). 3. Clean and tighten the positive (+) and negative (−) battery cable connections at the battery, vehicle frame and genset (Page 17). 4. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations.
  • STARTING BATTERIES RUN DOWN
    Cause: (Marginal battery, battery connections, or charging system; or parasitic loads)
    Fix: 1. Clean and tighten the positive (+) and negative (−) battery cable connections at the battery, vehicle frame and genset (Page 17). 2. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations.
  • STARTER ENGAGES-DISENGAGES
    Cause: (Cranking voltage dips below 6 volts—low battery charge, poor connections, long cables)
    Fix: 1. Have the vehicle propulsion engine running while trying to start the genset—the battery charging alternator may be able to maintain starting voltage high enough to get the genset started. 2. Clean and tighten the positive (+) and negative (−) battery cable connections at the battery, vehicle frame and genset (Page 17). 3. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations. 4. Increase battery cable size or run parallel cables.
  • Shutdown due to high engine coolant temperature blink-blink-blink-pause-blink-blink-blink-blink-blink-blink-long pause-repeat

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan HDKAS.

Service intervals

40
ItemActionHoursMonthsNotes
Air cleaner dust capCheck50 hrClean if required; footnote 3: perform more often in extremely dusty conditions
Air cleaner dust capClean8 hrClean if required; perform more often in extremely dusty conditions (table footnote 3)
Coolant levelCheck8 hrKeep recovery tank level between COLD and HOT
Engine oilCheck8 hrDaily or after 8 hours
Engine oil levelCheck8 hr0 moKeep oil level between FULL and ADD
Fuel levelCheck8 hrDaily or after 8 hours
Generator setInspect8 hrFootnote 1: check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running
GensetInspect8 hrCheck for oil, fuel, coolant and exhaust system leaks
Oil LevelCheck8 hrEvery Day / 8 Hr per Table 7-1
Battery charging systemCheck100 hrWeekly or after 50 hours
Battery specific gravityCheck100 hrWeekly or after 50 hours
Drive belt tensionCheck100 hrVisually check belts for evidence of slippage (table footnote 4)
Genset service (first service interval, all models)Other50 hrFirst service — First service interval is 50 hours for all models.
Air Cleaner Dust BootClean100 hr1 moPerform more often in dusty conditions (footnote 5)
Air cleaner elementClean100 hr
AntifreezeCheck250 hr6 moMonthly or after 100 hours
BatteryCheck100 hr1 moSee battery manufacturer's recommendations (footnote 2)
Fuel filter water/sedimentDrain250 hrMonthly or after 100 hours
Air Filter ElementReplace150 hrEvery 150 hours, more often in dusty conditions
Engine Oil and FilterChange1000 hrFirst service — Perform more often in dusty conditions; more often in hot weather; at least once a year
Genset service — GEN TYPE GAS RV (Camp Power)Other150 hrEC-30 service hour meter interval
Genset service — GEN TYPE GAS/LP (Marquis, Microlite, Micro Quiet)Other150 hrEC-30 service hour meter interval
Genset service — GEN TYPE QD 5.5 (Quiet Diesel; model HDKBx)Other150 hrEC-30 service hour meter interval
Genset service — GEN TYPE QD 6/8 (Quiet Diesel; model HDKAx)Other150 hrEC-30 service hour meter interval
genset serviceOther250 hrFirst service — GEN TYPE QD 7.5/8 (Quiet Diesel, HDKAx) Service IN hours
Anti-freezeCheck250 hr
Crankcase oil and filterChange250 hr6 moFirst service — Perform after first 35 hours of operation on new genset; change crankcase oil every 50 operating hours in extremely dusty conditions
Fuel filter elementChange500 hr12 mo6 months or after 250 hours
Fuel shut-off linkageCheck500 hr12 mo6 months or after 250 hours
Fuel tank sedimentDrain250 hr6 moFootnote 5: drain one cup of fuel to remove water and sediment
Generator assemblyClean250 hr6 moClean the generator set at least every six months
Generator set brushesCheck250 hr6 moBrushes inspected for wear and cleaning every six months
Genset service — GEN TYPE QD 10/12 (Quiet Diesel; models HDCAx, HDKCx)Other250 hrEC-30 service hour meter interval
V-Belt TensionCheck250 hr6 moCheck for slippage (footnote 3)
Water in FuelDrain250 hr6 moDrain about one cup to remove water and sediment (footnote 4)
Water/sediment from fuel filterDrain250 hr6 mo
Air Cleaner ElementChange500 hr12 moPerform more often in dusty conditions (footnote 5)
Coolant Anti-freeze ProtectionCheck1000 hr1 moPerform at least once a year
Coolant Anti-freeze ProtectionTest500 hrCheck Coolant Anti-freeze Protection
Cooling systemClean500 hr12 moOnce a year drain, flush and refill the cooling system with new coolant

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceBore2.64 inch (67 mm)inch (mm)
ClearanceClearance to top of genset compartment1inch (25.4 mm)minimum, including acoustic insulation
ClearanceCompartment opening free area, generator end200square inchesminimum
ClearanceExhaust system distance from combustible material3in
ClearanceFan belt deflection0.4 (10 mm)inch22 pounds (10 kg) finger pressure at middle of belt
ClearanceGenset to bulkhead/other equipment (pusher/suction fan)6inches (152 mm)minimum
ClearanceMinimum clearance between genset and compartment insulation1in
ClearanceMinimum clearance exhaust system to combustible material3in
ClearanceMinimum space between engine exhaust components and compartment insulation3in
ClearanceMuffler/tailpipe to combustible material3inches (76 mm)minimum, unless insulated or shielded
ClearanceStroke2.68 inch (68 mm)inch (mm)
ClearanceV-belt deflection0.4inch (10 mm)20 pounds (10 kg) applied at middle of pulley span
ClearanceV-belt deflection at 20 pounds (10 kg) applied to middle of pulley span0.4 inch (10 mm)inchat 20 lbs (10 kg)
CurrentBattery charging DC alternator output30amp
CurrentStarter motor draw at 12 VDC100A
GapFan belt deflection0.4inch (10 mm)22 pounds (10 kg) finger pressure at middle of belt
GapFan belt deflection at middle of belt0.4inch (10 mm)finger pressure of 22 pounds (10 kg)
OtherAUTO GEN disabled if safety input not verified30days
OtherActuator speed control lever stop screw (beginning Spec B)Turn in until just makes contact, then one more full turn (rotor not in place); set locknutAdjust whenever a different actuator base assembly is installed
OtherAltitude power derateapproximately 3 percent per 1000-foot (305 m) increase in elevationpercent
OtherBattery cable size, total cable length 0 to 10 feet (0 to 3 m)2AWGtemperatures down to –20°F (–29°C)
OtherBattery cable size, total cable length 11 to 15 feet (3 to 4.5 m)0AWGtemperatures down to –20°F (–29°C)
OtherBattery cable size, total cable length 16 to 20 feet (4.5 to 6 m)000AWGtemperatures down to –20°F (–29°C)
OtherBattery compartment ventilation opening1.7in2minimum at top and bottom
OtherBattery compartment ventilation opening11cm2minimum at top and bottom
OtherBattery electrolyte specific gravity (fully charged)1.260at approximately 80°F (27°C)
OtherBattery electrolyte specific gravity, charge if below1.215specific gravity
OtherBattery electrolyte specific gravity, fully charged1.260specific gravityat 80 F (27 C)
OtherBattery rating425CCA
OtherBattery rating625CCAbelow 32°F (0°C)
OtherBattery recharge threshold (charge if specific gravity less than)1.215specific gravity
OtherBattery specific gravity charge threshold1.215charge battery if specific gravity is less than this
OtherBore2.64inch (67 mm)
OtherBore2.99 (76) for HDKAL/HDKAQ; 2.83 (72) for HDKAR/HDKASin (mm)
OtherBore72mm
OtherBore76mm
OtherBrush wear limit (wire inserted into brush holder)1inch (25 mm)replace brush and spring if wire enters holder this far or more
OtherCircuit breaker rating35A2 pole, 60 Hz
OtherClamping screw (beginning Spec B high-idle adjustment)Run back in by hand until snug, back it out 1-1/2 turns, set lock nutturnsAfter setting high-idle speed
OtherCompartment depth25in
OtherCompartment height25in
OtherCompartment width38.4in
OtherCompression Ratio23 : 1
OtherCompression ratio23 to 1
OtherCompression ratio23:1
OtherContinuous operation at up to 80 percent of maximum power6000watts80% of maximum power
OtherCooling air requirement - Generator Inlet100in2
OtherCooling air requirement - Radiator200in2
OtherCooling system capacity4.2 quart (4 l)quart (l)includes coolant recovery tank
OtherCooling system capacity4.73L
OtherCranking time that triggers fault35secondscranking time exceeded fault (4 blinks)
OtherCranking time that trips fault code 435seconds
OtherCyclic horizontal forces±500lbs±1 g-force
OtherCyclic vertical forces±1500lbs±3 g-force
OtherDimensions L x W x D80.98 x 130.12 x 30.48mm (3.188 x 5.125 x 1.20 inches)
OtherDisplacement1001cm3
OtherDisplacement44inch3 (719 cc)
OtherDisplacement44 inch3 (719 cc)inch3 (cc)
OtherDisplacement898cm3
OtherEC-AGS+ gateway dimensions120 x 108 x 38mm

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 ethylene glycol antifreeze and water4.2 quarts (4 liters)Provides protection to -34°F (-37°C). Use distilled water if available. Replace every 2 years.
Coolant50/50 mixture ethylene glycol anti-freeze and waterContains rust and corrosion inhibitor; no stop-leak additiveabove -37°C4.0 l4.2 quart (4 l) capacity; suitable down to -34 F (-37 C)
Coolant50/50 mixture of ethylene glycol anti-freeze and waterReliable brand with rust and corrosion inhibitor; must not contain stop-leak additiveabove -37°C50/50 provides freeze protection to -34 F (-37 C); use distilled or soft water
Coolant50/50 mixture of ethylene glycol anti-freeze and water as shipped; use ethylene or propylene glycol anti-freeze solution containing rust and corrosion inhibitorAnti-freeze must not contain a stop-leak additive; water must be clean, low in minerals and free of corrosive chemicals; use distilled water if availableabove -37°C4.0 lFactory fill suitable down to -34 deg F (-37 deg C); cooling system capacity 4.2 quart (4 l) includes coolant recovery tank; replace coolant every two years
Coolant50/50 mixture of ethylene glycol anti-freeze and water; ethylene or propylene glycol solution containing rust and corrosion inhibitorNo stop-leak additive; use clean, low-mineral water, distilled if availableabove -37°C4.0 lSuitable for temperatures down to -34° F (-37° C); cooling system capacity 4.2 quart (4 l) including coolant recovery tank; replace coolant every two years
Coolant50/50 mixture of ethylene glycol antifreeze and waterabove -37°C4.0 lSuitable for temperatures down to –37 °C (–34 °F); antifreeze should be fully formulated with rust inhibitors and coolant stabilizers, mixed with fresh (distilled) water
Coolant50/50 mixture of water and ethylene glycolabove -37°CBest quality ethylene or propylene glycol antifreeze fully formulated with rust inhibitors and coolant stabilizers, but not stop-leak additives. Use fresh water low in minerals; distilled water is best. Shipped 50/50 mixture good for -34 F (-37 C).
Coolant50/50 mixture of water and ethylene glycol (or propylene glycol) antifreezeFully formulated with rust inhibitors and coolant stabilizers but not with stop-leak additives; use fresh water low in minerals, distilled bestabove -37°C4.73 LShipped with recommended 50/50 mixture, good for -34 F (-37 C); cooling system capacity 1.25 gal (4.73 L)
CoolantEthylene or propylene glycol anti-freeze, 50/50 mixtureabove -34°C4.2 quartMust contain rust and corrosion inhibitor; no stop-leak additives
CoolantEthylene glycol antifreeze, fully formulated with rust inhibitors and coolant stabilizersabove 37°C4.0 l (4.2 qt) incl. recovery tank50/50 mixture recommended for all climates
Engine oilCH-4, CG-4, or CF-4API performance class3.0 quarts (2.6 liters)May be combined with SJ, SH, or SG. Select viscosity grade per Chart 1 based on ambient temperature.
Engine oilSAE 15W-40 multi-grade recommended for year-round useAPI Class CF-4 or CF or better4.7 LPre-start checks state engine oil capacity 4.7 liters (5 quarts); Specifications state lubricating oil capacity with oil filter 6.0 liters (6.34 quarts). Choose viscosity grade per ambient temperature before next oil change.
Engine oilSAE 15W-40 multi-grade recommended for year-round use (choose viscosity grade per ambient temperature chart, Figure 2)API Class CG-4, CF-4, CF or better4.1 LLube oil capacity 4.34 qt (4.1 L) including filter
Engine oilSAE viscosity grade chosen from Chart 1 (Oil Viscosity vs. Temperature) for ambient temperatures expected until next oil changeAPI performance Class CH-4, CG-4 or CF-4, may be in combination with SJ, SH or SG (e.g. CH-4/SJ)2.6 l3 quart (2.6 l) with filter
Engine oilSAE viscosity grade per Chart 1 (Oil Viscosity vs. Temperature)API CH-4, CG-4 or CF-4 (may combine with SJ, SH or SG)2.6 l3 quarts (2.6 l) capacity with filter
Engine oilSAE viscosity grade per Chart 4-1 (oil viscosity vs. temperature)API performance Class CH-4, CG-4 or CF-4D, may be combined with SJ, SH or SG (e.g. CH-4/SJ)2.6 lOil capacity with filter 3 quart (2.6 l)
Engine oilSAE viscosity grade per engine lubrication sectionAPI classification per engine lubrication sectionRefer to Engine Workshop Manual for oil recommendation
Engine oilSAE viscosity grade selected per anticipated ambient temperature (Chart 1, Oil Viscosity vs. Temperature)API performance Class CH-4, CG-4 or CF-4, may be in combination with performance Class SJ, SH or SG (e.g. CH-4/SJ)3.0 quart (2.6 l)Oil capacity with filter; change oil if not appropriate for ambient temperatures during break-in
Engine oilSAE viscosity per anticipated ambient temperature (Table 1, Oil Viscosity vs. Temperature)API classification CC and later4.26 liters (4.5 quarts)Do not use synthetic oil or non-detergent oil. Do not mix different brands of oil. (Specifications section lists lube oil capacity 4.5 qt (4.25 L) including filter.)
Engine oilPerformance Class CH-4, CG-4 or CF-4-40°C to 40°C3.0 quartSelect SAE grade based on ambient temperature; see oil viscosity chart
Engine oilAPI Class CH-4, CG-4, or CF-4SAE viscosity grade based on ambient temperatureabove -34°C2.6 lSee Chart 1 for viscosity selection by temperature
Engine oil5W-30API CF, CF-4, CG-4, CH-4, or CI-4-28°C to 10°C
Engine oil10W-30 10W-40API CF, CF-4, CG-4, CH-4, or CI-4-18°C to 27°C
Engine oil15W-40 (OnaMax)API CF, CF-4, CG-4, CH-4, or CI-4-12°C to 38°CMultigrade oils such as SAE 15W-40 are recommended for year round use
Engine oilSAE 30API CF, CF-4, CG-4, CH-4, or CI-4above 0°C0 °C (32 °F) and higher
Engine oil10W-30 / 10W-40API CF/CF-4/CG-4/CH-4/CI-418°C to 27°C2.6 l (3 qt)
FuelASTM D975 (petroleum diesel); ASTM D7467 (B5-B20 blend); ASTM D6751 or EN14214 (bio-diesel component)B5 bio-diesel suitable. Up to B20 requires: HDKAL at Spec G or higher, vehicle engine B20-capable, OEM-installed B20-compatible fuel line and water separator. Blend properties change below 23 F (-5 C). Purge with pure ASTM D975 diesel for min 30 minutes before storage >90 days.
Fuel1-D DieselASTM D975below 0°CUse when ambient temperatures are below 32°F (0°C) and during long periods of light engine load
Fuel2-D DieselASTM D975Minimum Cetane number 45; best economy and performance under most conditions
FuelASTM 1-D (No. 1 Diesel)minimum Cetane number 45below 0°CUse when ambient temperatures are below 32°F (0°C) and during long periods of light engine load.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

42
CodeNameMeaningSeverityAction
1High engine coolant temperatureOne blink indicates shutdown due to high engine coolant temperature.ShutdownTouch Stop to check the second-level fault code; it will be either No. 33 or No. 34.
1, 2, 3, 4First level faultsFirst-level faults; avoid interpreting as second-level codes 11, 22, 33, or 44ShutdownPay close attention to the pause sequence
11Overload FaultSecond-level shutdown code No. 11 (blink once, pause, blink once). Not assigned a first-level fault (avoid confusion with first-level Code 1).ShutdownTurn off the genset line circuit breaker; if the genset no longer shuts down, check for and repair a short in vehicle appliances, wiring or shorted battery charger transformer; check whether vehicle engine and genset share the same starting battery and increase battery capacity or install a separate battery.
12Over VoltageThe control is unable to maintain rated voltage.ShutdownIf the vehicle engine and genset share a starting battery, increase battery capacity or install a separate battery and charging system for the genset.
13Under VoltageThe control is unable to maintain rated voltage.ShutdownReduce load (especially air conditioners and battery chargers).
14Over FrequencyThe engine governor is unable to maintain rated frequency.ShutdownReduce the number of connected appliances, especially when air conditioners and battery chargers are running.
15Underfrequency FaultThe engine governor is unable to maintain rated frequency.ShutdownReduce the number of connected appliances; have air conditioners and other appliances checked for proper operation (a locked compressor rotor can cause very low power factor).
17Fuel Pump FaultController sensed open circuit; bypassable fault prior to Spec F, discontinued beginning Spec FShutdownTry priming by holding control switch at Stop; reconnect fuel pump leads; test pump on 12 V battery; check P1-2/E2-1 and E2-2/ground continuity.
18Glow Plug Circuit Protection FaultController sensed short circuit; bypassable fault prior to Spec F, discontinued beginning Spec FShutdownReconnect HR-1 to glow plug bus bar; check HR-1 and A1-J8 for ground short; replace engine harness or control assembly.
19Governor Actuator FaultThe control sensed an open or shorted circuit.ShutdownSee an authorized Onan dealer.
2Low Oil Pressure (first-level fault)Two blinks indicate shutdown due to a loss of engine oil pressure; oil pressure switch actuates below 9 psi (62 kPa)ShutdownCheck oil level; check switch and wiring; replace switch or service engine if pressure <14 psi (98 kPa).
21Starter Solenoid Circuit Protection FaultController sensed short circuit; discontinued beginning Spec FShutdownReconnect K-1 to starter solenoid; test solenoid and starter; reconnect A1-J6; check continuity to ground; replace controller assembly.
22Not assignedThe duration of operation is near full-duty cycle beyond design limit.WarningStep 01 (0.5 hr): check load, air intake restriction, exhaust restriction, air leak in fuel system, stator for opens/shorts. Step 02 (1.0 hr): check fuel flow test, governor for binding, high idle adjustment, injectors, injection pump timing, compression (SRT 00-0BL)
23Low Oil Pressure Cutoff Switch FaultSwitch still open during start - not a running faultShutdownSee an authorized Onan dealer.
24Throttle Control FaultEngine throttle control malfunctionShutdownSee an authorized Onan dealer.
25Engine Sensor FaultGovernor unable to regulate to target speed.ShutdownSee an authorized Onan dealer.
26Engine Below Speed Target FaultGovernor unable to regulate to target speed.ShutdownStep 01 (0.5 hr): check loads, air in fuel system, air intake restriction, exhaust restriction. Step 02 (1.0 hr): check binding in the governor, high idle speed, injectors, injection timing, compression (SRT 00-0BQ)
27Voltage SenseThe control is unable to sense output voltage.ShutdownTest with load bank to isolate load; check PMA-to-control connections; measure PMA lead voltages (T1-T2, T2-T3, T3-T1 - should exceed 20 Vrms); troubleshoot rotor/stator; replace control assembly.
28DC Sense Lost FaultController unable to sense DC bus voltageShutdownOpen the circuit breaker; if the fault does not persist, check for and disconnect excessive loads from the genset before starting.
29High Battery Voltage FaultVoltage across the battery system is greater than 19 Volts.WarningCheck battery connections; measure DC voltage; check battery charger; verify ground at P1-7.
3Service fault (second-level code follows)Three blinks indicate a service fault; press Stop once to blink the two-digit second-level shutdown code (tens digit, pause, units digit)WarningTouch Stop to check the second-level fault code; it will be one of the codes in the troubleshooting table.
31Overspeed FaultEngine speed greater than 3600 rpm.ShutdownSee an authorized Onan dealer.
32Low Cranking Speed FaultCranking speed less than 180 rpm for more than 2 seconds; crank and generator frequency less than 3 Hz for greater than 2 secondsShutdownStep 01 (0.3 hr): check fuse, harness connections to starter, battery connections at set and battery, battery voltage at set. Step 02 (0.7 hr): check starter operation, harness connection for opens/shorts, stator resistance for opens/shorts, rotor magnets for failure (SRT 00-0BS)
33Not assignedSecond-level code 33 has not been assigned a faultShutdownStep 01 (0.5 hr): verify FC is actually a secondary code; verify coolant level and fill if needed; verify engine coolant temperature; air inlet/outlet opening for blockage; excessive coach loads; coolant pump belt for wear; cooling fan for damage; housing air leaks. Step 02 (0.5 hr): check temperature sensor lead for opens/shorts; radiator blockage and clean. Step 03 (2.0 hr): clean and flush coolant system; replace coolant thermostat (SRT 00-0CS)
34High Inverter Temperature FaultInverter heat sink temperature exceeded design limit.ShutdownRemove objects blocking the air inlet or outlet openings; reduce the number of appliances connected at the same time.
35Control Card FaultMicroprocessor EPROM error during self-test.ShutdownVerify problem and report to factory (SRT 00-0CA, 0.2 hours)
36Unknown Shutdown FaultThe engine stopped without receiving a command from the control.ShutdownStep 01 (0.3 hr): check fuel level in coach tanks, prime genset fuel system, air filter blockage, mechanical damage. Step 02 (0.5 hr): check auxiliary fuel pump, conduct fuel flow test, P1 and P2 connectors and wiring (SRT 00-0BW)
37Invalid Genset Configuration FaultThe generator set control is not configured properly for the generator setShutdownVerify problem and report to factory (SRT 00-CHA, 0.2 hours)
38Overload FaultToo many loads connected.ShutdownStep 01 (0.2 hr): reduce coach loads, cool inverter. Step 02 (1.0 hr): check if set has engine performance issue, fuel supply for sucking air, fuel flow test, governor operates smoothly, high idle speed, current transformer for shorts/opens (SRT 00-0BX)
39Low Battery Voltage FaultPrior to Spec F onlyWarningInspect connections; check fuel/air leaks; avoid cranking propulsion engine; check battery voltage; replace/recharge battery.
4OvercrankSet cranked for 35 seconds without starting (speed >1200 RPM) (Begin Spec K)ShutdownTroubleshoot as an out-of-fuel condition (see FC36); check fuel flow and return, actuator operation, wiring.
4 blinksCranking time exceeded 35 secondsStatus indicator light repeatedly blinks four timesShutdownCheck fuel supply and priming before re-cranking
41Generator RotorControl unable to sense field or output voltageShutdownContact local dealer or distributor.
42Processor FaultMicroprocessor ROM error during self-test; beginning Spec F and replacement controller assembliesShutdownVerify fault code (SRT 00-0CB, 0.2 hours)
43Processor FaultMicroprocessor RAM error during self-test; beginning Spec F and replacement controller assembliesShutdownVerify fault code (SRT 00-0CC, 0.2 hours)
44Not assignedSecond-level code 44 has not been assigned a fault
45Speed SenseThe control is unable to sense quadrature frequency.ShutdownContact local dealer or distributor.
46Inverter Power Supply FaultLow battery voltage or power supply device failure; beginning Spec F and replacement controller assembliesShutdownVerify fault code, voltage at set during cranking, voltage at starter during cranking, battery connections at set and battery, battery condition, set charging system if equipped (SRT 00-0BZ, 0.5 hours)
48Generator Field SenseThe control is unable to sense field voltage.ShutdownContact local dealer or distributor.
57Over PrimePriming exceeded 3 minutes.ShutdownCheck for and remove any object holding either control switch in the STOP/PRIME position.
8Overload (Models HDKAH & HDKAV only)Starter or cranking circuit malfunctionShutdownReduce load and restart.
restoreRestoring fault code blinkingFault code stops blinking after five minutesInfoPress Stop three times within three seconds to restore fault code blinking

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting V-Belt Tension adjustment

⚠ Accidental starting can cause severe personal injury or death. Disconnect the negative (-) cable(s) at the battery(ies).

  1. Disconnect the negative (-) battery cable(s) to prevent the engine from starting and remove the top belt guard.
  2. Loosen the alternator pivot bolt first, then the adjusting bracket bolt on top.
  3. Tighten belt tension by pivoting the alternator outwards; hold tension by tightening the adjusting bracket bolt.
  4. Apply 20 pounds (10 kg) at the middle of the pulley span and measure deflection, which should be 0.4 inch (10 mm).
  5. Tighten the alternator bolts when tension is correct.
  6. Secure the belt guard and reconnect the battery cables (negative last).
Fan Belt Adjustment adjustment

⚠ Do not operate the generator set without the belt guard in place.

⚠ Stop the set and disable by disconnecting battery cables before service.

  1. Remove the generator set starting battery cables, negative cable first.
  2. Remove the belt guard from the front of the set.
  3. Loosen the bolt through the long slot in the alternator mounting bracket.
  4. Slide the alternator until the tension is correct.
  5. Check tension: 22 pounds finger pressure deflects belt 0.4 inch.
Governor Actuator Speed Control Lever Stop Adjustment (Spec B and later) adjustment
  1. Loosen the stop screw locknut and back the screw out a few turns.
  2. Turn the stop screw in until it just makes contact.
  3. Turn the screw 1 full turn further in and set the locknut (rotor not in place procedure).
  4. Alternatively with actuator in place: loosen set screw locknut, turn stop screw in until just makes contact, set locknut.
High-Idle Speed Adjustment adjustment

⚠ Do not let engine speed exceed 3600 RPM.

Tools: tachometer

  1. Remove front housing panel.
  2. Set up tachometer.
  3. Remove actuator cover and reattach leads.
  4. Start generator set and push actuator rotor clockwise fully (about 12 mm).
  5. Adjust high-idle speed to 3500-3600 RPM.
  6. For Spec A, adjust screw; for Spec B, adjust screws and set locknut.
  7. Let rotor go; generator should stop and display fault code.
  8. Restart and recheck high idle speed.
Setting GEN TYPE adjustment

⚠ GEN TYPE sets the service interval for service messages and critical automatic starting parameters.

  1. Navigate to the SETUP & INFO display and press ENTER.
  2. Navigate to the SETUP GENSET display and press ENTER; the GEN TYPE is displayed.
  3. Press SET; the display will flash.
  4. Use the UP/DOWN key to select the GEN TYPE and press ENTER when the appropriate type is displayed.
Setting Quiet Time (QT) Start & End adjustment

⚠ QUIET ON mode prohibits the genset from automatically starting between the start and end of Quiet Time.

  1. Use the UP/DOWN key to navigate to the QT START or QT END display; the current setting is shown.
  2. Press SET to change the setting.
  3. Use the UP/DOWN key to change the value.
  4. Press ENTER to store the new time.
Setting Safety Type adjustment

⚠ If it has not been setup (SafeType NONE), automatic operation will not be allowed.

  1. Use the UP/DOWN key to select the correct type of safety input: Ignition, Brake, or Park.
  2. Press ENTER to store in permanent memory.
Setting the Hour-Meter adjustment
  1. If the EC-20 is installed on an existing genset, check its hour-meter and record the reading.
  2. ENTER the SETUP & INFO menu and navigate to the SETUP GENSET display.
  3. Press ENTER and use the DOWN key to select the SET gen hours display.
  4. Press SET; the next display says ENTER to unlock; press ENTER to continue.
  5. Hold down UP/DOWN and scroll until the left most digit matches the desired value.
  6. Release UP/DOWN and wait four seconds for the underline to move to the next digit to the right, then scroll to its desired value.
  7. Set each successive digit to the right until the correct genset hours are displayed and press ENTER.
Setting the Hour-Meter (SET Gen Hour) adjustment

⚠ ENTER to unlock prevents unauthorized changes to the hour-meter.

  1. Check the hour-meter on the genset and record the reading.
  2. Enter the SETUP & INFO menu and navigate to the SETUP GENSET display; press ENTER.
  3. Use the DOWN key to select the SET Gen hour's display; press SET.
  4. Press ENTER at the ENTER to unlock display to continue.
  5. Hold down the UP/DOWN key and scroll until the left-most digit matches the desired value.
  6. Release the UP/DOWN key and wait four seconds for the underline to move to the next digit; scroll to its desired value.
  7. Set each successive digit to the right until the correct genset hours are displayed, then press ENTER to store.
Valves − Adjust, All adjustment
  1. Remove and install cover and panels, valve cover
  2. Adjust valve lash
  3. Test run unit
Voltage Adjustment adjustment

⚠ Touching uninsulated live parts can cause severe injury or death.

Tools: voltmeter

  1. Start generator set; allow voltage and frequency to stabilize 3-5 seconds.
  2. Rapidly press Start switch 6 times within first minute to enter voltage adjust mode.
  3. To increase: press and quickly release Start switch; each press increases about 0.6 volts.
  4. To decrease: press and hold Start switch about 1 second; each press decreases about 0.6 volts.
  5. Repeat until desired voltage.
  6. Wait 20 seconds for amber light to stop blinking.
  7. Press Stop switch to save adjustment.
Voltage Adjustment Procedure adjustment

⚠ Do not change the 50/60 Hz setting on the regulator.

⚠ The V/Hz Break Point pot is factory set and sealed; do not adjust.

Tools: flat-blade screwdriver, voltmeter

  1. Attach a voltmeter securely to the L1 and L2 leads.
  2. Start the generator set and place a typical load on its output.
  3. Use a flat-blade screwdriver to set the voltage adjust potentiometer for correct voltage.
  4. Retighten the locking nut when complete.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
AC Present + positive#14Positive input for shore AC present sensing; do not connect 120VAC or 240VAC line voltage.
AC Present - ground#13Supplied by UL Listed 120VAC to 12-16VAC transformer, or the 12VDC ground side of a UL Listed 120VAC to 12VDC plug-in power supply.
Battery ground (negative)#1Supplies the ground or negative side of the circuit for the EC-30; must be supplied from the genset.
Genset status light#6Diagnostic output that flashes the red light in the START/STOP switch to indicate a genset fault; decoded to a text fault message.
Start/preheat#3Supplies the start/preheat signal to the genset; controlled by the STOP/START switch and, in automatic mode, by the EC-30.
Stop output#2Active low or grounded output to the genset; controlled by the STOP/START switch and, in automatic mode, by the EC-30.
Switched B+ from genset#5Switched to battery positive voltage when the genset is running; provides genset hour meter and running indication.
singleQuadrature power connection Q60 - 60 Hz, Q50 - 50 Hz unitsQ1, Q50, Q60Note 2: Quadrature power connection Q60-60 Hz, Q50-50 Hz units. Note 3: AVR reference voltage. Note 1: From J2-15 for field flashing.
1001Reconnection chart
1001reconnection chart
100singlereconnection chartL0
100single-phase50 Hz; see reconnection chart
100single-phaseL0, L1T4, T3, L2, L1, Q50, Q60, T2, T1, S2, 2, S1, Q1
100/2001Reconnection chartWiring diagram 612-6637 reconnection chart
100/2001reconnection chart
100/200singleAs shownT1, T2, T3, T4; L0(N), L1100/200 volts only; stator resistance values differ (T1-T2, T3-T4: 0.150 ohm; Q1-Q60: 2.3 ohms)
100/200singlereconnection chartL0, L1
100/200single-phase50 Hz; see reconnection chart
100/200single-phaseL0(N), L1Q50, Q60, T2, T1, S2, 2, S1, Q150 Hz
1101reconnection chartT4, T3; L1
110single-phaseL0, L1T4, T2, T3, T1, L0
110/190350 HZ CODE ZT1-T12
110/2201As shownT1, T2, T3, T4See reconnection chart for other voltages
110/2201reconnection chartT4, T3, T2, T1; L2, L1, L0(N)
110/220350 HZ CODE M,P,ZT1-T12
110/220singleAs shown (60 Hz)T1, T2, T3, T4; L0(N), L1, L260 Hz
110/220singleSee reconnection chart (50 Hz)T1, T2, T3, T4; L0, L150 Hz
110/220singleas shownT4, T3, T2, T1, L0, L1See reconnection chart for other voltages
110/220single-phaseAs shown (L0(N), L1, L2)T1, T2, T3, T4, Q60, Q160 Hz
110/220single-phaseas shown

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Cummins/Onan HDKAS?

The Cummins/Onan HDKAS engine has an oil capacity of 4.5 liters.

What is the displacement of the Cummins/Onan HDKAS?

The Cummins/Onan HDKAS has a displacement of 0.898 liters with 3 cylinders.

Which generators use the Cummins/Onan HDKAS engine?

The Cummins/Onan HDKAS powers 1 generator set(s), including Cummins/Onan HDKA.

What is a common problem with the Cummins/Onan HDKAS engine?

A commonly reported issue on generators using the Cummins/Onan HDKAS is: Weakness and Sleepiness. Fix: IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired..